VIOX Electric
Language

VOB3-63H Miniature Circuit Breaker

The VIOX VOB3-63H miniature circuit breaker provides overload and short-circuit protection for AC 50/60 Hz circuits. It covers rated currents from 1 A to 63 A, B, C and D tripping curves, and 1P to 4P configurations. Its 10 kA breaking capacity supports DIN-rail installation in residential, commercial and light-industrial distribution systems.

Rated Current
1-63 A
Pole Configuration
1P, 2P, 3P, 4P
Tripping Curves
B, C, D
Breaking Capacity
10 kA

Overview

The VOB3-63H is a miniature circuit breaker for overload and short-circuit protection in AC 50/60 Hz electrical circuits. It provides a rated short-circuit breaking capacity of 10 kA and covers rated currents from 1 A to 63 A. Available configurations include 1P, 2P, 3P and 4P versions with B, C or D tripping curves. The breaker is designed for DIN-rail installation in distribution boards, consumer units and control panels used in residential, commercial and light-industrial distribution systems. Rated-voltage options listed in the catalog extend up to 240/400 V or 400 V, depending on pole configuration.

Features

  • Overload and short-circuit protection for AC 50/60 Hz circuits.
  • Rated short-circuit breaking capacity of 10 kA.
  • Rated-current range from 1 A to 63 A.
  • B, C and D tripping-curve options.
  • Available in 1P, 2P, 3P and 4P configurations.
  • Compact 18 mm unipolar width with contact-position indication and top or bottom power entry.

Models

Catalog designation Pole configuration
VOB3-63H 1P 1P
VOB3-63H 2P 2P
VOB3-63H 3P 3P
VOB3-63H 4P 4P

Specifications

Electrical Data

Parameter Specification
Rated frame current 63 A
Rated current 1, 2, 3, 4, 6, 10, 16, 20, 25, 32, 40, 50, 63 A
Rated voltage 240/400 V (1P, 2P); 400 V (2P, 3P, 4P)
Rated frequency 50/60 Hz
Rated insulation voltage (Ui) 500 V
Rated impulse withstand voltage (Uimp) 4 kV
Dielectric strength test voltage (1 min) 2 kV
Rated short-circuit breaking capacity 10 kA

Protection Data

Parameter Specification
Tripping curves B (3-5 In), C (5-10 In), D (10-20 In)
Degree of protection IP20

Mechanical Data

Parameter Specification
Number of poles 1P, 2P, 3P, 4P
Unipolar width 18 mm
Mechanical life 20,000 operations
Electrical life 4,000 operations

Installation Data

Parameter Specification
Installation DIN rail
Wiring capacity 25 mm²
Incoming method Top or bottom power entry

Environmental and Standards Data

Parameter Specification
Reference temperature 30 °C
Compliant standards GB/T 10963.1, IEC 60898-1

Selection Guide

Code position Meaning Catalog value or options
VO Enterprise identification VO
B Miniature circuit breaker B
3 Design serial number 3
60 Shell frame current 60
B / C / D Tripping curve B, C or D
Rated-current code Rated current 1 A, 2 A, 3 A, 4 A, 6 A, 10 A, 16 A, 20 A, 25 A, 32 A, 40 A, 50 A or 63 A
H Short-circuit breaking-capacity level code H
1P / 2P / 3P / 4P Number of poles 1P, 2P, 3P or 4P

Rated Current

Select one of the catalog ratings from 1 A to 63 A according to the circuit rating and protection requirements.

Tripping Curve

Choose B, C or D according to the required instantaneous tripping range: B (3-5 In), C (5-10 In) or D (10-20 In).

Pole Configuration

Select a 1P, 2P, 3P or 4P configuration to match the circuit arrangement.

Rated Voltage

Confirm the catalog voltage for the selected pole configuration: 240/400 V is listed for 1P and 2P, while 400 V is listed for 2P, 3P and 4P.

Trip Curves

Characteristic Catalog value
Agreed non-tripping time at 1.13 In, cold state, for In ≤ 63 A 1 h
Agreed tripping time at 1.45 In, hot state, for In ≤ 63 A 1 h
B instantaneous characteristic 3-5 In
C instantaneous characteristic 5-10 In
D instantaneous characteristic 10-20 In

Dimensions

VOB3-63H MCB dimensional drawing
VOB3-63H MCB dimensional drawing.

Applications

  • Residential electrical distribution systems.
  • Commercial distribution boards.
  • Light-industrial control panels.
  • Consumer units requiring overload and short-circuit protection.

Installation

  • Install the selected configuration on a DIN rail in a suitable distribution board, consumer unit or control panel.
  • Confirm that the circuit voltage, rated current, pole configuration and tripping curve match the selected breaker.
  • Use conductors within the listed 25 mm² wiring capacity.
  • Power entry may be made from the top or bottom.

FAQ

What protection does the VOB3-63H provide?

It provides overload and short-circuit protection for AC 50/60 Hz electrical circuits.

What rated currents and tripping curves are available?

The catalog lists rated currents from 1 A to 63 A with B, C and D tripping curves.

Which pole configurations are offered?

The VOB3-63H is available in 1P, 2P, 3P and 4P configurations.

What is the rated short-circuit breaking capacity?

The rated short-circuit breaking capacity is 10 kA.

How is the VOB3-63H installed and connected?

It is designed for DIN-rail installation, has a listed wiring capacity of 25 mm² and permits top or bottom power entry.

Which standards are listed for the VOB3-63H?

The technical specifications list GB/T 10963.1 and IEC 60898-1.

Need a Product Quote?
Let’s Build It Together.

Send us the product model, technical ratings, quantity, and OEM requirements. Our team will review your application and respond within one business day.

Request a Quote