The VKL11F is a Type F residual current circuit breaker for AC 50/60 Hz installations incorporating single-phase frequency converters and electronically controlled equipment. It detects sinusoidal AC, pulsating DC and composite or mixed-frequency residual currents up to 1 kHz. The range includes 16 A to 100 A ratings, 30, 100 and 300 mA sensitivities, and 2P or 4P configurations. Voltage-independent magnetic operation, short-time delay and surge-current immunity support use in residential, commercial and industrial installations. The RCCB must be used together with suitable overload and short-circuit protection.
Đặc trưng
- Detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz.
- Maintains normal functionality with superimposed smooth DC residual current up to 10 mA.
- Voltage-independent magnetic operation with short-time delay.
- Surge-current immunity up to 3 kA.
- Mechanical red/green contact-position indicator.
- Designed according to IEC/EN 62423 and IEC/EN 61008-1.
Mô hình
| Catalog designation | Cấu hình cực | Bình áp | Test circuit voltage range |
|---|---|---|---|
| VKL11F RCCB 2P | 2P | 230/240 V AC | 184-264 V AC |
| VKL11F RCCB 4P | 4 P | 400/415 V AC | 184-440 V AC |
Thông số kỹ thuật
Electrical Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Loại sản phẩm | RCCB loại F |
| Dòng điện định mức (In) | 16, 25, 32, 40, 63, 80, 100 A |
| Rated residual operating current (IΔn) | 30, 100, 300 mA |
| Tần số định mức | 50/60 Hz |
| Chế độ hoạt động | Độc lập với điện áp |
| Điện áp cách điện định mức (Ui) | 500 V |
| Điện áp chịu xung định mức (Uimp) | 4 kV (1.2/50 μs) |
| Rated conditional short-circuit current (Inc) | 10 kA |
| Rated making and breaking capacity (Im) | 1,500 A |
| Maximum backup fuse | 100 A gG/gL |
Protection Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Độ nhạy dòng dư | AC, pulsating DC and mixed-frequency residual currents up to 1 kHz |
| Superimposed smooth DC | Normal functionality maintained up to 10 mA |
| Smooth DC fault current | Not detected |
| Đặc tính thời gian | K short-time delayed (G/ASi) |
| Dòng điện chịu đựng cực đại | 3 kA (8/20 μs), surge-current proof |
| Cách ly điện | Contact gap greater than 4 mm |
Mechanical Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Điện sức chịu đựng | ≥2,000 operating cycles |
| Cơ khí sức chịu đựng | ≥4,000 operating cycles |
| Chỉ báo vị trí tiếp điểm | Mechanical red/green indicator |
Installation Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Loại thiết bị đầu cuối | Open/lift terminals |
| Công suất thiết bị đầu cuối | 1-25 mm² |
| Terminal tightening torque | 2-2.5 N·m |
| Độ dày thanh cái | 0.8-2 mm |
Environmental and Standards Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Nhiệt độ hoạt động | -25°C đến +55°C |
| Nhiệt độ bảo quản và vận chuyển | -40°C đến +70°C |
| Climatic resistance | According to IEC/EN 61008 |
| Các tiêu chuẩn áp dụng | IEC/EN 62423, IEC/EN 61008-1, OVE E8601 |
Hướng dẫn lựa chọn
| Code position | Ý nghĩa | Catalog value or options |
|---|---|---|
| V | VIOX enterprise identification | V |
| KL | RCCB product family code | KL |
| 11 | Design serial number | 11 |
| F | Loại dòng rò | F |
| Rated-current code | Dòng điện định mức | 16, 25, 32, 40, 63, 80 or 100 A |
| Residual-current code | Dòng điện dư định mức khi vận hành | 30, 100 or 300 mA |
| 2P / 4P | Số cực | 2P or 4P |
Bình Hiện Tại
Select one of the listed ratings from 16 A to 100 A to match the circuit rating.
Nhạy cảm
Choose 30, 100 or 300 mA according to the required residual-current protection application.
Poles and Voltage
Select 2P for 230/240 V AC or 4P for 400/415 V AC installations.
Residual-Current Profile
Use Type F where sinusoidal AC, pulsating DC or mixed-frequency residual currents up to 1 kHz may occur. Smooth DC fault current is not detected.
Kích thước
Ứng dụng
- Washing machines and dishwashers.
- Heat pumps and air conditioners.
- Lighting ballasts and electronically controlled equipment.
- Power tools and welding equipment.
Cài đặt
- Use the RCCB together with suitable overload and short-circuit protection.
- Use conductors within the listed terminal capacity of 1-25 mm².
- Apply the listed terminal tightening torque of 2-2.5 N·m.
- Use busbars within the listed thickness range of 0.8-2 mm.
- Confirm that the operating environment remains within the listed -25°C to +55°C range.
Câu hỏi thường gặp
Which residual currents can the VKL11F Type F detect?
It detects sinusoidal AC, pulsating DC and composite or mixed-frequency residual currents up to 1 kHz.
How does the VKL11F respond to smooth DC residual current?
Normal functionality is maintained with superimposed smooth DC residual current up to 10 mA. The catalog states that smooth DC fault current is not detected.
Which rated currents and sensitivities are available?
Rated-current options are 16, 25, 32, 40, 63, 80 and 100 A. Residual operating-current options are 30, 100 and 300 mA.
Which pole and voltage configurations are offered?
The 2P configuration is rated at 230/240 V AC, while the 4P configuration is rated at 400/415 V AC.
What equipment is listed as a typical application?
The catalog lists washing machines, dishwashers, heat pumps, air conditioners, lighting ballasts, power tools and welding equipment.
Which standards are listed for the VKL11F Type F?
The applicable standards are IEC/EN 62423, IEC/EN 61008-1 and OVE E8601.