VRL7E Type AC RCBO

The VIOX VRL7E is an electronic Type AC RCBO for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N design combines residual-current, overload and short-circuit protection with 2-40 A ratings, B or C tripping characteristics and 10, 30 or 100 mA sensitivities. It provides a 4.5 kA short-circuit capacity and mounts on a standard 35 mm DIN rail.

정격 전류
2-40 A
누전 전류
10, 30, 100 mA
폴 구성
1P+N
단 용량
4.5 kA

개요

The VIOX VRL7E is an electronic Type AC residual current circuit breaker with overcurrent protection for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N configuration combines residual-current, overload and short-circuit protection in one compact device. The Type AC detection system responds to sinusoidal alternating residual currents, while B and C thermomagnetic tripping characteristics support different circuit and load requirements. The RCBO is intended for residential, commercial and light industrial distribution boards and installs on a standard 35 mm DIN rail.

특징

  • Electronic Type AC residual-current detection.
  • Residual-current, overload and short-circuit protection.
  • 1P+N configuration for AC 230 V circuits.
  • B and C thermomagnetic release characteristics.
  • 4.5 kA rated short-circuit capacity.
  • 통합형 고장 전류 표시기.
  • 35 mm DIN-rail mounting with a fast-clip device.

사양

전기 데이터

매개변수사양
Operating ModeElectronic type
정격 전류2, 4, 6, 10, 16, 20, 25, 32, 40 A
폴 구성1P+N
정격 작동 전압230 V AC
정격 주파수50/60Hz
정격 절연 전압250 V
정격 임펄스 내전압4 kV, 1.2/50 μs
유전체 테스트 전압1분간 2 kV

보호 데이터

매개변수사양
잔류 전류 유형AC 유형
Thermomagnetic Release CharacteristicB, C
정격 잔류 동작 전류10, 30, 100 mA
정격 잔류 차단 및 투입 용량500 A
Rated Short-Circuit Capacity4.5 kA
Break Time at IΔn≤ 0.1 s
오염 정도2

기계 및 설치 데이터

매개변수사양
전기 수명4,000회 작동
기계 수명10,000회 작동
Fault-Current Indicator
보호 수준IP20
Terminal ConnectionCable / pin-type busbar / U-type busbar
Cable Terminal Capacity25 mm², AWG 18-5, top/bottom
Busbar Terminal Capacity25 mm², AWG 18-3, top/bottom
마운팅35 mm DIN rail to EN 60715; fast-clip device
Supply ConnectionFrom top

Environmental Data

매개변수사양
주변 온도-5 °C to +40 °C; daily average ≤ 35 °C
보관 온도-25 °C to +70 °C

매개변수사양
IEC/EN 61009-1

선택 가이드

코드 요소의미사용 가능한 값
VVIOX 기업 식별V
RLRCBO 제품군RL
7E설계 시리즈7E
곡선과전류 트립 곡선B 또는 C
현재정격 전류2-40 A
감도정격 감도 전류10, 30 or 100 mA
폴란드Ordering designation2P in the catalog example
Example Model구성
VRL7E-B16-10B curve, 16 A, 10 mA
VRL7E-C20-30C curve, 20 A, 30 mA
VRL7E-C40-100C curve, 40 A, 100 mA

트리핑 커브

Select a B or C thermomagnetic release characteristic according to the circuit and load requirements.

정격 전류

Select one of the listed ratings from 2 A to 40 A.

잔류 감도

Select a rated residual operating current of 10, 30 or 100 mA.

회로 구성

The technical specification identifies a 1P+N configuration for AC 230 V final distribution circuits.

트립 커브

The VRL7E is available with B and C time-current tripping characteristics. The catalog provides time-current graphs for both curves and specifies a residual-current break time of no more than 0.1 seconds at IΔn.

Protection CharacteristicAvailable Option
Thermomagnetic ReleaseB or C curve
Residual-Current Break Time≤ 0.1 s at IΔn

치수

VRL7E Type AC RCBO dimensional drawing
VRL7E Type AC RCBO dimensional drawing.

애플리케이션

  • Residential final distribution boards.
  • Commercial final distribution circuits.
  • Light industrial distribution boards.
  • AC 230 V circuits requiring combined Type AC residual-current and overcurrent protection.

설치

  • Install on a 35 mm DIN rail conforming to EN 60715 using the fast-clip device.
  • Connect the supply from the top.
  • Use cable, pin-type busbar or U-type busbar connections as specified.
  • Observe the stated 25 mm² terminal capacity for cable and busbar connections.
  • Install within the specified ambient temperature range of -5 °C to +40 °C.

자주 묻는 질문

What residual-current type does the VRL7E use?

It uses electronic Type AC detection for sinusoidal alternating residual currents.

사용 가능한 정격 전류는 어떻게 됩니까?

The available ratings are 2, 4, 6, 10, 16, 20, 25, 32 and 40 A.

Which residual-current sensitivities are available?

The available rated residual operating currents are 10, 30 and 100 mA.

What is the VRL7E short-circuit capacity?

The rated short-circuit capacity is 4.5 kA.

How is the VRL7E installed?

It mounts on a 35 mm DIN rail conforming to EN 60715 and uses a fast-clip device. The supply connection is from the top.

제품 견적이 필요하신가요?
함께 만들어 갑시다.

제품 모델, 기술 정격, 수량 및 OEM 요구 사항을 보내주십시오. 당사 팀에서 귀하의 애플리케이션을 검토한 후 영업일 기준 1일 이내에 답변해 드리겠습니다.