Ikhtisar
The VIOX VRL7E is an electronic Type AC residual current circuit breaker with overcurrent protection for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N configuration combines residual-current, overload and short-circuit protection in one compact device. The Type AC detection system responds to sinusoidal alternating residual currents, while B and C thermomagnetic tripping characteristics support different circuit and load requirements. The RCBO is intended for residential, commercial and light industrial distribution boards and installs on a standard 35 mm DIN rail.
Fitur
- Electronic Type AC residual-current detection.
- Residual-current, overload and short-circuit protection.
- 1P+N configuration for AC 230 V circuits.
- B and C thermomagnetic release characteristics.
- 4.5 kA rated short-circuit capacity.
- Indikator arus gangguan terintegrasi.
- 35 mm DIN-rail mounting with a fast-clip device.
Spesifikasi
Data Kelistrikan
| Parameter | Spesifikasi |
|---|---|
| Operating Mode | Electronic type |
| Nilai Saat Ini | 2, 4, 6, 10, 16, 20, 25, 32, 40 A |
| Konfigurasi Tiang | 1P + N |
| Nilai Tegangan Operasional | 230 V AC |
| Frekuensi yang dinilai | 50/60 Hz |
| Tegangan Isolasi Terukur | 250 V |
| Tegangan Impuls Tahan Terukur | 4 kV, 1.2/50 μs |
| Tegangan Uji Dielektrik | 2 kV selama 1 menit |
Data proteksi
| Parameter | Spesifikasi |
|---|---|
| Tipe Arus Sisa | Tipe AC |
| Thermomagnetic Release Characteristic | B, C |
| Arus operasi sisa terukur | 10, 30, 100 mA |
| Kapasitas Pemutusan dan Penyambungan Arus Sisa Terukur | 500 A |
| Rated Short-Circuit Capacity | 4.5 kA |
| Break Time at IΔn | ≤ 0.1 s |
| Tingkat Polusi | 2 |
Data Mekanis dan Pemasangan
| Parameter | Spesifikasi |
|---|---|
| Kehidupan Listrik | 4.000 operasi |
| Kehidupan Mekanis | 10.000 operasi |
| Fault-Current Indicator | Ya |
| Tingkat Perlindungan | IP20 |
| Terminal Connection | Cable / pin-type busbar / U-type busbar |
| Cable Terminal Capacity | 25 mm², AWG 18-5, top/bottom |
| Busbar Terminal Capacity | 25 mm², AWG 18-3, top/bottom |
| Pemasangan | 35 mm DIN rail to EN 60715; fast-clip device |
| Supply Connection | From top |
Environmental Data
| Parameter | Spesifikasi |
|---|---|
| Suhu Sekitar | -5 °C to +40 °C; daily average ≤ 35 °C |
| Suhu Penyimpanan | -25 °C to +70 °C |
Standar
| Parameter | Spesifikasi |
|---|---|
| Standar | IEC/EN 61009-1 |
Panduan Pemilihan
| Elemen Kode | Arti | Nilai yang Tersedia |
|---|---|---|
| V | Identifikasi perusahaan VIOX | V |
| RL | Keluarga produk RCBO | RL |
| 7E | Seri desain | 7E |
| Kurva | Kurva trip arus lebih | B atau C |
| Saat ini | Nilai saat ini | 2-40 A |
| Sensitivitas | Arus operasi sisa terukur | 10, 30 or 100 mA |
| Polandia | Ordering designation | 2P in the catalog example |
| Example Model | Konfigurasi |
|---|---|
| VRL7E-B16-10 | B curve, 16 A, 10 mA |
| VRL7E-C20-30 | C curve, 20 A, 30 mA |
| VRL7E-C40-100 | C curve, 40 A, 100 mA |
Kurva Tripping
Select a B or C thermomagnetic release characteristic according to the circuit and load requirements.
Nilai Saat Ini
Select one of the listed ratings from 2 A to 40 A.
Sensitivitas Sisa
Select a rated residual operating current of 10, 30 or 100 mA.
Konfigurasi Sirkuit
The technical specification identifies a 1P+N configuration for AC 230 V final distribution circuits.
Kurva Perjalanan
The VRL7E is available with B and C time-current tripping characteristics. The catalog provides time-current graphs for both curves and specifies a residual-current break time of no more than 0.1 seconds at IΔn.
| Protection Characteristic | Available Option |
|---|---|
| Thermomagnetic Release | B or C curve |
| Residual-Current Break Time | ≤ 0.1 s at IΔn |
Dimensi
Aplikasi
- Residential final distribution boards.
- Commercial final distribution circuits.
- Light industrial distribution boards.
- AC 230 V circuits requiring combined Type AC residual-current and overcurrent protection.
Instalasi
- Install on a 35 mm DIN rail conforming to EN 60715 using the fast-clip device.
- Connect the supply from the top.
- Use cable, pin-type busbar or U-type busbar connections as specified.
- Observe the stated 25 mm² terminal capacity for cable and busbar connections.
- Install within the specified ambient temperature range of -5 °C to +40 °C.
PERTANYAAN YANG SERING DIAJUKAN
What residual-current type does the VRL7E use?
It uses electronic Type AC detection for sinusoidal alternating residual currents.
Berapa arus pengenal yang tersedia?
The available ratings are 2, 4, 6, 10, 16, 20, 25, 32 and 40 A.
Which residual-current sensitivities are available?
The available rated residual operating currents are 10, 30 and 100 mA.
What is the VRL7E short-circuit capacity?
The rated short-circuit capacity is 4.5 kA.
How is the VRL7E installed?
It mounts on a 35 mm DIN rail conforming to EN 60715 and uses a fast-clip device. The supply connection is from the top.