VIOX Electric
Language

RCBO Tipe AC VRL7E

The VIOX VRL7E is an electronic Type AC RCBO for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N design combines residual-current, overload and short-circuit protection with 2-40 A ratings, B or C tripping characteristics and 10, 30 or 100 mA sensitivities. It provides a 4.5 kA short-circuit capacity and mounts on a standard 35 mm DIN rail.

Nilai Saat Ini
2-40 A
Arus Sisa
10, 30, 100 mA
Konfigurasi Tiang
1P + N
Kapasitas Putus
4.5 kA

Ikhtisar

The VIOX VRL7E is an electronic Type AC residual current circuit breaker with overcurrent protection for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N configuration combines residual-current, overload and short-circuit protection in one compact device. The Type AC detection system responds to sinusoidal alternating residual currents, while B and C thermomagnetic tripping characteristics support different circuit and load requirements. The RCBO is intended for residential, commercial and light industrial distribution boards and installs on a standard 35 mm DIN rail.

Fitur

  • Electronic Type AC residual-current detection.
  • Residual-current, overload and short-circuit protection.
  • 1P+N configuration for AC 230 V circuits.
  • B and C thermomagnetic release characteristics.
  • 4.5 kA rated short-circuit capacity.
  • Indikator arus gangguan terintegrasi.
  • 35 mm DIN-rail mounting with a fast-clip device.

Spesifikasi

Data Kelistrikan

ParameterSpesifikasi
Operating ModeElectronic type
Nilai Saat Ini2, 4, 6, 10, 16, 20, 25, 32, 40 A
Konfigurasi Tiang1P + N
Nilai Tegangan Operasional230 V AC
Frekuensi yang dinilai50/60 Hz
Tegangan Isolasi Terukur250 V
Tegangan Impuls Tahan Terukur4 kV, 1.2/50 μs
Tegangan Uji Dielektrik2 kV selama 1 menit

Data proteksi

ParameterSpesifikasi
Tipe Arus SisaTipe AC
Thermomagnetic Release CharacteristicB, C
Arus operasi sisa terukur10, 30, 100 mA
Kapasitas Pemutusan dan Penyambungan Arus Sisa Terukur500 A
Rated Short-Circuit Capacity4.5 kA
Break Time at IΔn≤ 0.1 s
Tingkat Polusi2

Data Mekanis dan Pemasangan

ParameterSpesifikasi
Kehidupan Listrik4.000 operasi
Kehidupan Mekanis10.000 operasi
Fault-Current IndicatorYa
Tingkat PerlindunganIP20
Terminal ConnectionCable / pin-type busbar / U-type busbar
Cable Terminal Capacity25 mm², AWG 18-5, top/bottom
Busbar Terminal Capacity25 mm², AWG 18-3, top/bottom
Pemasangan35 mm DIN rail to EN 60715; fast-clip device
Supply ConnectionFrom top

Environmental Data

ParameterSpesifikasi
Suhu Sekitar-5 °C to +40 °C; daily average ≤ 35 °C
Suhu Penyimpanan-25 °C to +70 °C

Standar

ParameterSpesifikasi
StandarIEC/EN 61009-1

Panduan Pemilihan

Elemen KodeArtiNilai yang Tersedia
VIdentifikasi perusahaan VIOXV
RLKeluarga produk RCBORL
7ESeri desain7E
KurvaKurva trip arus lebihB atau C
Saat iniNilai saat ini2-40 A
SensitivitasArus operasi sisa terukur10, 30 or 100 mA
PolandiaOrdering designation2P in the catalog example
Example ModelKonfigurasi
VRL7E-B16-10B curve, 16 A, 10 mA
VRL7E-C20-30C curve, 20 A, 30 mA
VRL7E-C40-100C curve, 40 A, 100 mA

Kurva Tripping

Select a B or C thermomagnetic release characteristic according to the circuit and load requirements.

Nilai Saat Ini

Select one of the listed ratings from 2 A to 40 A.

Sensitivitas Sisa

Select a rated residual operating current of 10, 30 or 100 mA.

Konfigurasi Sirkuit

The technical specification identifies a 1P+N configuration for AC 230 V final distribution circuits.

Kurva Perjalanan

The VRL7E is available with B and C time-current tripping characteristics. The catalog provides time-current graphs for both curves and specifies a residual-current break time of no more than 0.1 seconds at IΔn.

Protection CharacteristicAvailable Option
Thermomagnetic ReleaseB or C curve
Residual-Current Break Time≤ 0.1 s at IΔn

Dimensi

VRL7E Type AC RCBO dimensional drawing
VRL7E Type AC RCBO dimensional drawing.

Aplikasi

  • Residential final distribution boards.
  • Commercial final distribution circuits.
  • Light industrial distribution boards.
  • AC 230 V circuits requiring combined Type AC residual-current and overcurrent protection.

Instalasi

  • Install on a 35 mm DIN rail conforming to EN 60715 using the fast-clip device.
  • Connect the supply from the top.
  • Use cable, pin-type busbar or U-type busbar connections as specified.
  • Observe the stated 25 mm² terminal capacity for cable and busbar connections.
  • Install within the specified ambient temperature range of -5 °C to +40 °C.

PERTANYAAN YANG SERING DIAJUKAN

What residual-current type does the VRL7E use?

It uses electronic Type AC detection for sinusoidal alternating residual currents.

Berapa arus pengenal yang tersedia?

The available ratings are 2, 4, 6, 10, 16, 20, 25, 32 and 40 A.

Which residual-current sensitivities are available?

The available rated residual operating currents are 10, 30 and 100 mA.

What is the VRL7E short-circuit capacity?

The rated short-circuit capacity is 4.5 kA.

How is the VRL7E installed?

It mounts on a 35 mm DIN rail conforming to EN 60715 and uses a fast-clip device. The supply connection is from the top.

Butuh Penawaran Produk?
Mari Kita Bangun Bersama.

Kirimkan model produk, peringkat teknis, kuantitas, dan persyaratan OEM kepada kami. Tim kami akan meninjau aplikasi Anda dan merespons dalam satu hari kerja.

Minta Penawaran