Обзор
The VIOX VM6 Series is a compact, low-temperature-rise thermomagnetic molded case circuit breaker (MCCB) platform covering 8 industrial frame sizes from 125 A to 2000 A (10 A–2000 A rated current) for AC 50/60 Hz power distribution and motor protection up to 690 V AC. Engineered with a multiple contact-blade arc-quenching system and compliant with IEC/EN 60947-2 and GB/T 14048.2 (Class A, Ui 1000 V, Uimp 8 kV), VM6 delivers four short-circuit breaking tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC, optional low-temperature-rise builds (40 K / 50 K), and a full ecosystem of internal and external switchgear accessories.
Характеристики
- Compliant with IEC/EN 60947-2 and GB/T 14048.2 (Selectivity Category Class A).
- 8 industrial frame sizes (125, 160, 250, 400, 630, 800, 1250, and 2000 A) covering 10 A to 2000 A.
- Four breaking capacity tiers (C, S, M, H) up to 100 kA Icu / 85 kA Ics at 400 V AC.
- High insulation rating (Ui 1000 V) and impulse withstand voltage (Uimp 8 kV) across all frames.
- Thermomagnetic distribution release (Code 3) or magnetic-only motor protection (Code 2), plus 4P neutral types A, B, C, and D.
- Optional low-temperature-rise builds (Type V 50 K / Type V1 40 K) and 20 factory internal accessory combinations (Codes 08–78).
Модели
| Frame Series | Rated Current In (A) | Breaking Tiers | Полюса | Max Icu / Ics (400 V AC) |
|---|---|---|---|---|
| VM6-125 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A | C, S, M, H | 1P, 2P, 3P, 4P | 50 kA / 50 kA |
| VM6-160 | 10, 16, 20, 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 A | C, S, M, H | 2P (C/S), 3P, 4P | 50 kA / 50 kA |
| VM6-250 | 100, 125, 140, 160, 180, 200, 225, 250 A | C, S, M, H | 3P, 4P | 65 kA / 50 kA |
| VM6-400 | 250, 315, 350, 400 A | S, M, H | 3P, 4P | 65 kA / 65 kA |
| VM6-630 | 400, 500, 630 A | M, H | 3P, 4P | 65 kA / 65 kA |
| VM6-800 | 500, 630, 700, 800 A | M, H | 3P, 4P | 85 kA / 65 kA |
| VM6-1250 | 630, 700, 800, 1000, 1250 A | S, M, H | 3P, 4P | 85 kA / 65 kA |
| VM6-2000 | 1000, 1250, 1600, 2000 A | M, H | 3P, 4P | 100 kA / 85 kA |
Технические характеристики
General Electrical & Standards Data
| Параметр | Спецификация |
|---|---|
| Применимые стандарты | IEC/EN 60947-2; GB/T 14048.2 |
| Frame current range (Inm) | 125, 160, 250, 400, 630, 800, 1250, 2000 A |
| Rated current range (In) | 10 A – 2000 A |
| Rated working voltage (Ue) | AC 230 V / AC 400 V / AC 690 V |
| Номинальное напряжение изоляции (Ui) | 1000 V |
| Номинальное импульсное выдерживаемое напряжение (Uimp) | : 8 кВ |
| Категория селективности | Класс A |
| Overcurrent release type | Thermomagnetic (Code 3) / Magnetic-only motor protection (Code 2) |
| Low temperature rise options | Standard; Type V (50 K); Type V1 (40 K) |
Breaking Capacity — VM6-125 to VM6-630
| Model & Tier | Полюса | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|
| VM6-125C | 1P / 2P / 3P / 4P | 5 / 5 / 3 kA | 8 / 8 / 5 kA |
| VM6-125S | 1P / 2P / 3P / 4P | 15 / 13 (3P/4P) / 3 (3P/4P) kA | 30 / 25 (3P/4P) / 6 (3P/4P) kA |
| VM6-125M | 1P / 2P / 3P / 4P | 35 (3P/4P) / 18 / 5 (3P/4P) kA | 36 (1P) · 50 (3P/4P) / 36 / 10 (3P/4P) kA |
| VM6-125H | 1P / 2P / 3P / 4P | 50 / 50 / 8 kA | 50 / 50 / 15 kA |
| VM6-160C | 2P / 3P / 4P | 7 / 10 / 2 kA | 10 / 15 / 8 kA |
| VM6-160S | 2P / 3P / 4P | 10 / 13 / 3 kA | 20 / 25 / 6 kA |
| VM6-160M | 3P / 4P | 25 / 18 / 5 kA | 30 / 36 / 10 kA |
| VM6-160H | 3P / 4P | 35 / 35 (2P) · 50 (3P/4P) / 10 kA | 50 / 50 / 15 kA |
| VM6-250C | 3P / 4P | 20 / 10 / 3 kA | 30 / 15 / 5 kA |
| VM6-250S | 3P / 4P | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-250M | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 15 kA |
| VM6-250H | 3P / 4P | 50 / 50 / 15 kA | 70 / 65 / 20 kA |
| VM6-400S | 3P / 4P | 25 / 15 / 4 kA | 50 / 30 / 8 kA |
| VM6-400M | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-400H | 3P / 4P | 50 / 65 / 12 kA | 70 / 65 / 25 kA |
| VM6-630M | 3P / 4P | 20 / 35 / 5 kA | 30 / 50 / 10 kA |
| VM6-630H | 3P / 4P | 30 / 65 / 30 kA | 50 / 65 / 20 kA |
Breaking Capacity — High-Current VM6-800 to VM6-2000
| Model & Tier | Полюса | Ics (230 / 400 / 690 V) | Icu (230 / 400 / 690 V) |
|---|---|---|---|
| VM6-800M | 3P / 4P | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-800H | 3P / 4P | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-1250S | 3P / 4P | 40 / 35 / 10 kA | 65 / 50 / 20 kA |
| VM6-1250M | 3P / 4P | 65 / 50 / 15 kA | 80 / 65 / 25 kA |
| VM6-1250H | 3P / 4P | 70 / 65 / 20 kA | 85 / 85 / 35 kA |
| VM6-2000M | 3P / 4P | — / 50 / 20 kA | — / 50 / 20 kA |
| VM6-2000H | 3P / 4P | — / 85 / 20 kA | — / 100 / 20 kA |
Outline Dimensions (mm)
| Рамка | Полюса | Width W (mm) | Length L (mm) | Height to Cover (mm) | Height to Handle (mm) |
|---|---|---|---|---|---|
| VM6-125 | 1P / 2P / 3P / 4P | 25 / 50 / 75 / 100 | 130 | 68 | 94.5 |
| VM6-160 | 2P / 3P / 4P | 60 / 90 / 120 | 155 | 68 / 82 | 94 / 108 |
| VM6-250 | 3P / 4P | 105 / 140 | 165 | 68 / 88 | 96 / 116 |
| VM6-400 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-630 | 3P / 4P | 140 / 184 | 257 | 103 | 152 |
| VM6-800 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-1250 | 3P / 4P | 210 / 280 | 275.5 | 103 | 152 |
| VM6-2000 | 3P / 4P | 210 / 280 | 340 | 141 | 244 |
External Accessories Compatibility
| External Accessory | VM6-125 | VM6-160 / 250 | VM6-400 / 630 / 800 | VM6-1250 / 2000 |
|---|---|---|---|---|
| Electric Motor Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Manual Rotary Operation | 3P, 4P | 3P, 4P | 3P, 4P | 3P, 4P |
| Extension Copper Bar | 1P–4P | 2P–4P (160) / 3P–4P (250) | 3P, 4P | 3P, 4P |
| Механическая блокировка | 3P, 4P | 3P, 4P | 3P, 4P | Нет в наличии |
| Plug-in Front / Back Panel | 3P, 4P | 3P, 4P | 3P, 4P | Нет в наличии |
| Draw-out Back-Panel Type | Нет в наличии | Нет в наличии | 3P only | Нет в наличии |
Руководство по выбору
| Код позиции | Значение | Catalog Value or Options |
|---|---|---|
| VM6 | Серия изделия | Thermomagnetic molded case circuit breaker (IEC/EN 60947-2) |
| 125–2000 | Frame current (Inm) | 125, 160, 250, 400, 630, 800, 1250, 2000 A |
| C / S / M / H | Breaking capacity tier | C (Basic), S (Standard), M (Moderate), H (High Breaking) |
| Операция | Handle / motor operator | Direct (blank), P1 (DC3 electric), P2 (DC6 electric), ZY1/ZF1/ZY2/ZF2/Z3 (rotary handle) |
| 1 / 2 / 3 / 4 | Количество полюсов | 1P–4P (125 A); 2P–4P (160 A); 3P–4P (250–2000 A) |
| 2 / 3 | Release method | 2 = Magnetic-only (motor protection); 3 = Thermal + magnetic (distribution) |
| 00–78 | Internal accessory code | 00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux(+Alarm) · 50 Shunt+UVT · 60/61/62/68/69 Multi-Aux(+Alarm) · 70/71/78 UVT+Aux(+Alarm) |
| A / B / C / D | 4P neutral pole type | A: N unswitched, no trip · B: N switched, no trip · C: N switched + trip · D: N unswitched + trip |
| V / V1 | Low temperature rise | V = 50 K low temperature rise; V1 = 40 K low temperature rise |
| Wiring & Cover | Mounting & terminal cover | P (copper bar), Z1 (back-panel), Z2Q/Z2H/Z3Q/Z3H (plug-in), DF/DR (draw-out), K/JK/CK (wiring box), Z (terminal cover) |
1. Match Frame & Breaking
Size the frame (125–2000 A) above load current and verify prospective fault level against C, S, M, or H Icu/Ics ratings at 400 V or 690 V AC.
2. Select Release & Neutral
Use Code 3 thermal-magnetic for power distribution feeders or Code 2 magnetic-only for motor circuits; specify 4P neutral type A, B, C, or D.
3. Specify Internal Codes
Order factory-installed shunt, undervoltage (DC 24/110/220 V, AC 230/400 V), auxiliary, or alarm contacts via codes 08–78.
4. Confirm Mounting & Drive
Choose fixed front/back panel, plug-in (up to 800 A), draw-out (400–800 A 3P), extended rotary handle, or DC3/DC6 motor operator.
Установка
- Verify panel cutout clearance and mounting depth against the VM6 outline dimension table (height to face cover and handle).
- Confirm coil control voltage (DC 24 V, DC 110 V, DC 220 V, AC 230 V standard, or AC 400 V) for shunt, undervoltage, and electric motor operators.
- For Code 50 (Shunt + UVT), note customized left-side UVT on VM6-125/160 and customized left-side shunt release on VM6-250.
- Coordinate upstream incoming feeders with downstream Автоматические выключатели VIOX, АВДТ, и СПД, or explore the full линейке VIOX MCCB.
ЧАСТО ЗАДАВАЕМЫЕ ВОПРОСЫ
What current range and breaking capacity does the VIOX VM6 Series cover?
The VM6 Series spans 8 industrial frame sizes from 125 A to 2000 A (rated currents 10 A–2000 A) with four short-circuit breaking tiers (C, S, M, H) reaching up to 100 kA Icu and 85 kA Ics at 400 V AC.
Can VM6 MCCBs be used for both power distribution and motor protection?
Yes. Specify release code 3 (thermomagnetic) for power distribution feeders or release code 2 (magnetic-only, usage code 2) for motor protection circuits up to 630 A.
What are the differences between 4P neutral types A, B, C, and D?
Type A has an unswitched neutral without overcurrent release; Type B switches neutral with the three phase poles without overcurrent release; Type C switches neutral with overcurrent release; Type D keeps neutral permanently connected with overcurrent release.
Which control voltages are available for VM6 internal accessories and motor operators?
Shunt releases, undervoltage releases, and DC3/DC6 electric operating mechanisms support DC 24 V, DC 110 V, DC 220 V, AC 230 V (conventional standard), and AC 400 V.
Are plug-in and draw-out bases available for VM6 MCCBs?
Yes. Front-panel and back-panel plug-in bases (split, integrated, and fixed types) are available from VM6-125 through VM6-800 (3P/4P). Draw-out back-panel bases are supported on VM6-400, VM6-630, and VM6-800 in 3P configurations.
Does VIOX offer low-temperature-rise builds for compact switchboards?
Yes. In addition to the standard IEC/EN 60947-2 build, VM6 is available in Type V (50 K low temperature rise) and Type V1 (40 K low temperature rise) for high-ambient or densely packed distribution panels.