VIOX VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Dedicated SPD Backup Disconnector (SCB)

The VIOX VSP-SSD50X, VSP-SSD80, and VSP-SSD160 are dedicated SPD Backup Protectors (SCB / Special Disconnector) engineered to replace oversized MCBs or fuses in series with surge protection devices. They remain completely closed during 30 kA (10/350 μs) or 80–160 kA (8/20 μs) lightning surges, yet trip instantaneously at ≥3 A power-frequency follow current to prevent SPD thermal runaway and panel fires.

VIOX 시리즈
VSP-SSD50X / VSP-SSD80 / VSP-SSD160
정격 전압
AC 440V (50/60 Hz)
Surge Rating
T1 Iimp 30kA · T2 Imax 80kA / 160kA
준
IEC 61643-11 Coordinated · CE / CB

개요

The VIOX VSP-SSD50X, VSP-SSD80, and VSP-SSD160 are dedicated SPD Backup Protectors (SCB / Special Disconnector) engineered to replace oversized MCBs or fuses in series with surge protection devices. They remain completely closed during 30 kA (10/350 μs) or 80–160 kA (8/20 μs) lightning surges, yet trip instantaneously at ≥3 A power-frequency follow current to prevent SPD thermal runaway and panel fires.

특징

  • Eliminates the classic MCB/fuse mismatch: withstands full lightning impulses (Iimp 30 kA on VSP-SSD50X; Imax 80/160 kA on VSP-SSD80/160) without nuisance tripping.
  • Ultra-sensitive power-frequency follow-current tripping (≥3 A) disconnects degraded MOVs long before thermal runaway or fire occurs.
  • Ultra-low residual voltage drop across the SCB preserves the SPD's low Up clamping performance.
  • 25,000 A short-circuit breaking capacity (Isccr) in 1P, 2P, 3P, and 4P DIN-rail formats (only L-N poles protected; never break PE).

사양

VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Electrical & Mechanical Specifications

매개변수사양
장치 유형Dedicated SPD External Backup Disconnector (SCB / SSD)
Max Continuous Operating Voltage (Uc)440 V AC
Impulse Non-Trip RatingVSP-SSD50X: Iimp 30 kA (10/350 μs) · VSP-SSD80: Imax 80 kA · VSP-SSD160: Imax 160 kA (8/20 μs)
Power-Frequency Trip Threshold≥3 A (fast disconnection on MOV short-circuit / degradation)
Admissible Short-Circuit Current (Isccr)25,000 A · Response Time: ≤100 ns
Network SystemsTN-S, TN-C, TT (install on L and N conductors only)
Terminals & Housing6–35 mm² (4.5 N·m) · PBT/PA UL94 V-0 · IP20 · -40°C to +70°C

VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Available Poles & Dimensions

모델1P2P3P4P
VSP-SSD80 (T2 80kA)18 × 90 × 67 mm36 × 90 × 67 mm54 × 90 × 67 mm72 × 90 × 67 mm
VSP-SSD50X / VSP-SSD16036 × 90 × 67 mm72 × 90 × 67 mm108 × 90 × 67 mm144 × 90 × 67 mm

치수 및 설치

VIOX VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Dedicated SPD Backup Disconnector (SCB) Dimensional Drawing (mm)
VSP-SSD50X / VSP-SSD80 / VSP-SSD160 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Wire strictly in series upstream of the SPD phase/neutral input terminals (never install an SCB in the PE earth path).
  • Selection rule: pair VSP-SSD50X with Type 1 / T1+T2 SPDs; VSP-SSD80 with 20–80 kA Type 2 SPDs; VSP-SSD160 with 100–160 kA Type 2 SPDs.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

자주 묻는 질문

Why use a VIOX VSP-SSD (SCB) instead of a standard 32A/63A MCB in front of an SPD?

Standard MCBs either trip falsely during a 20–80 kA lightning surge (leaving the panel unprotected) or fail to trip on low 5–15 A MOV leakage fault currents (causing SPD overheating and fire). VSP-SSD solves both issues simultaneously.

제품 견적이 필요하신가요?
함께 만들어 갑시다.

제품 모델, 기술 정격, 수량 및 OEM 요구 사항을 보내주십시오. 당사 팀에서 귀하의 애플리케이션을 검토한 후 영업일 기준 1일 이내에 답변해 드리겠습니다.