Tổng quan
The VIOX VRL7E is an electronic Type AC residual current circuit breaker with overcurrent protection for AC 230 V, 50/60 Hz final distribution circuits. Its 1P+N configuration combines residual-current, overload and short-circuit protection in one compact device. The Type AC detection system responds to sinusoidal alternating residual currents, while B and C thermomagnetic tripping characteristics support different circuit and load requirements. The RCBO is intended for residential, commercial and light industrial distribution boards and installs on a standard 35 mm DIN rail.
Đặc trưng
- Electronic Type AC residual-current detection.
- Residual-current, overload and short-circuit protection.
- 1P+N configuration for AC 230 V circuits.
- B and C thermomagnetic release characteristics.
- 4.5 kA rated short-circuit capacity.
- Integrated fault-current indicator.
- 35 mm DIN-rail mounting with a fast-clip device.
Thông số kỹ thuật
Electrical Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Operating Mode | Electronic type |
| Bình Hiện Tại | 2, 4, 6, 10, 16, 20, 25, 32, 40 A |
| Cấu hình cực | 1P+N |
| Điện áp hoạt động định mức | 230 V AC |
| Tần số định mức | 50/60 Hz |
| Điện áp cách điện định mức | 250 V |
| Điện áp chịu xung định mức | 4 kV, 1.2/50 μs |
| Điện áp thử nghiệm điện môi | 2 kV for 1 minute |
Protection Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Residual-Current Type | Loại AC |
| Thermomagnetic Release Characteristic | B, C |
| Rated Residual Operating Current | 10, 30, 100 mA |
| Rated Residual Making and Breaking Capacity | 500 A |
| Rated Short-Circuit Capacity | 4.5 kA |
| Break Time at IΔn | ≤ 0.1 s |
| Mức độ ô nhiễm | 2 |
Mechanical and Installation Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Cuộc sống điện | 4,000 operations |
| Cuộc sống cơ học | 10.000 lần hoạt động |
| Fault-Current Indicator | Yes |
| Mức độ bảo vệ | IP20 |
| Terminal Connection | Cable / pin-type busbar / U-type busbar |
| Cable Terminal Capacity | 25 mm², AWG 18-5, top/bottom |
| Busbar Terminal Capacity | 25 mm², AWG 18-3, top/bottom |
| Lắp ráp | 35 mm DIN rail to EN 60715; fast-clip device |
| Supply Connection | From top |
Environmental Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Nhiệt độ môi trường | -5 °C to +40 °C; daily average ≤ 35 °C |
| Nhiệt độ lưu trữ | -25 °C to +70 °C |
Chuẩn
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Chuẩn | IEC/EN 61009-1 |
Hướng dẫn lựa chọn
| Code Element | Ý nghĩa | Available Values |
|---|---|---|
| V | VIOX enterprise identification | V |
| RL | RCBO product family | RL |
| 7E | Design series | 7E |
| Đường cong đặc tính | Đường cong tác động quá dòng | B hoặc C |
| Hiện hành | Dòng điện định mức | 2-40 A |
| Nhạy cảm | Dòng điện dư định mức khi vận hành | 10, 30 or 100 mA |
| Cực | Ordering designation | 2P in the catalog example |
| Example Model | Cấu hình |
|---|---|
| VRL7E-B16-10 | B curve, 16 A, 10 mA |
| VRL7E-C20-30 | C curve, 20 A, 30 mA |
| VRL7E-C40-100 | C curve, 40 A, 100 mA |
Đường cong vấp ngã
Select a B or C thermomagnetic release characteristic according to the circuit and load requirements.
Bình Hiện Tại
Select one of the listed ratings from 2 A to 40 A.
Residual Sensitivity
Select a rated residual operating current of 10, 30 or 100 mA.
Cấu hình mạch
The technical specification identifies a 1P+N configuration for AC 230 V final distribution circuits.
Đường cong chuyến đi
The VRL7E is available with B and C time-current tripping characteristics. The catalog provides time-current graphs for both curves and specifies a residual-current break time of no more than 0.1 seconds at IΔn.
| Protection Characteristic | Available Option |
|---|---|
| Thermomagnetic Release | B or C curve |
| Residual-Current Break Time | ≤ 0.1 s at IΔn |
Kích thước
Ứng dụng
- Residential final distribution boards.
- Commercial final distribution circuits.
- Light industrial distribution boards.
- AC 230 V circuits requiring combined Type AC residual-current and overcurrent protection.
Cài đặt
- Install on a 35 mm DIN rail conforming to EN 60715 using the fast-clip device.
- Connect the supply from the top.
- Use cable, pin-type busbar or U-type busbar connections as specified.
- Observe the stated 25 mm² terminal capacity for cable and busbar connections.
- Install within the specified ambient temperature range of -5 °C to +40 °C.
Câu hỏi thường gặp
What residual-current type does the VRL7E use?
It uses electronic Type AC detection for sinusoidal alternating residual currents.
What rated currents are available?
The available ratings are 2, 4, 6, 10, 16, 20, 25, 32 and 40 A.
Which residual-current sensitivities are available?
The available rated residual operating currents are 10, 30 and 100 mA.
What is the VRL7E short-circuit capacity?
The rated short-circuit capacity is 4.5 kA.
How is the VRL7E installed?
It mounts on a 35 mm DIN rail conforming to EN 60715 and uses a fast-clip device. The supply connection is from the top.