VIOX VM6 Series Thermomagnetic Molded Case Circuit Breaker (125 A–2000 A)
Product Overview
The VIOX VM6 Series is a compact, low-temperature-rise thermomagnetic molded case circuit breaker (MCCB) platform engineered for industrial and commercial power distribution networks at AC 50/60 Hz, rated working voltage up to AC 690 V, and frame currents from 125 A to 2000 A. Built with a multiple contact-blade arc-quenching architecture and compliant with IEC/EN 60947-2 and GB/T 14048.2 (Selectivity Category A), VM6 protects feeders, transformers, and power equipment against overload, short-circuit, and undervoltage faults, with optional magnetic-only release configurations for motor protection.
Key Engineering Features
- Complete 8-Frame Industrial Range: VM6-125, VM6-160, VM6-250, VM6-400, VM6-630, VM6-800, VM6-1250, and VM6-2000 covering rated currents from 10 A to 2000 A.
- Four Breaking Capacity Tiers (C / S / M / H): Up to 100 kA Icu / 85 kA Ics at AC 400 V (VM6-2000H), 85 kA Icu / 65 kA Ics (VM6-800H & VM6-1250H), 65 kA Icu / 65 kA Ics (VM6-400H & VM6-630H), and 50 kA Icu / 50 kA Ics (VM6-125H & VM6-160H).
- High Insulation & Impulse Withstand: Rated insulation voltage Ui = 1000 V and rated impulse withstand voltage Uimp = 8 kV across the entire series.
- Low Temperature Rise & Compact Volume: Multiple contact-blade design minimizes contact resistance; optional low-temperature-rise variants V (50 K) and V1 (40 K) support high-density switchgear enclosures.
- Flexible Release & 4P Neutral Options: Available in thermal-magnetic distribution release (code 3) or magnetic-only motor protection release (code 2), plus four 4-pole neutral configurations (Types A, B, C, and D).
- Complete Accessory Ecosystem: Supports electric motor operators (DC3 / DC6), manual rotary handles, mechanical interlocking, front/back plug-in and draw-out bases, plus 20 factory internal accessory combinations (codes 08–78).
Technical Specifications Summary
| Parameter | Specification |
|---|---|
| Product Series | VIOX VM6 Series Thermomagnetic MCCB |
| Applicable Standards | IEC/EN 60947-2; GB/T 14048.2 |
| Frame Current Range (Inm) | 125 A, 160 A, 250 A, 400 A, 630 A, 800 A, 1250 A, 2000 A |
| Rated Current Range (In) | 10 A – 2000 A |
| Number of Poles | 1P, 2P, 3P, 4P (1P on VM6-125; 2P on VM6-125/160; 3P/4P across all frames) |
| Rated Working Voltage (Ue) | AC 230 V / AC 400 V / AC 690 V |
| Rated Insulation Voltage (Ui) | 1000 V |
| Rated Impulse Withstand Voltage (Uimp) | 8 kV |
| Breaking Capacity Codes | C (Basic), S (Standard), M (Moderate), H (High Breaking) |
| Maximum Icu / Ics (AC 400 V) | Up to 100 kA Icu / 85 kA Ics (VM6-2000H) |
| Selectivity Category | Class A |
| Overcurrent Release Type | Thermomagnetic (Code 3: Power Distribution) / Magnetic-Only (Code 2: Motor Protection) |
| Low Temperature Rise Options | Standard; Type V (50 K); Type V1 (40 K) |
| Installation & Wiring Methods | Fixed Front-Panel, Back-Panel (Z1), Plug-in Split/Integrated (Z2Q/Z2H/Z3Q/Z3H), Draw-out (DF/DR, 400–800 A) |
Model Nomenclature & Quick Selection Code
Example order code: VM6-160 M P1 / 4 3 00 2 A V / P Z In=100A. Specify each code block below when submitting a panel schedule or RFQ:
| Code Segment | Options & Engineering Meaning | Selection Notes |
|---|---|---|
| Series Prefix | VM6 — Thermomagnetic Molded Case Circuit Breaker | IEC/EN 60947-2 Class A platform |
| Frame Current (Inm) | 125, 160, 250, 400, 630, 800, 1250, 2000 A | Select frame ≥ required rated current In |
| Breaking Capacity Code | C (Basic) · S (Standard) · M (Moderate) · H (High Breaking) | 400, 630, 800, 1250 (also S), and 2000 A frames primarily use M and H tiers |
| Operation Code | Blank: Direct handle · P1: DC3 electric operator · P2: DC6 electric operator · ZY1 / ZF1: Center rotary handle (circular/square) · ZY2 / ZF2: Eccentric rotary handle · Z3: Integrated manual rotary handle (125/160/250 A only) | 1P & 2P support direct handle only. Electric operator voltages: DC 24 V, DC 110 V, DC 220 V, AC 230 V (standard), AC 400 V |
| Poles Code | 1 (1P) · 2 (2P) · 3 (3P) · 4 (4P) | 125 A: 1P–4P · 160 A: 2P (C/S), 3P, 4P · 250–2000 A: 3P, 4P |
| Release Method | 2: Magnetic-only release · 3: Thermal + magnetic release | Use code 3 for distribution; code 2 for motor protection |
| Internal Accessory Code | 00 (None) to 78 (Shunt, UVT, Auxiliary, Alarm combinations) | 125 A 1P has no internal accessories; default lead length 500 mm (customizable); UVT uses terminal type |
| Usage Code | Blank: Power distribution · 2: Motor protection | ≤40 A: 8.5×In non-trip; 500 A action; 700–2000 A: power distribution only |
| 4P Neutral Pole Type | A: N unswitched, no overcurrent release · B: N switched with 3 poles, no overcurrent release · C: N switched + overcurrent release · D: N always connected + overcurrent release | Specify for all 4-pole orders |
| Additional Function | Blank: Standard · V: Low temperature rise 50 K · V1: Low temperature rise 40 K | Ideal for high-ambient or compact switchboards |
| Installation & Wiring | Blank: Front-panel fixed · P: Extension copper bar · Z1: Back-panel fixed · Z2Q / Z2H: Plug-in front/back split · Z3Q / Z3H: Plug-in front/back integrated · DF / DR: Draw-out front/back · K / JK / CK: Wiring box (full / incoming / outgoing) | 1P/2P: connecting bars & back-panel only. Draw-out unavailable on 125–250 A. 1250/2000 A: connecting bars only |
| Protective Cover | Blank: Standard · Z: Terminal cover | Available for 3P (narrow/wide, short/long); unavailable on 125 A & 2000 A |
| Rated Current (In) |
125 A frame: 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A 160 A frame: 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 A 250 A frame: 100, 125, 140, 160, 180, 200, 225, 250 A 400 A frame: 250, 315, 350, 400 A 630 A frame: 400, 500, 630 A 800 A frame: 500, 630, 700, 800 A 1250 A frame: 630, 700, 800, 1000, 1250 A 2000 A frame: 1000, 1250, 1600, 2000 A |
Full industrial step coverage from 10 A to 2000 A |
Main Electrical Performance — VM6-125 to VM6-630 Frames
All frames feature rated insulation voltage Ui = 1000 V, impulse withstand voltage Uimp = 8 kV, Selectivity Category Class A, and thermomagnetic overcurrent release.
| Model & Tier | Rated Current In (A) | Poles | Ue (AC) | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|---|---|
| VM6-125C | 10–125 A | 1P / 2P / 3P / 4P | 230 / 400 / 690 V | 5 / 5 / 3 kA | 8 / 8 / 5 kA |
| VM6-125S | 10–125 A | 1P / 2P / 3P / 4P | 230 / 400 / 690 V | 15 / 13 (3P/4P) / 3 (3P/4P) kA | 30 / 25 (3P/4P) / 6 (3P/4P) kA |
| VM6-125M | 10–125 A | 1P / 2P / 3P / 4P | 230 (1P) / 400 / 690 V | 35 (3P/4P) / 18 (1P/3P/4P) / 5 (3P/4P) kA | 36 (1P) · 50 (3P/4P) / 36 / 10 (3P/4P) kA |
| VM6-125H | 10–125 A | 1P / 2P / 3P / 4P | 230 (1P) / 400 / 690 V | 50 / 50 / 8 kA | 50 / 50 / 15 kA |
| VM6-160C | 10–160 A | 2P / 3P / 4P | 230 / 400 / 690 V | 7 / 10 / 2 kA | 10 / 15 / 8 kA |
| VM6-160S | 10–160 A | 2P / 3P / 4P | 230 / 400 / 690 V | 10 / 13 / 3 kA | 20 / 25 / 6 kA |
| VM6-160M | 10–160 A | 3P / 4P | 230 / 400 / 690 V | 25 / 18 / 5 kA | 30 / 36 / 10 kA |
| VM6-160H | 10–160 A | 3P / 4P | 230 / 400 / 690 V | 35 / 35 (2P) · 50 (3P/4P) / 10 kA | 50 / 50 / 15 kA |
| VM6-250C | 100–250 A | 3P / 4P | 230 / 400 / 690 V | 20 / 10 / 3 kA | 30 / 15 / 5 kA |
| VM6-250S | 100–250 A | 3P / 4P | 230 / 400 / 690 V | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-250M | 100–250 A | 3P / 4P | 230 / 400 / 690 V | 40 / 35 / 10 kA | 65 / 50 / 15 kA |
| VM6-250H | 100–250 A | 3P / 4P | 230 / 400 / 690 V | 50 / 50 / 15 kA | 70 / 65 / 20 kA |
| VM6-400S | 250–400 A | 3P / 4P | 230 / 400 / 690 V | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-400M | 250–400 A | 3P / 4P | 230 / 400 / 690 V | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-400H | 250–400 A | 3P / 4P | 230 / 400 / 690 V | 50 / 65 / 12 kA | 70 / 65 / 25 kA |
| VM6-630M | 400–630 A | 3P / 4P | 230 / 400 / 690 V | 20 / 35 / 5 kA | 30 / 50 / 10 kA |
| VM6-630H | 400–630 A | 3P / 4P | 230 / 400 / 690 V | 30 / 65 / 30 kA | 50 / 65 / 20 kA |
Main Electrical Performance — High-Current VM6-800 to VM6-2000 Frames
| Model & Tier | Rated Current In (A) | Poles | Ue (AC) | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|---|---|
| VM6-800M | 500, 630, 700, 800 A | 3P / 4P | 230 / 400 / 690 V | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-800H | 500, 630, 700, 800 A | 3P / 4P | 230 / 400 / 690 V | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-1250S | 630, 700, 800, 1000, 1250 A | 3P / 4P | 240 / 400 / 690 V | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-1250M | 630, 700, 800, 1000, 1250 A | 3P / 4P | 230 / 400 / 690 V | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-1250H | 630, 700, 800, 1000, 1250 A | 3P / 4P | 230 / 400 / 690 V | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-2000M | 1000, 1250, 1600, 2000 A | 3P / 4P | 400 / 690 V | — / 50 / 20 kA | — / 50 / 20 kA |
| VM6-2000H | 1000, 1250, 1600, 2000 A | 3P / 4P | 400 / 690 V | — / 85 / 20 kA | — / 100 / 20 kA |
Outline Dimensions (mm) — All 8 Frame Sizes
Height measured from the bottom of the base to the face cover and to the top of the operating handle.
| Frame | Poles | Width W (mm) | Length L (mm) | Height to Cover (mm) | Height to Handle (mm) |
|---|---|---|---|---|---|
| VM6-125 | 1P / 2P / 3P / 4P | 25 / 50 / 75 / 100 | 130 | 68 | 94.5 |
| VM6-160 | 2P / 3P / 4P | 60 / 90 / 120 | 155 | 68 / 82 | 94 / 108 |
| VM6-250 | 3P / 4P | 105 / 140 | 165 | 68 / 88 | 96 / 116 |
| VM6-400 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-630 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-800 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-1250 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-2000 | 3P / 4P | 210 / 280 | 340 | 141 | 244 |
External Accessories Compatibility Matrix
| External Accessory | VM6-125 | VM6-160 | VM6-250 | VM6-400 / 630 / 800 | VM6-1250 / 2000 |
|---|---|---|---|---|---|
| Electric Motor Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Manual Rotary Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Extension Copper Bar | 1P, 2P, 3P, 4P | 2P, 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Mechanical Interlocking | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P | Not available |
| Plug-in Front-Panel (Split / Integrated / Fixed) | 3P, 4P (Integrated/Fixed); 3P (Split) | 3P, 4P | 3P, 4P | 3P, 4P | Not available |
| Plug-in Back-Panel (Split / Integrated / Fixed) | 3P, 4P (Integrated/Fixed); 3P (Split) | 3P, 4P | 3P, 4P | 3P, 4P | Not available |
| Draw-out Back-Panel Type | Not available | Not available | Not available | 3P only | Not available |
Internal Accessories & Factory Installation Codes (00–78)
Shunt and undervoltage release control voltages: DC 24 V, DC 110 V, DC 220 V, AC 230 V (standard), AC 400 V. Note: For Code 50 (Shunt + Undervoltage), VM6-125 and VM6-160 require customized left-side undervoltage release; VM6-250 requires customized left-side shunt release.
| Accessory Code | Internal Accessory Configuration | Supported Frames & Poles |
|---|---|---|
| 00 | None (Standard breaker without internal accessories) | All frames (1P–4P) |
| 08 | Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 10 | Shunt release | VM6-125/160 (2P, 3P, 4P); VM6-250 to 2000 (3P, 4P) |
| 18 | Shunt release + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 20 | Single auxiliary contact (1 set changeover) | VM6-125/160 (2P, 3P, 4P); VM6-250 to 2000 (3P, 4P) |
| 27 | Dual auxiliary contacts (2 sets changeover) | VM6-125/160 (2P, 3P, 4P); VM6-250 to 2000 (3P, 4P) |
| 28 | Single auxiliary contact + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 29 | Dual auxiliary contacts + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 30 | Undervoltage release (UVT) | VM6-125/160 (2P, 3P, 4P); VM6-250 to 2000 (3P, 4P) |
| 38 | Undervoltage release + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 40 | Shunt release + Single auxiliary contact | VM6-125 to VM6-2000 (3P, 4P) |
| 41 | Shunt release + Dual auxiliary contacts | VM6-125 to VM6-2000 (3P, 4P) |
| 48 | Shunt release + Auxiliary + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 50 | Shunt release + Undervoltage release | VM6-125 to VM6-2000 (3P, 4P; see Note above) |
| 60 | Two sets of single auxiliary contacts | VM6-125 to VM6-2000 (3P, 4P) |
| 61 | Single auxiliary contact + Dual auxiliary contacts | VM6-125 to VM6-2000 (3P, 4P) |
| 62 | Two sets of dual auxiliary contacts | VM6-125 to VM6-2000 (3P, 4P) |
| 68 | Single auxiliary contact + Auxiliary + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 69 | Dual auxiliary contacts + Auxiliary + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
| 70 | Undervoltage release + Single auxiliary contact | VM6-125 to VM6-2000 (3P, 4P) |
| 71 | Undervoltage release + Dual auxiliary contacts | VM6-125 to VM6-2000 (3P, 4P) |
| 78 | Undervoltage release + Auxiliary + Alarm contact | VM6-125 to VM6-2000 (3P, 4P) |
Applications & Engineering Support
The VIOX VM6 Series is suited for main incoming switchgear, commercial sub-distribution boards, transformer feeders, generator panels, HVAC & pump motor control centers, and industrial OEM switchboards. Explore the full VIOX MCCB range, coordinate downstream protection with VIOX MCBs and RCBOs, or send your panel schedule for matched factory pricing and CAD drawings.