Overview
The VIOX VSP-SSD50X, VSP-SSD80, and VSP-SSD160 are dedicated SPD Backup Protectors (SCB / Special Disconnector) engineered to replace oversized MCBs or fuses in series with surge protection devices. They remain completely closed during 30 kA (10/350 μs) or 80–160 kA (8/20 μs) lightning surges, yet trip instantaneously at ≥3 A power-frequency follow current to prevent SPD thermal runaway and panel fires.
Features
- Eliminates the classic MCB/fuse mismatch: withstands full lightning impulses (Iimp 30 kA on VSP-SSD50X; Imax 80/160 kA on VSP-SSD80/160) without nuisance tripping.
- Ultra-sensitive power-frequency follow-current tripping (≥3 A) disconnects degraded MOVs long before thermal runaway or fire occurs.
- Ultra-low residual voltage drop across the SCB preserves the SPD's low Up clamping performance.
- 25,000 A short-circuit breaking capacity (Isccr) in 1P, 2P, 3P, and 4P DIN-rail formats (only L-N poles protected; never break PE).
Specifications
VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Electrical & Mechanical Specifications
| Parameter | Specification |
|---|---|
| Device Type | Dedicated SPD External Backup Disconnector (SCB / SSD) |
| Max Continuous Operating Voltage (Uc) | 440 V AC |
| Impulse Non-Trip Rating | VSP-SSD50X: Iimp 30 kA (10/350 μs) · VSP-SSD80: Imax 80 kA · VSP-SSD160: Imax 160 kA (8/20 μs) |
| Power-Frequency Trip Threshold | ≥3 A (fast disconnection on MOV short-circuit / degradation) |
| Admissible Short-Circuit Current (Isccr) | 25,000 A · Response Time: ≤100 ns |
| Network Systems | TN-S, TN-C, TT (install on L and N conductors only) |
| Terminals & Housing | 6–35 mm² (4.5 N·m) · PBT/PA UL94 V-0 · IP20 · -40°C to +70°C |
VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Available Poles & Dimensions
| Model | 1P | 2P | 3P | 4P |
|---|---|---|---|---|
| VSP-SSD80 (T2 80kA) | 18 × 90 × 67 mm | 36 × 90 × 67 mm | 54 × 90 × 67 mm | 72 × 90 × 67 mm |
| VSP-SSD50X / VSP-SSD160 | 36 × 90 × 67 mm | 72 × 90 × 67 mm | 108 × 90 × 67 mm | 144 × 90 × 67 mm |
Dimensions & Installation

- Wire strictly in series upstream of the SPD phase/neutral input terminals (never install an SCB in the PE earth path).
- Selection rule: pair VSP-SSD50X with Type 1 / T1+T2 SPDs; VSP-SSD80 with 20–80 kA Type 2 SPDs; VSP-SSD160 with 100–160 kA Type 2 SPDs.
- Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.
FAQ
Why use a VIOX VSP-SSD (SCB) instead of a standard 32A/63A MCB in front of an SPD?
Standard MCBs either trip falsely during a 20–80 kA lightning surge (leaving the panel unprotected) or fail to trip on low 5–15 A MOV leakage fault currents (causing SPD overheating and fire). VSP-SSD solves both issues simultaneously.