VRL22 Type A/AC/ASi RCBO

The VIOX VRL22 RCBO combines residual-current, overload and short-circuit protection for AC 50/60 Hz circuits. It supports 2-63 A rated currents, 10-500 mA residual-current options, B, C and D tripping curves, and 1P+N or 3P+N configurations. Type AC, A, ASi, A G and A S versions are available for residential, commercial and light industrial distribution systems.

Rated Current
2-63 A
Residual Current
10-500 mA
Pole Configuration
1P+N, 3P+N
Breaking Capacity
6 kA or 10 kA

Overview

The VIOX VRL22 is an electromagnetic, voltage-independent residual current circuit breaker with overcurrent protection. It combines residual-current, overload and short-circuit protection for AC 50/60 Hz circuits. Available configurations include Type AC, Type A, Type ASi, Type A G short-time-delayed and Type A S selective versions. The series covers 1P+N circuits at 230/240 V AC and 3P+N circuits at 400/415 V AC. It is intended for residential, commercial and light industrial distribution systems and may also be used for infrequent switching under normal operating conditions.

Features

  • Residual-current, overload and short-circuit protection in one device.
  • Electromagnetic, voltage-independent operating principle.
  • Type AC, A, ASi, A G short-time-delayed and A S selective options.
  • B, C and D overcurrent tripping curves.
  • Rated short-circuit breaking capacity of 6 kA or 10 kA.
  • Top or bottom power entry.
  • 5,000-cycle electrical and mechanical endurance.

Models

Model Configuration Maximum Rated Current Rated Voltage
VRL22 1P+N 63 A 230/240 V AC
VRL22-40 3P+N 40 A 400/415 V AC
VRL22-63 3P+N 63 A 400/415 V AC

Specifications

Electrical Data

ParameterSpecification
Rated Frame Current63 A
Rated Current2, 4, 5, 6, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63 A
Rated Voltage1P+N: 230/240 V AC; 3P+N: 400/415 V AC
Rated Frequency50/60 Hz
Rated Impulse Withstand Voltage4 kV
Operating PrincipleElectromagnetic, voltage-independent

Protection Data

ParameterSpecification
Residual-Current TypesType AC; Type A; Type ASi; Type A G short-time-delayed; Type A S selective
Rated Residual Operating Current10 mA for 1P+N up to 32 A only; 30, 100, 300, 500 mA
Rated Residual Non-Operating Current5 mA for 1P+N up to 32 A only; 15, 50, 150, 250 mA
Tripping CurvesB: 3-5 In; C: 5-10 In; D: 10-20 In
Rated Short-Circuit Breaking Capacity6 kA or 10 kA; energy-limiting class 3 for B and C curves
Rated Residual Making and Breaking Capacity3,000 A

Mechanical Data

ParameterSpecification
Pole Configuration1P+N; 3P+N
Electrical Endurance5,000 operating cycles
Mechanical Endurance5,000 operating cycles
Power EntryTop or bottom

Standards

ParameterSpecification
Applicable StandardsIEC/EN 61009-1; AS/NZS 61009.1; OVE E 8601 for Type A G short-time-delayed versions

Selection Guide

Code ElementMeaningAvailable Values
VVIOX enterprise identificationV
RLRCBO product familyRL
22Design series22
Residual TypeResidual-current typeAC, A, ASi, AG or AS
CurveOvercurrent tripping curveB, C or D
CurrentRated current2-63 A
SensitivityRated residual operating current10, 30, 100, 300 or 500 mA
PolesNumber of poles2P or 4P ordering designation

Catalog configuration example: V-RL-22-A-C-32A-30mA-1P+N

Residual Type

Select Type AC, A, ASi, A G short-time-delayed or A S selective according to the required residual-current response.

Rated Current

Select one of the listed current ratings from 2 A to 63 A, observing the 40 A limit of the VRL22-40 model.

Residual Sensitivity

Select 10, 30, 100, 300 or 500 mA. The 10 mA option is limited to 1P+N models rated up to 32 A.

Poles and Voltage

Use 1P+N for 230/240 V AC circuits or 3P+N for 400/415 V AC circuits.

Trip Curves

Test CurrentSpecified TimeResultApplicable Curve
1.13 Int ≥ 1 hNon-trippingB, C
1.45 Int < 1 hTrippingB, C
2.55 In1 s < t < 60 sTrippingB, C
3 Int ≥ 0.1 sNon-trippingB
5 Int < 0.1 sTrippingB
5 Int ≥ 0.1 sNon-trippingC
10 Int < 0.1 sTrippingC

The catalog lists D-curve availability but provides detailed instantaneous test criteria only for B and C curves.

At IΔnAt 2 IΔnAt 5 IΔnAt IΔt
0.1 s0.05 s0.04 s0.04 s

Applications

  • Residential distribution boards.
  • Commercial building electrical distribution.
  • Light industrial distribution systems.
  • Industrial installations requiring combined residual-current and overcurrent protection.

Installation

  • Match the 1P+N or 3P+N configuration to the circuit voltage and conductor arrangement.
  • Use either top or bottom power entry according to the distribution-board layout.
  • Observe the model-specific current limit when selecting VRL22, VRL22-40 or VRL22-63.

FAQ

What protection functions does the VRL22 provide?

It combines residual-current, overload and short-circuit protection.

Which residual-current types are available?

The catalog lists Type AC, Type A, Type ASi, Type A G short-time-delayed and Type A S selective versions.

What rated currents are available?

Rated-current options extend from 2 A to 63 A, with model-specific limits for the 3P+N versions.

Which residual-current sensitivities can be selected?

Available ratings are 10, 30, 100, 300 and 500 mA. The 10 mA option is limited to 1P+N models up to 32 A.

What is the available short-circuit breaking capacity?

The VRL22 is available with a rated short-circuit breaking capacity of 6 kA or 10 kA.