VIOX VM6 Series Thermomagnetic MCCB (125A–2000A)

VIOX VM6 Series Thermomagnetic Molded Case Circuit Breakers (MCCB) cover 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current, 1P/2P/3P/4P) for AC 230 V / 400 V / 690 V distribution and motor protection. Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 offers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, low-temperature-rise options (40 K / 50 K), and a complete ecosystem of internal (shunt, UVT, auxiliary, alarm) and external (motor operator, rotary handle, plug-in, draw-out, interlock) accessories.

Frame Range
125–2000 A (8 Frames)
Max Breaking (400V)
Up to 100 kA Icu / 85 kA Ics
폴 구성
1P, 2P, 3P, 4P
Standards & Ui
IEC 60947-2 · Ui 1000 V / 8 kV

개요

The VIOX VM6 Series is a compact, low-temperature-rise thermomagnetic molded case circuit breaker (MCCB) platform covering 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current) for AC 50/60 Hz power distribution and motor protection up to 690 V AC. Engineered with a multiple contact-blade arc-quenching system and compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 delivers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, optional low-temperature-rise builds (40 K / 50 K), and a full ecosystem of internal and external switchgear accessories.

특징

  • Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Selectivity Category Class A).
  • 8 industrial frame sizes (125, 160, 250, 400, 630, 800, 1250, and 2000 A) covering 10 A to 2000 A.
  • Four breaking capacity tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC.
  • High insulation rating (Ui 1000 V) and impulse withstand voltage (Uimp 8 kV) across all frames.
  • Thermomagnetic distribution release (Code 3) or magnetic-only motor protection (Code 2), plus 4P neutral types A, B, C, and D.
  • Optional low-temperature-rise builds (Type V 50 K / Type V1 40 K) and 20 factory internal accessory combinations (Codes 08–78).

모델

Frame Series Rated Current In (A) Breaking Tiers 폴란드 Max Icu / Ics (400 V AC)
VM6-12510, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 AC, S, M, H1P, 2P, 3P, 4P50 kA / 50 kA
VM6-16010, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 AC, S, M, H2P (C/S), 3P, 4P50 kA / 50 kA
VM6-250100, 125, 140, 160, 180, 200, 225, 250 AC, S, M, H3P, 4P65 kA / 50 kA
VM6-400250, 315, 350, 400 AS, M, H3P, 4P65 kA / 65 kA
VM6-630400, 500, 630 AM, H3P, 4P65 kA / 65 kA
VM6-800500, 630, 700, 800 AM, H3P, 4P85 kA / 65 kA
VM6-1250630, 700, 800, 1000, 1250 AS, M, H3P, 4P85 kA / 65 kA
VM6-20001000, 1250, 1600, 2000 AM, H3P, 4P100 kA / 85 kA

사양

General Electrical & Standards Data

매개변수사양
적용 표준IEC/EN 60947-2; GB/T 14048.2
Frame current range (Inm)125, 160, 250, 400, 630, 800, 1250, 2000 A
Rated current range (In)10 A – 2000 A
Rated working voltage (Ue)AC 230 V / AC 400 V / AC 690 V
정격 절연 전압(Ui)1000 V
정격 임펄스 내전압(Uimp)8 kV
선택성 카테고리Class A
Overcurrent release typeThermomagnetic (Code 3) / Magnetic-only motor protection (Code 2)
Low temperature rise optionsStandard; Type V (50 K); Type V1 (40 K)

Breaking Capacity — VM6-125 to VM6-630

Model & Tier 폴란드 Ics (230 / 400 / 690 V) Icu (230 / 400 / 690 V)
VM6-125C1P / 2P / 3P / 4P5 / 5 / 3 kA8 / 8 / 5 kA
VM6-125S1P / 2P / 3P / 4P15 / 13 (3P/4P) / 3 (3P/4P) kA30 / 25 (3P/4P) / 6 (3P/4P) kA
VM6-125M1P / 2P / 3P / 4P35 (3P/4P) / 18 / 5 (3P/4P) kA36 (1P) · 50 (3P/4P) / 36 / 10 (3P/4P) kA
VM6-125H1P / 2P / 3P / 4P50 / 50 / 8 kA50 / 50 / 15 kA
VM6-160C2P / 3P / 4P7 / 10 / 2 kA10 / 15 / 8 kA
VM6-160S2P / 3P / 4P10 / 13 / 3 kA20 / 25 / 6 kA
VM6-160M3P / 4P25 / 18 / 5 kA30 / 36 / 10 kA
VM6-160H3P / 4P35 / 35 (2P) · 50 (3P/4P) / 10 kA50 / 50 / 15 kA
VM6-250C3P / 4P20 / 10 / 3 kA30 / 15 / 5 kA
VM6-250S3P / 4P25 / 15 / 4 kA50 / 30 / 8 kA
VM6-250M3P / 4P40 / 35 / 10 kA65 / 50 / 15 kA
VM6-250H3P / 4P50 / 50 / 15 kA70 / 65 / 20 kA
VM6-400S3P / 4P25 / 15 / 4 kA50 / 30 / 8 kA
VM6-400M3P / 4P40 / 35 / 10 kA65 / 50 / 20 kA
VM6-400H3P / 4P50 / 65 / 12 kA70 / 65 / 25 kA
VM6-630M3P / 4P20 / 35 / 5 kA30 / 50 / 10 kA
VM6-630H3P / 4P30 / 65 / 30 kA50 / 65 / 20 kA

Breaking Capacity — High-Current VM6-800 to VM6-2000

Model & Tier 폴란드 Ics (230 / 400 / 690 V) Icu (230 / 400 / 690 V)
VM6-800M3P / 4P65 / 50 / 15 kA80 / 65 / 25 kA
VM6-800H3P / 4P70 / 65 / 20 kA85 / 85 / 35 kA
VM6-1250S3P / 4P40 / 35 / 10 kA65 / 50 / 20 kA
VM6-1250M3P / 4P65 / 50 / 15 kA80 / 65 / 25 kA
VM6-1250H3P / 4P70 / 65 / 20 kA85 / 85 / 35 kA
VM6-2000M3P / 4P— / 50 / 20 kA— / 50 / 20 kA
VM6-2000H3P / 4P— / 85 / 20 kA— / 100 / 20 kA

Outline Dimensions (mm)

액자 폴란드 Width W (mm) Length L (mm) Height to Cover (mm) Height to Handle (mm)
VM6-1251P / 2P / 3P / 4P25 / 50 / 75 / 1001306894.5
VM6-1602P / 3P / 4P60 / 90 / 12015568 / 8294 / 108
VM6-2503P / 4P105 / 14016568 / 8896 / 116
VM6-4003P / 4P140 / 184257103152
VM6-6303P / 4P140 / 184257103152
VM6-8003P / 4P210 / 280275.5103152
VM6-12503P / 4P210 / 280275.5103152
VM6-20003P / 4P210 / 280340141244

External Accessories Compatibility

External Accessory VM6-125 VM6-160 / 250 VM6-400 / 630 / 800 VM6-1250 / 2000
Electric Motor Operation3P, 4P3P, 4P3P, 4P3P, 4P
Manual Rotary Operation3P, 4P3P, 4P3P, 4P3P, 4P
Extension Copper Bar1P–4P2P–4P (160) / 3P–4P (250)3P, 4P3P, 4P
기계적 연동3P, 4P3P, 4P3P, 4P사용할 수 없음
Plug-in Front / Back Panel3P, 4P3P, 4P3P, 4P사용할 수 없음
Draw-out Back-Panel Type사용할 수 없음사용할 수 없음3P only사용할 수 없음

선택 가이드

코드 위치 의미 Catalog Value or Options
VM6제품 시리즈Thermomagnetic molded case circuit breaker (IEC/EN 60947-2)
125–2000Frame current (Inm)125, 160, 250, 400, 630, 800, 1250, 2000 A
C / S / M / HBreaking capacity tierC (Basic), S (Standard), M (Moderate), H (High Breaking)
가동Handle / motor operatorDirect (blank), P1 (DC3 electric), P2 (DC6 electric), ZY1/ZF1/ZY2/ZF2/Z3 (rotary handle)
1 / 2 / 3 / 4극 수1P–4P (125 A); 2P–4P (160 A); 3P–4P (250–2000 A)
2 / 3Release method2 = Magnetic-only (motor protection); 3 = Thermal + magnetic (distribution)
00–78Internal accessory code00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux(+Alarm) · 50 Shunt+UVT · 60/61/62/68/69 Multi-Aux(+Alarm) · 70/71/78 UVT+Aux(+Alarm)
A / B / C / D4P neutral pole typeA: N unswitched, no trip · B: N switched, no trip · C: N switched + trip · D: N unswitched + trip
V / V1Low temperature riseV = 50 K low temperature rise; V1 = 40 K low temperature rise
Wiring & CoverMounting & terminal coverP (copper bar), Z1 (back-panel), Z2Q/Z2H/Z3Q/Z3H (plug-in), DF/DR (draw-out), K/JK/CK (wiring box), Z (terminal cover)

1. Match Frame & Breaking

Size the frame (125–2000 A) above load current and verify prospective fault level against C, S, M, or H Icu/Ics ratings at 400 V or 690 V AC.

2. Select Release & Neutral

Use Code 3 thermal-magnetic for power distribution feeders or Code 2 magnetic-only for motor circuits; specify 4P neutral type A, B, C, or D.

3. Specify Internal Codes

Order factory-installed shunt, undervoltage (DC 24/110/220 V, AC 230/400 V), auxiliary, or alarm contacts via codes 08–78.

4. Confirm Mounting & Drive

Choose fixed front/back panel, plug-in (up to 800 A), draw-out (400–800 A 3P), extended rotary handle, or DC3/DC6 motor operator.

설치

  • Verify panel cutout clearance and mounting depth against the VM6 outline dimension table (height to face cover and handle).
  • Confirm coil control voltage (DC 24 V, DC 110 V, DC 220 V, AC 230 V standard, or AC 400 V) for shunt, undervoltage, and electric motor operators.
  • For Code 50 (Shunt + UVT), note customized left-side UVT on VM6-125/160 and customized left-side shunt release on VM6-250.
  • Coordinate upstream incoming feeders with downstream VIOX MCB, RCBO및 SPD, or explore the full VIOX MCCB 제품군.

자주 묻는 질문

What current range and breaking capacity does the VIOX VM6 Series cover?

The VM6 Series spans 8 industrial frame sizes from 125 A to 2000 A (rated currents 10 A–2000 A) with four short-circuit breaking tiers (C, S, M, H) reaching up to 100 kA Icu and 85 kA Ics at 400 V AC.

Can VM6 MCCBs be used for both power distribution and motor protection?

Yes. Specify release code 3 (thermomagnetic) for power distribution feeders or release code 2 (magnetic-only, usage code 2) for motor protection circuits up to 630 A.

What are the differences between 4P neutral types A, B, C, and D?

Type A has an unswitched neutral without overcurrent release; Type B switches neutral with the three phase poles without overcurrent release; Type C switches neutral with overcurrent release; Type D keeps neutral permanently connected with overcurrent release.

Which control voltages are available for VM6 internal accessories and motor operators?

Shunt releases, undervoltage releases, and DC3/DC6 electric operating mechanisms support DC 24 V, DC 110 V, DC 220 V, AC 230 V (conventional standard), and AC 400 V.

Are plug-in and draw-out bases available for VM6 MCCBs?

Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed types) are available from VM6-125 through VM6-800 (3P/4P). Draw-out back-panel bases are supported on VM6-400, VM6-630, and VM6-800 in 3P configurations.

Does VIOX offer low-temperature-rise builds for compact switchboards?

Yes. In addition to the standard IEC/EN 60947-2 build, VM6 is available in Type V (50 K low temperature rise) and Type V1 (40 K low temperature rise) for high-ambient or densely packed distribution panels.