VIOX VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Dedicated SPD Backup Disconnector (SCB)

The VIOX VSP-SSD50X, VSP-SSD80, and VSP-SSD160 are dedicated SPD Backup Protectors (SCB / Special Disconnector) engineered to replace oversized MCBs or fuses in series with surge protection devices. They remain completely closed during 30 kA (10/350 μs) or 80–160 kA (8/20 μs) lightning surges, yet trip instantaneously at ≥3 A power-frequency follow current to prevent SPD thermal runaway and panel fires.

Série VIOX
VSP-SSD50X / VSP-SSD80 / VSP-SSD160
Tension nominale
AC 440V (50/60 Hz)
Surge Rating
T1 Iimp 30kA · T2 Imax 80kA / 160kA
Standard
IEC 61643-11 Coordinated · CE / CB

Vue d'ensemble

The VIOX VSP-SSD50X, VSP-SSD80, and VSP-SSD160 are dedicated SPD Backup Protectors (SCB / Special Disconnector) engineered to replace oversized MCBs or fuses in series with surge protection devices. They remain completely closed during 30 kA (10/350 μs) or 80–160 kA (8/20 μs) lightning surges, yet trip instantaneously at ≥3 A power-frequency follow current to prevent SPD thermal runaway and panel fires.

Caractéristiques

  • Eliminates the classic MCB/fuse mismatch: withstands full lightning impulses (Iimp 30 kA on VSP-SSD50X; Imax 80/160 kA on VSP-SSD80/160) without nuisance tripping.
  • Ultra-sensitive power-frequency follow-current tripping (≥3 A) disconnects degraded MOVs long before thermal runaway or fire occurs.
  • Ultra-low residual voltage drop across the SCB preserves the SPD's low Up clamping performance.
  • 25,000 A short-circuit breaking capacity (Isccr) in 1P, 2P, 3P, and 4P DIN-rail formats (only L-N poles protected; never break PE).

Spécifications

VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Electrical & Mechanical Specifications

ParamètreSpécification
Type d'appareilDedicated SPD External Backup Disconnector (SCB / SSD)
Max Continuous Operating Voltage (Uc)440 V AC
Impulse Non-Trip RatingVSP-SSD50X: Iimp 30 kA (10/350 μs) · VSP-SSD80: Imax 80 kA · VSP-SSD160: Imax 160 kA (8/20 μs)
Power-Frequency Trip Threshold≥3 A (fast disconnection on MOV short-circuit / degradation)
Admissible Short-Circuit Current (Isccr)25,000 A · Response Time: ≤100 ns
Network SystemsTN-S, TN-C, TT (install on L and N conductors only)
Terminals & Housing6–35 mm² (4.5 N·m) · PBT/PA UL94 V-0 · IP20 · -40°C to +70°C

VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Available Poles & Dimensions

Modèle1P2P3P4P
VSP-SSD80 (T2 80kA)18 × 90 × 67 mm36 × 90 × 67 mm54 × 90 × 67 mm72 × 90 × 67 mm
VSP-SSD50X / VSP-SSD16036 × 90 × 67 mm72 × 90 × 67 mm108 × 90 × 67 mm144 × 90 × 67 mm

Dimensions et Installation

VIOX VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Dedicated SPD Backup Disconnector (SCB) Dimensional Drawing (mm)
VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Wire strictly in series upstream of the SPD phase/neutral input terminals (never install an SCB in the PE earth path).
  • Selection rule: pair VSP-SSD50X with Type 1 / T1+T2 SPDs; VSP-SSD80 with 20–80 kA Type 2 SPDs; VSP-SSD160 with 100–160 kA Type 2 SPDs.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

FAQ

Why use a VIOX VSP-SSD (SCB) instead of a standard 32A/63A MCB in front of an SPD?

Standard MCBs either trip falsely during a 20–80 kA lightning surge (leaving the panel unprotected) or fail to trip on low 5–15 A MOV leakage fault currents (causing SPD overheating and fire). VSP-SSD solves both issues simultaneously.

Besoin d'un devis produit ?
Construisons-le ensemble.

Envoyez-nous le modèle du produit, les caractéristiques techniques, la quantité et les exigences OEM. Notre équipe examinera votre demande et vous répondra dans un délai d'un jour ouvré.

Demander un Devis