فيوكس إلكتريك
Language

RCBO من النوع Type AC طراز VRL7E

The VIOX VRL7E is an electronic Type AC RCBO for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N design combines residual-current, overload and short-circuit protection with 2-40 A ratings, B or C tripping characteristics and 10, 30 or 100 mA sensitivities. It provides a 4.5 kA short-circuit capacity and mounts on a standard 35 mm DIN rail.

التيار المقنن
2-40 A
التيار المتبقي
10, 30, 100 mA
تكوين العمود
1ص+ن
القدرة الاستيعابية
4.5 كيلو أمبير

نظرة عامة

The VIOX VRL7E is an electronic Type AC residual current circuit breaker with overcurrent protection for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N configuration combines residual-current, overload and short-circuit protection in one compact device. The Type AC detection system responds to sinusoidal alternating residual currents, while B and C thermomagnetic tripping characteristics support different circuit and load requirements. The RCBO is intended for residential, commercial and light industrial distribution boards and installs on a standard 35 mm DIN rail.

الميزات

  • Electronic Type AC residual-current detection.
  • Residual-current, overload and short-circuit protection.
  • 1P+N configuration for AC 230 V circuits.
  • B and C thermomagnetic release characteristics.
  • 4.5 kA rated short-circuit capacity.
  • مؤشر مدمج لتيار العطل.
  • 35 mm DIN-rail mounting with a fast-clip device.

المواصفات

البيانات الكهربائية

المعلمةالمواصفات
Operating ModeElectronic type
التيار المقنن2, 4, 6, 10, 16, 20, 25, 32, 40 A
تكوين العمود1ص+ن
الجهد التشغيلي المقدر230 V AC
التردد المقدر50/60 هرتز
جهد العزل المقدر250 V
الجهد المقدر لتحمل النبضات4 kV، 1.2/50 μs
جهد اختبار العزل الكهربائي2 kV لمدة دقيقة واحدة

بيانات الحماية

المعلمةالمواصفات
Residual-Current Typeنوع التكييف
Thermomagnetic Release Characteristicب، ج
تيار التشغيل المتبقي المقنن10, 30, 100 mA
قدرة الوصل والفصل للتيار المتبقي المقننة500 A
Rated Short-Circuit Capacity4.5 كيلو أمبير
Break Time at IΔn≤ 0.1 s
درجة التلوث2

البيانات الميكانيكية وبيانات التركيب

المعلمةالمواصفات
الحياة الكهربائية4,000 عملية تشغيل
الحياة الميكانيكية10000 عملية
Fault-Current Indicatorنعم
درجة الحمايةIP20
Terminal ConnectionCable / pin-type busbar / U-type busbar
Cable Terminal Capacity25 mm², AWG 18-5, top/bottom
Busbar Terminal Capacity25 mm², AWG 18-3, top/bottom
التركيب35 mm DIN rail to EN 60715; fast-clip device
Supply ConnectionFrom top

Environmental Data

المعلمةالمواصفات
درجة الحرارة المحيطة-5 °C to +40 °C; daily average ≤ 35 °C
درجة حرارة التخزين-25 °C to +70 °C

قياسي

المعلمةالمواصفات
قياسيIEC/EN 61009-1

دليل الاختيار

عنصر الكودالمعنىالقيم المتاحة
Vتعريف مؤسسة VIOXV
RLعائلة منتجات RCBORL
7Eسلسلة التصميم7E
منحنى الفصلمنحنى الفصل عند التيار الزائدB أو C
الحاليالتيار المقنن2-40 A
الحساسيةتيار التشغيل المتبقي المقنن10, 30 or 100 mA
القطبينOrdering designation2P in the catalog example
Example Modelالتكوين
VRL7E-B16-10B curve, 16 A, 10 mA
VRL7E-C20-30C curve, 20 A, 30 mA
VRL7E-C40-100C curve, 40 A, 100 mA

منحنى التعثر

Select a B or C thermomagnetic release characteristic according to the circuit and load requirements.

التيار المقنن

Select one of the listed ratings from 2 A to 40 A.

حساسية التيار المتبقي

Select a rated residual operating current of 10, 30 or 100 mA.

تكوين الدائرة

The technical specification identifies a 1P+N configuration for AC 230 V final distribution circuits.

منحنيات الرحلة

The VRL7E is available with B and C time-current tripping characteristics. The catalog provides time-current graphs for both curves and specifies a residual-current break time of no more than 0.1 seconds at IΔn.

Protection CharacteristicAvailable Option
Thermomagnetic ReleaseB or C curve
Residual-Current Break Time≤ 0.1 s at IΔn

الأبعاد

VRL7E Type AC RCBO dimensional drawing
VRL7E Type AC RCBO dimensional drawing.

التطبيقات

  • Residential final distribution boards.
  • Commercial final distribution circuits.
  • Light industrial distribution boards.
  • AC 230 V circuits requiring combined Type AC residual-current and overcurrent protection.

التركيب

  • Install on a 35 mm DIN rail conforming to EN 60715 using the fast-clip device.
  • Connect the supply from the top.
  • Use cable, pin-type busbar or U-type busbar connections as specified.
  • Observe the stated 25 mm² terminal capacity for cable and busbar connections.
  • Install within the specified ambient temperature range of -5 °C to +40 °C.

الأسئلة الشائعة

What residual-current type does the VRL7E use?

It uses electronic Type AC detection for sinusoidal alternating residual currents.

ما هي قيم تيارات التشغيل المقننة (In) المتاحة؟

The available ratings are 2, 4, 6, 10, 16, 20, 25, 32 and 40 A.

Which residual-current sensitivities are available?

The available rated residual operating currents are 10, 30 and 100 mA.

What is the VRL7E short-circuit capacity?

The rated short-circuit capacity is 4.5 kA.

How is the VRL7E installed?

It mounts on a 35 mm DIN rail conforming to EN 60715 and uses a fast-clip device. The supply connection is from the top.

هل تحتاج إلى عرض سعر للمنتج؟
لنبنيها معاً.

أرسل لنا طراز المنتج، والتقييمات الفنية، والكمية، ومتطلبات الشركة المصنعة للمعدات الأصلية (OEM). سيقوم فريقنا بمراجعة طلبك والرد في غضون يوم عمل واحد.

طلب عرض أسعار