VIOX Electric
Language

VKL11F Type F Residual Current Circuit Breaker

The VIOX VKL11F Type F residual current circuit breaker detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz. Available in 16-100 A ratings, 30-300 mA sensitivities and 2P or 4P configurations, it combines voltage-independent operation, short-time delay and 3 kA surge-current immunity for installations incorporating frequency converters and electronically controlled equipment.

Rated Current
16-100 A
Residual Current
30, 100, 300 mA
Pole Configuration
2P, 4P
RCCB Type
Type F

Overview

The VKL11F is a Type F residual current circuit breaker for AC 50/60 Hz installations incorporating single-phase frequency converters and electronically controlled equipment. It detects sinusoidal AC, pulsating DC and composite or mixed-frequency residual currents up to 1 kHz. The range includes 16 A to 100 A ratings, 30, 100 and 300 mA sensitivities, and 2P or 4P configurations. Voltage-independent magnetic operation, short-time delay and surge-current immunity support use in residential, commercial and industrial installations. The RCCB must be used together with suitable overload and short-circuit protection.

Features

  • Detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz.
  • Maintains normal functionality with superimposed smooth DC residual current up to 10 mA.
  • Voltage-independent magnetic operation with short-time delay.
  • Surge-current immunity up to 3 kA.
  • Mechanical red/green contact-position indicator.
  • Designed according to IEC/EN 62423 and IEC/EN 61008-1.

Models

Catalog designation Pole configuration Rated voltage Test circuit voltage range
VKL11F RCCB 2P 2P 230/240 V AC 184-264 V AC
VKL11F RCCB 4P 4P 400/415 V AC 184-440 V AC

Specifications

Electrical Data

Parameter Specification
Product type Type F RCCB
Rated current (In) 16, 25, 32, 40, 63, 80, 100 A
Rated residual operating current (IΔn) 30, 100, 300 mA
Rated frequency 50/60 Hz
Mode of operation Voltage independent
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV (1.2/50 μs)
Rated conditional short-circuit current (Inc) 10 kA
Rated making and breaking capacity (Im) 1,500 A
Maximum backup fuse 100 A gG/gL

Protection Data

Parameter Specification
Residual-current sensitivity AC, pulsating DC and mixed-frequency residual currents up to 1 kHz
Superimposed smooth DC Normal functionality maintained up to 10 mA
Smooth DC fault current Not detected
Time characteristic K short-time delayed (G/ASi)
Peak withstand current 3 kA (8/20 μs), surge-current proof
Electrical isolation Contact gap greater than 4 mm

Mechanical Data

Parameter Specification
Electrical endurance ≥2,000 operating cycles
Mechanical endurance ≥4,000 operating cycles
Contact-position indicator Mechanical red/green indicator

Installation Data

Parameter Specification
Terminal type Open/lift terminals
Terminal capacity 1-25 mm²
Terminal tightening torque 2-2.5 N·m
Busbar thickness 0.8-2 mm

Environmental and Standards Data

Parameter Specification
Operating temperature -25°C to +55°C
Storage and transport temperature -40°C to +70°C
Climatic resistance According to IEC/EN 61008
Applicable standards IEC/EN 62423, IEC/EN 61008-1, OVE E8601

Selection Guide

Code position Meaning Catalog value or options
V VIOX enterprise identification V
KL RCCB product family code KL
11 Design serial number 11
F Residual current type F
Rated-current code Rated current 16, 25, 32, 40, 63, 80 or 100 A
Residual-current code Rated residual operating current 30, 100 or 300 mA
2P / 4P Number of poles 2P or 4P

Rated Current

Select one of the listed ratings from 16 A to 100 A to match the circuit rating.

Sensitivity

Choose 30, 100 or 300 mA according to the required residual-current protection application.

Poles and Voltage

Select 2P for 230/240 V AC or 4P for 400/415 V AC installations.

Residual-Current Profile

Use Type F where sinusoidal AC, pulsating DC or mixed-frequency residual currents up to 1 kHz may occur. Smooth DC fault current is not detected.

Dimensions

VKL11F Type F RCCB dimensional drawing
VKL11F Type F 2P and 4P RCCB dimensional drawing.

Applications

  • Washing machines and dishwashers.
  • Heat pumps and air conditioners.
  • Lighting ballasts and electronically controlled equipment.
  • Power tools and welding equipment.

Installation

  • Use the RCCB together with suitable overload and short-circuit protection.
  • Use conductors within the listed terminal capacity of 1-25 mm².
  • Apply the listed terminal tightening torque of 2-2.5 N·m.
  • Use busbars within the listed thickness range of 0.8-2 mm.
  • Confirm that the operating environment remains within the listed -25°C to +55°C range.

FAQ

Which residual currents can the VKL11F Type F detect?

It detects sinusoidal AC, pulsating DC and composite or mixed-frequency residual currents up to 1 kHz.

How does the VKL11F respond to smooth DC residual current?

Normal functionality is maintained with superimposed smooth DC residual current up to 10 mA. The catalog states that smooth DC fault current is not detected.

Which rated currents and sensitivities are available?

Rated-current options are 16, 25, 32, 40, 63, 80 and 100 A. Residual operating-current options are 30, 100 and 300 mA.

Which pole and voltage configurations are offered?

The 2P configuration is rated at 230/240 V AC, while the 4P configuration is rated at 400/415 V AC.

What equipment is listed as a typical application?

The catalog lists washing machines, dishwashers, heat pumps, air conditioners, lighting ballasts, power tools and welding equipment.

Which standards are listed for the VKL11F Type F?

The applicable standards are IEC/EN 62423, IEC/EN 61008-1 and OVE E8601.

Need a Product Quote?
Let’s Build It Together.

Send us the product model, technical ratings, quantity, and OEM requirements. Our team will review your application and respond within one business day.

Request a Quote