Přehled
The VIOX VM6 Series is a compact, low-temperature-rise thermomagnetic molded case circuit breaker (MCCB) platform covering 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current) for AC 50/60 Hz power distribution and motor protection up to 690 V AC. Engineered with a multiple contact-blade arc-quenching system and compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 delivers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, optional low-temperature-rise builds (40 K / 50 K), and a full ecosystem of internal and external switchgear accessories.
Funkce
- Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Selectivity Category Class A).
- 8 industrial frame sizes (125, 160, 250, 400, 630, 800, 1250, and 2000 A) covering 10 A to 2000 A.
- Four breaking capacity tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC.
- High insulation rating (Ui 1000 V) and impulse withstand voltage (Uimp 8 kV) across all frames.
- Thermomagnetic distribution release (Code 3) or magnetic-only motor protection (Code 2), plus 4P neutral types A, B, C, and D.
- Optional low-temperature-rise builds (Type V 50 K / Type V1 40 K) and 20 factory internal accessory combinations (Codes 08–78).
Modely
| Frame Series | Rated Current In (A) | Breaking Tiers | Poláci | Max Icu / Ics (400 V AC) |
|---|---|---|---|---|
| VM6-125 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A | C, S, M, H | 1P, 2P, 3P, 4P | 50 kA / 50 kA |
| VM6-160 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 A | C, S, M, H | 2P (C/S), 3P, 4P | 50 kA / 50 kA |
| VM6-250 | 100, 125, 140, 160, 180, 200, 225, 250 A | C, S, M, H | 3P, 4P | 65 kA / 50 kA |
| VM6-400 | 250, 315, 350, 400 A | S, M, H | 3P, 4P | 65 kA / 65 kA |
| VM6-630 | 400, 500, 630 A | M, H | 3P, 4P | 65 kA / 65 kA |
| VM6-800 | 500, 630, 700, 800 A | M, H | 3P, 4P | 85 kA / 65 kA |
| VM6-1250 | 630, 700, 800, 1000, 1250 A | S, M, H | 3P, 4P | 85 kA / 65 kA |
| VM6-2000 | 1000, 1250, 1600, 2000 A | M, H | 3P, 4P | 100 kA / 85 kA |
Specifikace
General Electrical & Standards Data
| Parametr | Specifikace |
|---|---|
| Platné normy | IEC/EN 60947-2; GB/T 14048.2 |
| Frame current range (Inm) | 125, 160, 250, 400, 630, 800, 1250, 2000 A |
| Rated current range (In) | 10 A – 2000 A |
| Rated working voltage (Ue) | AC 230 V / AC 400 V / AC 690 V |
| Jmenovité izolační napětí (Ui) | 1000 V |
| Jmenovité impulzní výdržné napětí (Uimp) | 8 kV |
| Kategorie selektivity | Třída A |
| Overcurrent release type | Thermomagnetic (Code 3) / Magnetic-only motor protection (Code 2) |
| Low temperature rise options | Standard; Type V (50 K); Type V1 (40 K) |
Breaking Capacity — VM6-125 to VM6-630
| Model & Tier | Poláci | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|
| VM6-125C | 1P / 2P / 3P / 4P | 5 / 5 / 3 kA | 8 / 8 / 5 kA |
| VM6-125S | 1P / 2P / 3P / 4P | 15 / 13 (3P/4P) / 3 (3P/4P) kA | 30 / 25 (3P/4P) / 6 (3P/4P) kA |
| VM6-125M | 1P / 2P / 3P / 4P | 35 (3P/4P) / 18 / 5 (3P/4P) kA | 36 (1P) · 50 (3P/4P) / 36 / 10 (3P/4P) kA |
| VM6-125H | 1P / 2P / 3P / 4P | 50 / 50 / 8 kA | 50 / 50 / 15 kA |
| VM6-160C | 2P / 3P / 4P | 7 / 10 / 2 kA | 10 / 15 / 8 kA |
| VM6-160S | 2P / 3P / 4P | 10 / 13 / 3 kA | 20 / 25 / 6 kA |
| VM6-160M | 3P / 4P | 25 / 18 / 5 kA | 30 / 36 / 10 kA |
| VM6-160H | 3P / 4P | 35 / 35 (2P) · 50 (3P/4P) / 10 kA | 50 / 50 / 15 kA |
| VM6-250C | 3P / 4P | 20 / 10 / 3 kA | 30 / 15 / 5 kA |
| VM6-250S | 3P / 4P | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-250M | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 15 kA |
| VM6-250H | 3P / 4P | 50 / 50 / 15 kA | 70 / 65 / 20 kA |
| VM6-400S | 3P / 4P | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-400M | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-400H | 3P / 4P | 50 / 65 / 12 kA | 70 / 65 / 25 kA |
| VM6-630M | 3P / 4P | 20 / 35 / 5 kA | 30 / 50 / 10 kA |
| VM6-630H | 3P / 4P | 30 / 65 / 30 kA | 50 / 65 / 20 kA |
Breaking Capacity — High-Current VM6-800 to VM6-2000
| Model & Tier | Poláci | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|
| VM6-800M | 3P / 4P | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-800H | 3P / 4P | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-1250S | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-1250M | 3P / 4P | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-1250H | 3P / 4P | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-2000M | 3P / 4P | — / 50 / 20 kA | — / 50 / 20 kA |
| VM6-2000H | 3P / 4P | — / 85 / 20 kA | — / 100 / 20 kA |
Outline Dimensions (mm)
| Rám | Poláci | Width W (mm) | Length L (mm) | Height to Cover (mm) | Height to Handle (mm) |
|---|---|---|---|---|---|
| VM6-125 | 1P / 2P / 3P / 4P | 25 / 50 / 75 / 100 | 130 | 68 | 94.5 |
| VM6-160 | 2P / 3P / 4P | 60 / 90 / 120 | 155 | 68 / 82 | 94 / 108 |
| VM6-250 | 3P / 4P | 105 / 140 | 165 | 68 / 88 | 96 / 116 |
| VM6-400 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-630 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-800 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-1250 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-2000 | 3P / 4P | 210 / 280 | 340 | 141 | 244 |
External Accessories Compatibility
| External Accessory | VM6-125 | VM6-160 / 250 | VM6-400 / 630 / 800 | VM6-1250 / 2000 |
|---|---|---|---|---|
| Electric Motor Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Manual Rotary Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Extension Copper Bar | 1P–4P | 2P–4P (160) / 3P–4P (250) | 3P, 4P | 3P, 4P |
| Mechanické blokování | 3P, 4P | 3P, 4P | 3P, 4P | Není k dispozici |
| Plug-in Front / Back Panel | 3P, 4P | 3P, 4P | 3P, 4P | Není k dispozici |
| Draw-out Back-Panel Type | Není k dispozici | Není k dispozici | 3P only | Není k dispozici |
Průvodce výběrem
| Pozice kódu | Význam | Catalog Value or Options |
|---|---|---|
| VM6 | Produktová řada | Thermomagnetic molded case circuit breaker (IEC/EN 60947-2) |
| 125–2000 | Frame current (Inm) | 125, 160, 250, 400, 630, 800, 1250, 2000 A |
| C / S / M / H | Breaking capacity tier | C (Basic), S (Standard), M (Moderate), H (High Breaking) |
| Operace | Handle / motor operator | Direct (blank), P1 (DC3 electric), P2 (DC6 electric), ZY1/ZF1/ZY2/ZF2/Z3 (rotary handle) |
| 1 / 2 / 3 / 4 | Počet pólů | 1P–4P (125 A); 2P–4P (160 A); 3P–4P (250–2000 A) |
| 2 / 3 | Release method | 2 = Magnetic-only (motor protection); 3 = Thermal + magnetic (distribution) |
| 00–78 | Internal accessory code | 00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux(+Alarm) · 50 Shunt+UVT · 60/61/62/68/69 Multi-Aux(+Alarm) · 70/71/78 UVT+Aux(+Alarm) |
| A / B / C / D | 4P neutral pole type | A: N unswitched, no trip · B: N switched, no trip · C: N switched + trip · D: N unswitched + trip |
| V / V1 | Low temperature rise | V = 50 K low temperature rise; V1 = 40 K low temperature rise |
| Wiring & Cover | Mounting & terminal cover | P (copper bar), Z1 (back-panel), Z2Q/Z2H/Z3Q/Z3H (plug-in), DF/DR (draw-out), K/JK/CK (wiring box), Z (terminal cover) |
1. Match Frame & Breaking
Size the frame (125–2000 A) above load current and verify prospective fault level against C, S, M, or H Icu/Ics ratings at 400 V or 690 V AC.
2. Select Release & Neutral
Use Code 3 thermal-magnetic for power distribution feeders or Code 2 magnetic-only for motor circuits; specify 4P neutral type A, B, C, or D.
3. Specify Internal Codes
Order factory-installed shunt, undervoltage (DC 24/110/220 V, AC 230/400 V), auxiliary, or alarm contacts via codes 08–78.
4. Confirm Mounting & Drive
Choose fixed front/back panel, plug-in (up to 800 A), draw-out (400–800 A 3P), extended rotary handle, or DC3/DC6 motor operator.
Instalace
- Verify panel cutout clearance and mounting depth against the VM6 outline dimension table (height to face cover and handle).
- Confirm coil control voltage (DC 24 V, DC 110 V, DC 220 V, AC 230 V standard, or AC 400 V) for shunt, undervoltage, and electric motor operators.
- For Code 50 (Shunt + UVT), note customized left-side UVT on VM6-125/160 and customized left-side shunt release on VM6-250.
- Coordinate upstream incoming feeders with downstream Jističe VIOX MCB, proudových chráničů (RCBO)a SPD, or explore the full řady VIOX MCCB.
ČASTO KLADENÉ DOTAZY
What current range and breaking capacity does the VIOX VM6 Series cover?
The VM6 Series spans 8 industrial frame sizes from 125 A to 2000 A (rated currents 10 A–2000 A) with four short-circuit breaking tiers (C, S, M, H) reaching up to 100 kA Icu and 85 kA Ics at 400 V AC.
Can VM6 MCCBs be used for both power distribution and motor protection?
Yes. Specify release code 3 (thermomagnetic) for power distribution feeders or release code 2 (magnetic-only, usage code 2) for motor protection circuits up to 630 A.
What are the differences between 4P neutral types A, B, C, and D?
Type A has an unswitched neutral without overcurrent release; Type B switches neutral with the three phase poles without overcurrent release; Type C switches neutral with overcurrent release; Type D keeps neutral permanently connected with overcurrent release.
Which control voltages are available for VM6 internal accessories and motor operators?
Shunt releases, undervoltage releases, and DC3/DC6 electric operating mechanisms support DC 24 V, DC 110 V, DC 220 V, AC 230 V (conventional standard), and AC 400 V.
Are plug-in and draw-out bases available for VM6 MCCBs?
Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed types) are available from VM6-125 through VM6-800 (3P/4P). Draw-out back-panel bases are supported on VM6-400, VM6-630, and VM6-800 in 3P configurations.
Does VIOX offer low-temperature-rise builds for compact switchboards?
Yes. In addition to the standard IEC/EN 60947-2 build, VM6 is available in Type V (50 K low temperature rise) and Type V1 (40 K low temperature rise) for high-ambient or densely packed distribution panels.