Επισκόπηση
The VIOX VRL22 is an electromagnetic, voltage-independent residual current circuit breaker with overcurrent protection. It combines residual-current, overload and short-circuit protection for AC 50/60 Hz circuits. Available configurations include Type AC, Type A, Type ASi, Type A G short-time-delayed and Type A S selective versions. The series covers 1P+N circuits at 230/240 V AC and 3P+N circuits at 400/415 V AC. It is intended for residential, commercial and light industrial distribution systems and may also be used for infrequent switching under normal operating conditions.
Χαρακτηριστικά
- Residual-current, overload and short-circuit protection in one device.
- Electromagnetic, voltage-independent operating principle.
- Type AC, A, ASi, A G short-time-delayed and A S selective options.
- B, C and D overcurrent tripping curves.
- Rated short-circuit breaking capacity of 6 kA or 10 kA.
- Τροφοδοσία από την άνω ή την κάτω πλευρά.
- 5,000-cycle electrical and mechanical endurance.
Μοντέλα
| Μοντέλο | Διαμόρφωση | Maximum Rated Current | Ονομαστική τάση |
|---|---|---|---|
| VRL22 | 1P+N | 63 A | 230/240 V AC |
| VRL22-40 | 3P+N | 40 A | 400/415 V AC |
| VRL22-63 | 3P+N | 63 A | 400/415 V AC |
Προδιαγραφές
Ηλεκτρικά δεδομένα
| Παράμετρος | Προδιαγραφές |
|---|---|
| Ονομαστικό Ρεύμα Πλαισίου | 63 A |
| Ονομαστικό ρεύμα | 2, 4, 5, 6, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63 A |
| Ονομαστική τάση | 1P+N: 230/240 V AC; 3P+N: 400/415 V AC |
| Ονομαστική συχνότητα | 50/60 Hz |
| Ονομαστική τάση αντοχής ώθησης | 4 kV |
| Αρχή λειτουργίας | Electromagnetic, voltage-independent |
Δεδομένα προστασίας
| Παράμετρος | Προδιαγραφές |
|---|---|
| Residual-Current Types | Type AC; Type A; Type ASi; Type A G short-time-delayed; Type A S selective |
| Rated Residual Operating Current | 10 mA for 1P+N up to 32 A only; 30, 100, 300, 500 mA |
| Rated Residual Non-Operating Current | 5 mA for 1P+N up to 32 A only; 15, 50, 150, 250 mA |
| Καμπύλες απόζευξης | B: 3-5 In; C: 5-10 In; D: 10-20 In |
| Ονομαστική ικανότητα διακοπής βραχυκυκλώματος | 6 kA or 10 kA; energy-limiting class 3 for B and C curves |
| Rated Residual Making and Breaking Capacity | 3,000 A |
Μηχανικά δεδομένα
| Παράμετρος | Προδιαγραφές |
|---|---|
| Διαμόρφωση πόλου | 1P+N; 3P+N |
| Ηλεκτρική αντοχή | 5,000 operating cycles |
| Μηχανική αντοχή | 5,000 operating cycles |
| Είσοδος ισχύος | Επάνω ή κάτω |
Πρότυπα
| Παράμετρος | Προδιαγραφές |
|---|---|
| Εφαρμοστέα Πρότυπα | IEC/EN 61009-1; AS/NZS 61009.1; OVE E 8601 for Type A G short-time-delayed versions |
Οδηγός επιλογής
| Code Element | Σημασία | Available Values |
|---|---|---|
| V | Κωδικός αναγνώρισης επιχείρησης VIOX | V |
| RL | RCBO product family | RL |
| 22 | Σειρά σχεδιασμού | 22 |
| Residual Type | Τύπος διαφορικού ρεύματος | AC, A, ASi, AG or AS |
| Καμπύλη | Overcurrent tripping curve | B, C ή D |
| Τρέχον | Ονομαστικό ρεύμα | 2-63 A |
| Ευαισθησία | Ονομαστικό διαφορικό ρεύμα λειτουργίας | 10, 30, 100, 300 or 500 mA |
| Πολωνοί | Αριθμός πόλων | 2P or 4P ordering designation |
Παράδειγμα διαμόρφωσης καταλόγου: V-RL-22-A-C-32A-30mA-1P+N
Residual Type
Select Type AC, A, ASi, A G short-time-delayed or A S selective according to the required residual-current response.
Ονομαστικό ρεύμα
Select one of the listed current ratings from 2 A to 63 A, observing the 40 A limit of the VRL22-40 model.
Ευαισθησία υπολειπόμενου ρεύματος
Select 10, 30, 100, 300 or 500 mA. The 10 mA option is limited to 1P+N models rated up to 32 A.
Πόλοι και τάση
Use 1P+N for 230/240 V AC circuits or 3P+N for 400/415 V AC circuits.
Καμπύλες ταξιδιού
| Ρεύμα δοκιμής | Specified Time | Αποτέλεσμα | Applicable Curve |
|---|---|---|---|
| 1.13 Σε | t ≥ 1 h | Non-tripping | B, C |
| 1.45 In | t < 1 h | Σκοντάρισμα | B, C |
| 2.55 In | 1 s < t < 60 s | Σκοντάρισμα | B, C |
| 3 In | t ≥ 0.1 s | Non-tripping | B |
| 5 In | t < 0.1 s | Σκοντάρισμα | B |
| 5 In | t ≥ 0.1 s | Non-tripping | C |
| 10 In | t < 0.1 s | Σκοντάρισμα | C |
The catalog lists D-curve availability but provides detailed instantaneous test criteria only for B and C curves.
| At IΔn | At 2 IΔn | At 5 IΔn | At IΔt |
|---|---|---|---|
| 0.1 s | 0.05 s | 0.04 s | 0.04 s |
Εφαρμογές
- Residential distribution boards.
- Commercial building electrical distribution.
- Light industrial distribution systems.
- Industrial installations requiring combined residual-current and overcurrent protection.
Εγκατάσταση
- Match the 1P+N or 3P+N configuration to the circuit voltage and conductor arrangement.
- Use either top or bottom power entry according to the distribution-board layout.
- Observe the model-specific current limit when selecting VRL22, VRL22-40 or VRL22-63.
ΣΥΧΝΈΣ ΕΡΩΤΉΣΕΙΣ
What protection functions does the VRL22 provide?
It combines residual-current, overload and short-circuit protection.
Which residual-current types are available?
The catalog lists Type AC, Type A, Type ASi, Type A G short-time-delayed and Type A S selective versions.
What rated currents are available?
Rated-current options extend from 2 A to 63 A, with model-specific limits for the 3P+N versions.
Which residual-current sensitivities can be selected?
Available ratings are 10, 30, 100, 300 and 500 mA. The 10 mA option is limited to 1P+N models up to 32 A.
What is the available short-circuit breaking capacity?
The VRL22 is available with a rated short-circuit breaking capacity of 6 kA or 10 kA.