Overview
The VKL11 is a residual current circuit breaker for residual-current protection in AC 50/60 Hz electrical installations. It disconnects the circuit when earth leakage is detected and is available in Type AC, Type A and high-immunity Type ASi versions. The range covers rated currents from 16 A to 100 A, residual operating currents from 10 mA to 300 mA, and 2P or 4P configurations rated at 240 V AC or 415 V AC. Designed for residential, commercial and industrial distribution systems, it mounts on a 35 mm DIN rail and is intended for use with suitable overload and short-circuit protection.
Features
- Compliant with IEC/EN 61008-1.
- Type AC, Type A and high-immunity Type ASi versions.
- Voltage-independent magnetic operation.
- Integrated fault-current indicator.
- Rated-current options from 16 A to 100 A.
- Top or bottom power entry.
Models
| Type | Detectable residual current | Time characteristic | Recommended applications |
|---|---|---|---|
| Type AC | Sinusoidal AC residual current | Instantaneous | Conventional AC circuits and resistive loads |
| Type A | Sinusoidal AC and pulsating DC residual currents | Instantaneous | Residential, commercial and electronic equipment circuits |
| Type ASi | Type A characteristics with enhanced immunity to nuisance tripping | Short-time delayed | Circuits affected by harmonics, transient surges or electronic equipment |
Specifications
Electrical Data
| Parameter | Specification |
|---|---|
| Rated current | 16, 25, 32, 40, 63, 80, 100 A |
| Rated residual operating current | 10 mA (16-40 A); 30, 100, 300 mA |
| Rated voltage | 240 V AC (2P); 415 V AC (4P) |
| Rated frequency | 50/60 Hz |
| Rated residual making and breaking capacity | 500 A (16-40 A); 630 A (63 A); 800 A (80 A); 1,000 A (100 A) |
| Rated conditional short-circuit current | 6/10 kA |
| Rated insulation voltage | 500 V |
| Rated impulse withstand voltage | 6 kV |
| Dielectric test voltage | 2.5 kV for 1 minute |
Protection Data
| Parameter | Specification |
|---|---|
| Residual current type | AC, A, ASi |
| Tripping characteristic | Instantaneous; short-time delayed for ASi |
| Number of poles | 2P, 4P |
| Fault-current indicator | Yes |
| Degree of protection | IP20 |
Mechanical Data
| Parameter | Specification |
|---|---|
| Electrical life | ≥2,000 operations |
| Mechanical life | ≥2,000 operations |
Installation Data
| Parameter | Specification |
|---|---|
| Mounting | 35 mm DIN rail, EN 60715 |
| Terminal connection | Cable or pin-type busbar |
| Terminal capacity | Up to 35 mm² |
| Tightening torque | 2.5 N·m |
| Power entry | Top or bottom |
Environmental and Standards Data
| Parameter | Specification |
|---|---|
| Operating temperature | -25°C to +55°C |
| Storage temperature | -40°C to +70°C |
| Pollution degree | 2 |
| Compliant standard | IEC/EN 61008-1 |
Selection Guide
| Code position | Meaning | Catalog value or options |
|---|---|---|
| V | VIOX enterprise identification | V |
| KL | RCCB product family code | KL |
| 11 | Design serial number | 11 |
| AC / A / ASi | Residual current type | AC, A or ASi |
| Rated-current code | Rated current | 16, 25, 32, 40, 63, 80 or 100 A |
| Residual-current code | Rated residual operating current | 10, 30, 100 or 300 mA |
| 2P / 4P | Number of poles | 2P or 4P |
Residual Current Type
Select Type AC for sinusoidal AC residual current, Type A for sinusoidal AC and pulsating DC residual currents, or Type ASi when enhanced immunity and short-time-delayed operation are required.
Rated Current
Choose one of the listed ratings from 16 A to 100 A to match the circuit rating.
Sensitivity
Select 10, 30, 100 or 300 mA according to the required protection application. The 10 mA option is listed for 16-40 A ratings.
Poles and Voltage
Select 2P for 240 V AC or 4P for 415 V AC installations.
Dimensions
Applications
- 10 mA sensitivity for sensitive equipment and locations requiring enhanced personal protection.
- 30 mA sensitivity for additional protection against electric shock.
- 100 mA sensitivity for protection against indirect contact.
- 300 mA sensitivity for protection against insulation-fault fire risks.
Installation
- Mount the selected RCCB on a 35 mm DIN rail in accordance with EN 60715.
- Use cable or a pin-type busbar within the listed terminal capacity of up to 35 mm².
- Apply the listed terminal tightening torque of 2.5 N·m.
- Power entry may be made from the top or bottom.
- Use the RCCB together with suitable overload and short-circuit protection.
Downloads
FAQ
Which residual current types are available for the VKL11?
The VKL11 is available in Type AC, Type A and Type ASi versions.
Which rated currents and sensitivities are offered?
Rated currents are 16, 25, 32, 40, 63, 80 and 100 A. Residual operating-current options are 10 mA for 16-40 A ratings and 30, 100 or 300 mA.
Which voltage applies to each pole configuration?
The 2P configuration is rated at 240 V AC, while the 4P configuration is rated at 415 V AC.
Does the VKL11 provide overload and short-circuit protection?
The catalog specifies that the VKL11 is intended for use together with suitable overload and short-circuit protection.
How can the VKL11 terminals be connected?
The terminals accept cable or a pin-type busbar, with a listed capacity of up to 35 mm² and a tightening torque of 2.5 N·m.
Which standard is listed for the VKL11?
The catalog lists IEC/EN 61008-1 as the compliant standard.