VIOX VM6 Series Thermomagnetic MCCB (125A–2000A)

VIOX VM6 Series Thermomagnetic Molded Case Circuit Breakers (MCCB) cover 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current, 1P/2P/3P/4P) for AC 230 V / 400 V / 690 V distribution and motor protection. Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 offers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, low-temperature-rise options (40 K / 50 K), and a complete ecosystem of internal (shunt, UVT, auxiliary, alarm) and external (motor operator, rotary handle, plug-in, draw-out, interlock) accessories.

Frame Range
125–2000 A (8 Frames)
Max Breaking (400V)
Up to 100 kA Icu / 85 kA Ics
Konfiguration der Pole
1P, 2P, 3P, 4P
Standards & Ui
IEC 60947-2 · Ui 1000 V / 8 kV

Übersicht

The VIOX VM6 Series is a compact, low-temperature-rise thermomagnetic molded case circuit breaker (MCCB) platform covering 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current) for AC 50/60 Hz power distribution and motor protection up to 690 V AC. Engineered with a multiple contact-blade arc-quenching system and compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 delivers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, optional low-temperature-rise builds (40 K / 50 K), and a full ecosystem of internal and external switchgear accessories.

Eigenschaften

  • Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Selectivity Category Class A).
  • 8 industrial frame sizes (125, 160, 250, 400, 630, 800, 1250, and 2000 A) covering 10 A to 2000 A.
  • Four breaking capacity tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC.
  • High insulation rating (Ui 1000 V) and impulse withstand voltage (Uimp 8 kV) across all frames.
  • Thermomagnetic distribution release (Code 3) or magnetic-only motor protection (Code 2), plus 4P neutral types A, B, C, and D.
  • Optional low-temperature-rise builds (Type V 50 K / Type V1 40 K) and 20 factory internal accessory combinations (Codes 08–78).

Modelle

Frame Series Rated Current In (A) Breaking Tiers Polen Max Icu / Ics (400 V AC)
VM6-12510, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 AC, S, M, H1P, 2P, 3P, 4P50 kA / 50 kA
VM6-16010, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 AC, S, M, H2P (C/S), 3P, 4P50 kA / 50 kA
VM6-250100, 125, 140, 160, 180, 200, 225, 250 AC, S, M, H3P, 4P65 kA / 50 kA
VM6-400250, 315, 350, 400 AS, M, H3P, 4P65 kA / 65 kA
VM6-630400, 500, 630 AM, H3P, 4P65 kA / 65 kA
VM6-800500, 630, 700, 800 AM, H3P, 4P85 kA / 65 kA
VM6-1250630, 700, 800, 1000, 1250 AS, M, H3P, 4P85 kA / 65 kA
VM6-20001000, 1250, 1600, 2000 AM, H3P, 4P100 kA / 85 kA

Spezifikationen

General Electrical & Standards Data

ParameterSpezifikation
Anwendbare NormenIEC/EN 60947-2; GB/T 14048.2
Frame current range (Inm)125, 160, 250, 400, 630, 800, 1250, 2000 A
Rated current range (In)10 A – 2000 A
Rated working voltage (Ue)AC 230 V / AC 400 V / AC 690 V
Bemessungsisolationsspannung (Ui)1000 V
Bemessungs-Stoßspannungsfestigkeit (Uimp): 8 kV
SelektivitätskategorieKlasse A
Overcurrent release typeThermomagnetic (Code 3) / Magnetic-only motor protection (Code 2)
Low temperature rise optionsStandard; Type V (50 K); Type V1 (40 K)

Breaking Capacity — VM6-125 to VM6-630

Model & Tier Polen Ics (230 / 400 / 690 V) Icu (230 / 400 / 690 V)
VM6-125C1P / 2P / 3P / 4P5 / 5 / 3 kA8 / 8 / 5 kA
VM6-125S1P / 2P / 3P / 4P15 / 13 (3P/4P) / 3 (3P/4P) kA30 / 25 (3P/4P) / 6 (3P/4P) kA
VM6-125M1P / 2P / 3P / 4P35 (3P/4P) / 18 / 5 (3P/4P) kA36 (1P) · 50 (3P/4P) / 36 / 10 (3P/4P) kA
VM6-125H1P / 2P / 3P / 4P50 / 50 / 8 kA50 / 50 / 15 kA
VM6-160C2P / 3P / 4P7 / 10 / 2 kA10 / 15 / 8 kA
VM6-160S2P / 3P / 4P10 / 13 / 3 kA20 / 25 / 6 kA
VM6-160M3P / 4P25 / 18 / 5 kA30 / 36 / 10 kA
VM6-160H3P / 4P35 / 35 (2P) · 50 (3P/4P) / 10 kA50 / 50 / 15 kA
VM6-250C3P / 4P20 / 10 / 3 kA30 / 15 / 5 kA
VM6-250S3P / 4P25 / 15 / 4 kA50 / 30 / 8 kA
VM6-250M3P / 4P40 / 35 / 10 kA65 / 50 / 15 kA
VM6-250H3P / 4P50 / 50 / 15 kA70 / 65 / 20 kA
VM6-400S3P / 4P25 / 15 / 4 kA50 / 30 / 8 kA
VM6-400M3P / 4P40 / 35 / 10 kA65 / 50 / 20 kA
VM6-400H3P / 4P50 / 65 / 12 kA70 / 65 / 25 kA
VM6-630M3P / 4P20 / 35 / 5 kA30 / 50 / 10 kA
VM6-630H3P / 4P30 / 65 / 30 kA50 / 65 / 20 kA

Breaking Capacity — High-Current VM6-800 to VM6-2000

Model & Tier Polen Ics (230 / 400 / 690 V) Icu (230 / 400 / 690 V)
VM6-800M3P / 4P65 / 50 / 15 kA80 / 65 / 25 kA
VM6-800H3P / 4P70 / 65 / 20 kA85 / 85 / 35 kA
VM6-1250S3P / 4P40 / 35 / 10 kA65 / 50 / 20 kA
VM6-1250M3P / 4P65 / 50 / 15 kA80 / 65 / 25 kA
VM6-1250H3P / 4P70 / 65 / 20 kA85 / 85 / 35 kA
VM6-2000M3P / 4P— / 50 / 20 kA— / 50 / 20 kA
VM6-2000H3P / 4P— / 85 / 20 kA— / 100 / 20 kA

Outline Dimensions (mm)

Rahmen Polen Width W (mm) Length L (mm) Height to Cover (mm) Height to Handle (mm)
VM6-1251P / 2P / 3P / 4P25 / 50 / 75 / 1001306894.5
VM6-1602P / 3P / 4P60 / 90 / 12015568 / 8294 / 108
VM6-2503P / 4P105 / 14016568 / 8896 / 116
VM6-4003P / 4P140 / 184257103152
VM6-6303P / 4P140 / 184257103152
VM6-8003P / 4P210 / 280275.5103152
VM6-12503P / 4P210 / 280275.5103152
VM6-20003P / 4P210 / 280340141244

External Accessories Compatibility

External Accessory VM6-125 VM6-160 / 250 VM6-400 / 630 / 800 VM6-1250 / 2000
Electric Motor Operation3P, 4P3P, 4P3P, 4P3P, 4P
Manual Rotary Operation3P, 4P3P, 4P3P, 4P3P, 4P
Extension Copper Bar1P–4P2P–4P (160) / 3P–4P (250)3P, 4P3P, 4P
Mechanische Verriegelung3P, 4P3P, 4P3P, 4PNicht verfügbar
Plug-in Front / Back Panel3P, 4P3P, 4P3P, 4PNicht verfügbar
Draw-out Back-Panel TypeNicht verfügbarNicht verfügbar3P onlyNicht verfügbar

Auswahlhilfe

Codeposition Bedeutung Catalog Value or Options
VM6ProduktserieThermomagnetic molded case circuit breaker (IEC/EN 60947-2)
125–2000Frame current (Inm)125, 160, 250, 400, 630, 800, 1250, 2000 A
C / S / M / HBreaking capacity tierC (Basic), S (Standard), M (Moderate), H (High Breaking)
BetriebHandle / motor operatorDirect (blank), P1 (DC3 electric), P2 (DC6 electric), ZY1/ZF1/ZY2/ZF2/Z3 (rotary handle)
1 / 2 / 3 / 4Anzahl der Pole1P–4P (125 A); 2P–4P (160 A); 3P–4P (250–2000 A)
2 / 3Release method2 = Magnetic-only (motor protection); 3 = Thermal + magnetic (distribution)
00–78Internal accessory code00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux(+Alarm) · 50 Shunt+UVT · 60/61/62/68/69 Multi-Aux(+Alarm) · 70/71/78 UVT+Aux(+Alarm)
A / B / C / D4P neutral pole typeA: N unswitched, no trip · B: N switched, no trip · C: N switched + trip · D: N unswitched + trip
V / V1Low temperature riseV = 50 K low temperature rise; V1 = 40 K low temperature rise
Wiring & CoverMounting & terminal coverP (copper bar), Z1 (back-panel), Z2Q/Z2H/Z3Q/Z3H (plug-in), DF/DR (draw-out), K/JK/CK (wiring box), Z (terminal cover)

1. Match Frame & Breaking

Size the frame (125–2000 A) above load current and verify prospective fault level against C, S, M, or H Icu/Ics ratings at 400 V or 690 V AC.

2. Select Release & Neutral

Use Code 3 thermal-magnetic for power distribution feeders or Code 2 magnetic-only for motor circuits; specify 4P neutral type A, B, C, or D.

3. Specify Internal Codes

Order factory-installed shunt, undervoltage (DC 24/110/220 V, AC 230/400 V), auxiliary, or alarm contacts via codes 08–78.

4. Confirm Mounting & Drive

Choose fixed front/back panel, plug-in (up to 800 A), draw-out (400–800 A 3P), extended rotary handle, or DC3/DC6 motor operator.

Einrichtung

  • Verify panel cutout clearance and mounting depth against the VM6 outline dimension table (height to face cover and handle).
  • Confirm coil control voltage (DC 24 V, DC 110 V, DC 220 V, AC 230 V standard, or AC 400 V) for shunt, undervoltage, and electric motor operators.
  • For Code 50 (Shunt + UVT), note customized left-side UVT on VM6-125/160 and customized left-side shunt release on VM6-250.
  • Coordinate upstream incoming feeders with downstream VIOX MCBs, FI-/LS-Schalterund SPDs, or explore the full VIOX MCCB-Reihe.

FAQ

What current range and breaking capacity does the VIOX VM6 Series cover?

The VM6 Series spans 8 industrial frame sizes from 125 A to 2000 A (rated currents 10 A–2000 A) with four short-circuit breaking tiers (C, S, M, H) reaching up to 100 kA Icu and 85 kA Ics at 400 V AC.

Can VM6 MCCBs be used for both power distribution and motor protection?

Yes. Specify release code 3 (thermomagnetic) for power distribution feeders or release code 2 (magnetic-only, usage code 2) for motor protection circuits up to 630 A.

What are the differences between 4P neutral types A, B, C, and D?

Type A has an unswitched neutral without overcurrent release; Type B switches neutral with the three phase poles without overcurrent release; Type C switches neutral with overcurrent release; Type D keeps neutral permanently connected with overcurrent release.

Which control voltages are available for VM6 internal accessories and motor operators?

Shunt releases, undervoltage releases, and DC3/DC6 electric operating mechanisms support DC 24 V, DC 110 V, DC 220 V, AC 230 V (conventional standard), and AC 400 V.

Are plug-in and draw-out bases available for VM6 MCCBs?

Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed types) are available from VM6-125 through VM6-800 (3P/4P). Draw-out back-panel bases are supported on VM6-400, VM6-630, and VM6-800 in 3P configurations.

Does VIOX offer low-temperature-rise builds for compact switchboards?

Yes. In addition to the standard IEC/EN 60947-2 build, VM6 is available in Type V (50 K low temperature rise) and Type V1 (40 K low temperature rise) for high-ambient or densely packed distribution panels.

Benötigen Sie ein Produktangebot?
Lassen Sie es uns gemeinsam aufbauen.

Senden Sie uns das Produktmodell, die technischen Nennwerte, die Menge und die OEM-Anforderungen. Unser Team wird Ihre Anwendung prüfen und innerhalb eines Werktages antworten.

Angebot anfordern