ON DELAY VS OFF DELAY TIMERS: Complete Technical Comparison Guide (2026)

ON DELAY VS OFF DELAY TIMERS: Complete Technical Comparison Guide

Every year, industrial facilities lose an estimated $647 billion globally due to unplanned downtime—and improper timer relay selection accounts for 12-18% of control circuit failures. Choosing between on delay and off delay timers isn’t just a technical decision; it’s a critical factor in equipment longevity, energy efficiency, and operational safety.

Key Takeaways

  • On delay timers (TON) delay output activation after input signal, preventing false starts and equipment surge damage
  • Off delay timers (TOF) maintain output after input removal, ensuring proper cooling cycles and controlled shutdowns
  • Time ranges span from 0.1 seconds to 999 hours across industrial-grade models
  • Voltage compatibility includes 12VDC, 24VDC, 120VAC, and 240VAC configurations per IEC 61812-1 standards
  • Contact ratings typically range from 5A to 16A at 250VAC for general industrial applications
  • PLC programming uses TON and TOF function blocks with preset time (PT) and elapsed time (ET) parameters

What Are On Delay and Off Delay Timers?

Close-up of VIOX ON-delay and OFF-delay time relays mounted on a DIN rail with visible terminal markings
VIOX ON-delay and OFF-delay time relays mounted on a DIN rail with visible terminal markings.

Time delay relays are electromechanical or solid-state devices that control the timing of contact operation in electrical circuits. Unlike standard relays that switch instantaneously, time delay relays introduce precise, programmable delays between input signals and output actions.

On Delay Timer (TON) – Also called “delay-on-make” or “delay-on-operate,” this timer type delays the activation of its output contacts after receiving an input signal. The output remains OFF during the preset delay period and only energizes once the timer completes its countdown.

Off Delay Timer (TOF) – Known as “delay-on-break” or “delay-on-release,” this configuration activates its output immediately when the input energizes but maintains that output for a specified duration after the input signal is removed.

Both timer types comply with IEC 61812-1 standards for industrial timing relays and UL 508 certification for North American markets.


How On Delay Timers Work (TON)

The operational sequence of an on delay timer follows four distinct phases:

Phase 1: Standby State

  • Input contacts open, timer coil de-energized
  • Output contacts remain in normal state (NO contacts open, NC contacts closed)
  • Elapsed time (ET) = 0

Phase 2: Input Activation

  • Control signal applied to timer coil (terminals A1-A2)
  • Internal timing mechanism initiates countdown
  • Output contacts maintain initial state
  • ET begins incrementing toward preset time (PT)

Phase 3: Timing Period

  • Timer counts from 0 to PT (e.g., 0 to 10 seconds)
  • If input signal removed before PT reached, timer resets to ET = 0
  • Output remains inactive throughout delay

Phase 4: Output Activation

  • When ET = PT, output contacts change state
  • NO contacts close, NC contacts open
  • Output remains energized as long as input signal maintained
  • Upon input removal, output immediately de-energizes and timer resets
Technical cutaway diagram comparing the internal components of VIOX mechanical and solid state on delay timer relays
Comparison of internal components: Mechanical pneumatic vs. Solid-state electronic timer construction.

This timing behavior makes TON timers essential for applications requiring verification of sustained demand before committing equipment to operation. Learn more about how to wire a time relay for motor starter applications.


How Off Delay Timers Work (TOF)

Off delay timers operate with an inverse logic compared to on delay types:

Phase 1: Standby State

  • Input contacts open, timer coil de-energized
  • Output contacts in normal state
  • ET = 0, timer ready to accept trigger

Phase 2: Immediate Output Activation

  • Control signal applied to terminals A1-A2
  • Output contacts change state instantly (NO contacts close)
  • Connected load energizes without delay
  • Timer remains in standby, not yet timing

Phase 3: Input Signal Removal

  • Control switch opens or input signal removed
  • Output contacts remain in activated state
  • Timer begins countdown from 0 to PT
  • ET increments while output stays energized

Phase 4: Delayed Deactivation

  • When ET reaches PT (e.g., 15 seconds), output contacts return to normal state
  • NO contacts open, NC contacts close
  • Connected load de-energizes
  • If input reapplied during timing, most TOF relays reset and restart sequence
Motor control panel showing a VIOX time delay relay controlling a cooling fan system
Motor control panel featuring a VIOX time delay relay controlling a critical cooling fan system.

This behavior ensures equipment continues operating for a controlled period after the initiating signal ceases—critical for cooling cycles, material processing, and safety lighting applications.


Critical Differences: Side-by-Side Comparison

Feature On Delay Timer (TON) Off Delay Timer (TOF)
Timing Trigger Input signal application Input signal removal
Output Behavior on Input Delayed activation (waits PT) Immediate activation
Output Behavior on Input Removal Immediate deactivation Delayed deactivation (waits PT)
Primary Function Prevents false starts Ensures controlled shutdown
Typical Time Range 0.1s – 999h 0.1s – 999h
Reset Condition Input removal during timing Input reapplication (model-dependent)
IEC Symbol Dashed line input-to-output Solid line input-to-output
PLC Function Block TON TOF
Common Applications Motor soft start, HVAC sequencing Cooling fan delay, emergency lighting
Prevents Inrush current, false triggers Abrupt shutdowns, thermal shock
Power Loss Behavior Resets to 0 Most models reset (check datasheet)
Contact Configuration SPDT, DPDT available SPDT, DPDT available

Technical Specifications Comparison

Parameter Standard Range Industrial Grade Compliance Standards
Control Voltage (AC) 24VAC, 120VAC, 240VAC 90-265VAC universal IEC 61812-1, UL 508
Control Voltage (DC) 12VDC, 24VDC, 48VDC 12-48VDC range IEC 61812-1
Time Adjustment Range 0.1s – 30min 0.05s – 999h IEC 60255
Timing Accuracy ±5% at 25°C ±2% at 25°C IEC 61812-1
Contact Rating (Resistive) 5A @ 250VAC 10A @ 250VAC UL 508, IEC 60947-5-1
Contact Rating (Inductive) 3A @ 250VAC (cosφ 0.4) 5A @ 250VAC IEC 60947-5-1
Mechanical Life 10 million operations 30 million operations IEC 61810-1
Electrical Life 100,000 operations @ rated load 300,000 operations IEC 61810-1
Operating Temperature -10°C to +55°C -25°C to +70°C IEC 60068-2
Mounting Type DIN rail (35mm), panel mount DIN rail, socket, PCB IEC 60715
Protection Rating IP20 (standard) IP40, IP54 (industrial) IEC 60529
Dielectric Strength 2000VAC (1 minute) 4000VAC (1 minute) IEC 61812-1
Timing diagram comparison of VIOX On Delay TON and Off Delay TOF timer waveforms
Timing diagram comparison of VIOX On Delay (TON) and Off Delay (TOF) timer waveforms.

Real-World Applications by Industry

Manufacturing & Industrial Automation

Conveyor Belt Sequencing (TON Application)

  • Problem: Simultaneous motor startup causes voltage sag and breaker trips
  • Solution: On delay timers stagger motor activation in 3-5 second intervals
  • Settings: PT = 3-5s per motor, 24VDC control voltage
  • Result: Reduces inrush current by 60-75%, prevents nuisance tripping

Machine Tool Cooling (TOF Application)

  • Problem: Spindle motors require coolant circulation after shutdown to prevent thermal warping
  • Solution: Off delay timer maintains coolant pump operation post-machining
  • Settings: PT = 120-180s, 120VAC control
  • Result: Extends spindle bearing life by 40%, reduces thermal distortion

HVAC Systems

Compressor Anti-Short-Cycle Protection (TON)

  • Prevents compressor restart within 3-5 minutes of shutdown
  • Protects against liquid refrigerant slugging and bearing damage
  • Typical setting: PT = 180-300s
  • Complies with ASHRAE 15 safety standards

Exhaust Fan Purge Cycle (TOF)

  • Maintains ventilation fan operation after equipment shutdown
  • Ensures complete fume/heat evacuation from enclosures
  • Typical setting: PT = 60-120s
  • Meets NFPA 70 (NEC) Article 430.44 requirements

Motor Control Applications

Star-Delta Starter Transition (TON)

  • Delays transition from star to delta configuration during motor startup
  • Reduces starting current to 33% of direct-on-line starting
  • Typical setting: PT = 5-15s depending on motor inertia
  • Reference: Star Delta Starter Wiring Diagram

Cooling Fan Post-Run (TOF)

  • Maintains fan operation after motor shutdown for thermal management
  • Prevents bearing damage from residual heat
  • Typical setting: PT = 30-90s
  • Critical for motors >10HP in enclosed environments

Safety & Emergency Systems

Emergency Lighting (TOF)

  • Keeps egress lighting active after power interruption
  • Provides time for backup generator startup or safe evacuation
  • Typical setting: PT = 30-60s
  • Complies with NFPA 101 Life Safety Code

Fire Suppression Delay (TON)

  • Provides verification period before activating suppression systems
  • Prevents false discharge from transient smoke detector signals
  • Typical setting: PT = 10-30s
  • Meets NFPA 72 fire alarm code requirements
Industry/Application Timer Type Typical PT Range Key Benefit
Motor soft start TON 3-10s Reduces inrush current
Cooling fan delay TOF 30-180s Prevents thermal shock
HVAC sequencing TON 30-300s Staggers equipment startup
Emergency lighting TOF 30-90s Maintains illumination
Pump alternation TON 1-60s Equalizes wear
Conveyor sequencing TON 2-5s Prevents overload
Compressor protection TON 180-300s Anti-short-cycle
Ventilation purge TOF 60-300s Ensures air exchange

Wiring Methods and Circuit Diagrams

Wiring schematic comparing ladder logic diagrams for VIOX ON delay and OFF delay relays
Ladder logic schematic comparison: Standard IEC wiring for ON-Delay vs OFF-Delay configurations.

On Delay Timer Wiring (120VAC Control)

Wiring AH3-3 Timer For ON-Delay
Detailed wiring diagram for VIOX AH3-3 Timer in ON-Delay configuration.

Terminal Connections:

  • A1, A2: Control voltage input (120VAC from control switch)
  • 15-18: Normally Open (NO) timed contact
  • 15-16: Normally Closed (NC) timed contact
  • Load: Connected between contact 18 and L2 (neutral)

Operational Sequence:

  1. Close control switch → 120VAC applied to A1-A2
  2. Timer begins countdown (e.g., PT = 10s)
  3. After 10s, contact 15-18 closes, energizing load
  4. Open control switch → contact 15-18 opens immediately, load de-energizes

Off Delay Timer Wiring (24VDC Control)

Wiring AH3-3 Timer For OFF-Delay
Detailed wiring diagram for VIOX AH3-3 Timer in OFF-Delay configuration.

Terminal Connections:

  • A1 (+), A2 (-): DC control voltage (24VDC from PLC output)
  • 15-18: NO timed contact
  • 15-16: NC timed contact
  • Load: Connected through contact 15-18

Operational Sequence:

  1. PLC output HIGH → 24VDC applied to A1-A2
  2. Contact 15-18 closes immediately, load energizes
  3. PLC output LOW → timer begins countdown (e.g., PT = 15s)
  4. After 15s, contact 15-18 opens, load de-energizes

Critical Wiring Notes:

  • Always verify coil voltage matches control circuit voltage
  • Use appropriately rated wire gauge for contact current (14 AWG for 15A circuits)
  • Install surge suppression (RC snubber or MOV) across inductive loads
  • Follow NEC Article 430.72 for motor control circuit protection
  • Ensure proper grounding per IEC 60364-5-54

For comprehensive wiring guidance, see Timer Relay Voltage Selection Guide.


PLC Programming: TON vs TOF Instructions

Modern PLCs implement timer functions as standardized IEC 61131-3 function blocks. Understanding these blocks is essential for industrial automation.

TON Function Block (On Delay)

Standard Parameters:

  • IN (BOOL): Input trigger signal
  • PT (TIME): Preset time value (e.g., T#10S for 10 seconds)
  • Q (BOOL): Output status (TRUE when ET ≥ PT)
  • ET (TIME): Elapsed time since IN went TRUE

Ladder Logic Example:

|--[ ]--[TON]--( )--|
   IN    PT=T#5S  Q
         ET

Operational Logic:

  • When IN transitions FALSE → TRUE, ET begins incrementing
  • Q remains FALSE until ET = PT
  • If IN returns to FALSE before ET = PT, timer resets (ET = 0, Q = FALSE)
  • Q stays TRUE as long as IN = TRUE and ET ≥ PT

Typical Applications:

  • Motor starter delay to allow contactor settling
  • Sensor debouncing (PT = T#100MS)
  • Sequential machine startup

TOF Function Block (Off Delay)

Standard Parameters:

  • IN (BOOL): Input trigger signal
  • PT (TIME): Preset time value
  • Q (BOOL): Output status (TRUE when IN = TRUE OR timing active)
  • ET (TIME): Elapsed time since IN went FALSE

Ladder Logic Example:

|--[ ]--[TOF]--( )--|
   IN    PT=T#15S Q
         ET

Operational Logic:

  • When IN = TRUE, Q immediately becomes TRUE (ET = 0)
  • When IN transitions TRUE → FALSE, ET begins incrementing
  • Q remains TRUE during timing period
  • When ET = PT, Q transitions to FALSE
  • If IN returns to TRUE during timing, ET resets to 0 and Q stays TRUE

Typical Applications:

  • Cooling fan post-run after motor shutdown
  • Stairwell lighting with occupancy sensor
  • Pump run-on after flow switch opens

PLC Platform Variations:

  • Siemens S7: TON/TOF in IEC timer library (T#format)
  • Allen-Bradley: TON/TOF with .PRE (preset) and .ACC (accumulator) tags
  • Schneider: TON/TOF with %TMi addressing
  • Mitsubishi: T (timer) instruction with K constant for preset

For detailed PLC programming examples, explore Time Delay Relays Complete Guide.


Selection Guide: When to Use Each Type

Choose ON DELAY (TON) When:

Preventing False Starts

  • Momentary signals should not trigger equipment
  • Verification of sustained demand required
  • Example: Pressure switch with 5s verification delay

Sequencing Equipment Startup

  • Multiple motors must start in timed intervals
  • Prevents simultaneous inrush current
  • Example: Conveyor system with 3-motor sequence

Debouncing Mechanical Contacts

  • Switch bounce causes multiple triggers
  • Clean signal required for downstream logic
  • Example: Limit switch with 100ms debounce

Safety Interlocks

  • Guard door must remain closed for set duration before machine start
  • Prevents bypass of safety systems
  • Example: 3-second door verification before press cycle

Choose OFF DELAY (TOF) When:

Controlled Equipment Shutdown

  • Gradual deactivation prevents damage
  • Allows completion of mechanical cycles
  • Example: Spindle coolant pump 120s post-run

Thermal Management

  • Cooling required after equipment shutdown
  • Prevents bearing/component damage
  • Example: Motor cooling fan 60s delay

Maintaining Illumination

  • Lighting should remain on briefly after occupancy signal ends
  • Provides safe egress time
  • Example: Stairwell lights 45s after motion detection

Process Completion

  • Material must fully clear before next cycle
  • Ensures quality and prevents jams
  • Example: Packaging line discharge conveyor 30s run-on

Decision Tree Approach

Question 1: Does the load need to activate immediately when the control signal appears?

  • YES → Consider TOF (immediate activation, delayed deactivation)
  • NO → Consider TON (delayed activation)

Question 2: Is the delay needed at startup or shutdown?

  • Startup → TON
  • Shutdown → TOF

Question 3: Are you preventing false triggers or ensuring complete cycles?

  • Preventing false triggers → TON
  • Ensuring complete cycles → TOF

Question 4: What happens if power is lost during timing?

  • Must reset and restart → Standard TON/TOF
  • Must resume from last state → Retentive timer (RTO) required

For comprehensive relay selection criteria, reference How to Choose the Right Timer Relay.


Common Mistakes and Troubleshooting

Problem Likely Cause Solution Prevention
Timer doesn’t start timing Incorrect coil voltage Verify voltage with multimeter; check nameplate rating Always confirm coil voltage matches control circuit
Output activates immediately (TON) Wiring error – TOF mode selected Check mode selector switch/jumper; verify against datasheet Label timer type clearly during installation
Timer resets prematurely Input signal unstable/bouncing Add RC filter (0.1µF + 10kΩ) across input terminals Use contact debouncing for mechanical switches
Inconsistent timing Temperature variation affecting accuracy Relocate timer away from heat sources; use temperature-compensated model Maintain ambient temp within ±10°C of calibration temp
Contacts welding/failing Exceeding contact rating Measure actual load current; add contactor for loads >80% rating Always derate contacts to 70-80% of maximum rating
Timer doesn’t reset after power loss Capacitor-based timer retaining charge Discharge timing capacitor (short A1-A2 for 5s with power off) Use electronic timers with guaranteed reset on power loss
Erratic operation in noisy environment EMI/RFI interference Install ferrite core on control wires; use shielded cable; add MOV suppression Route control wiring away from VFDs, contactors, welders

Advanced Troubleshooting Techniques

Measuring Timing Accuracy:

  1. Apply rated control voltage to A1-A2
  2. Use stopwatch or oscilloscope to measure actual delay
  3. Compare to preset time (PT)
  4. Acceptable tolerance: ±5% per IEC 61812-1
  5. If outside tolerance, check for voltage variation or replace timer

Contact Resistance Testing:

  1. De-energize circuit and disconnect load
  2. Energize timer to close contacts
  3. Measure resistance across NO contacts with milliohm meter
  4. Acceptable: <50mΩ for new contacts, <200mΩ for aged contacts
  5. > 200mΩ indicates oxidation/wear—replace timer

Insulation Resistance Testing:

  1. De-energize and disconnect all wiring
  2. Apply 500VDC between coil and contacts using megohmmeter
  3. Acceptable: >100MΩ per IEC 61810-1
  4. <10MΩ indicates insulation breakdown—replace immediately

FAQ

What is the main difference between on delay and off delay timers?

The fundamental difference lies in when the timing delay occurs. An on delay timer (TON) delays the activation of its output after the input signal is applied—the output waits for the preset time before turning ON. An off delay timer (TOF) activates its output immediately when the input is applied but delays the deactivation—the output waits for the preset time before turning OFF after the input is removed. In practical terms: TON = “wait before starting,” TOF = “keep running after signal ends.”

When should I use a TON timer instead of a TOF timer?

Use a TON timer when you need to verify that a condition is sustained before committing equipment to operation. This is critical for:

  • Preventing false starts from momentary signals (pressure spikes, voltage transients)
  • Sequencing equipment to stagger startup and reduce inrush current
  • Safety interlocks requiring verification periods (guard doors, two-hand controls)
  • Debouncing mechanical switches to eliminate contact bounce

Use a TOF timer when you need equipment to continue operating after the initiating signal ends:

  • Cooling cycles for motors, compressors, or heat-generating equipment
  • Process completion ensuring materials fully clear before shutdown
  • Emergency lighting maintaining illumination during power transitions
  • Ventilation purge cycles after equipment shutdown

Can I use an on delay timer for motor cooling applications?

No—using a TON timer for motor cooling is incorrect and potentially damaging. Motor cooling requires the fan to continue running after the motor stops, which is an off delay (TOF) function. A TON timer would delay the fan startup when the motor starts, providing no cooling benefit. The correct configuration is:

  • Motor contactor auxiliary contact → TOF timer input
  • TOF timer output → Cooling fan contactor coil
  • Preset time: 60-180 seconds depending on motor size and duty cycle

This ensures the fan runs immediately when the motor starts and continues for the preset time after the motor stops. For detailed motor control wiring, see Contactors vs Relays: Understanding the Key Differences.

What voltage should I choose for my time delay relay?

Voltage selection depends on your control circuit standard:

  • 24VDC – Most common for PLC-controlled systems, low-voltage safety circuits, and modern industrial automation. Advantages: Safe, noise-immune, compatible with electronic controls.
  • 120VAC – Standard for North American residential/light commercial and direct switch control without transformers.
  • 240VAC – Used in European/international installations (230VAC), heavy industrial equipment, and three-phase motor control circuits.
  • 12VDC – Specialized applications like automotive, mobile equipment, and battery-powered systems.
  • Universal voltage (90-265VAC/DC) – Best for international equipment, uncertain voltage environments, and flexibility in installation.

Always verify the control voltage available at the installation location before ordering. For comprehensive guidance, reference Timer Relay Voltage Selection Guide: 12V, 24V, 120V, 230V.

How do I wire an off delay timer in a control circuit?

Basic OFF Delay Wiring (120VAC):

  1. Power Supply: Connect L1 (hot) and L2 (neutral) to control circuit
  2. Control Switch: Wire control switch in series with L1
  3. Timer Coil: Connect A1 to control switch output, A2 to L2
  4. Load Connection: Wire load between timer NO contact (terminal 18) and L2
  5. Common Terminal: Connect timer common (terminal 15) to L1

Operation: When control switch closes, timer coil energizes and contact 15-18 closes immediately, powering the load. When control switch opens, the load remains powered for the preset time, then de-energizes.

Critical Safety Notes:

  • Use appropriately rated wire (14 AWG minimum for 15A circuits)
  • Install overcurrent protection per NEC Article 430.72
  • Add surge suppression across inductive loads (MOV or RC snubber)
  • Ensure proper grounding of control panel per NEC Article 250

For visual wiring diagrams and step-by-step procedures, see What is a Time Relay.

What are common failure modes of time delay relays?

1. Contact Failure (40% of failures)

  • Symptoms: Intermittent operation, no output despite timing complete
  • Causes: Exceeding contact rating, inductive load without suppression, environmental contamination
  • Prevention: Derate contacts to 70-80% of rating, use contactors for heavy loads, install in IP54+ enclosures

2. Timing Drift (25% of failures)

  • Symptoms: Actual delay doesn’t match preset, inconsistent timing
  • Causes: Capacitor aging (electromechanical timers), temperature extremes, voltage variation
  • Prevention: Use electronic timers with crystal oscillators, maintain stable ambient temperature, regulate control voltage

3. Coil Burnout (20% of failures)

  • Symptoms: No response to input signal, coil resistance infinite
  • Causes: Overvoltage, sustained overcurrent, insulation breakdown
  • Prevention: Verify voltage compatibility, use fused control circuits, avoid moisture exposure

4. EMI/RFI Interference (10% of failures)

  • Symptoms: Erratic timing, false triggering, premature resets
  • Causes: Proximity to VFDs, contactors, welders, or radio transmitters
  • Prevention: Use shielded control cables, install ferrite cores, separate control and power wiring by >12 inches

5. Mechanical Wear (5% of failures)

  • Symptoms: Increasing contact resistance, delayed contact closure
  • Causes: Exceeding mechanical life rating, vibration, shock
  • Prevention: Select timers with appropriate mechanical life rating, use vibration dampening mounts

Conclusion

Selecting between on delay and off delay timers requires understanding the fundamental timing behavior: TON delays activation, while TOF delays deactivation. This seemingly simple distinction has profound implications for equipment protection, energy efficiency, and operational safety.

Key Decision Factors:

  • Application requirement: Startup control (TON) vs. shutdown control (TOF)
  • Voltage compatibility: Match control circuit voltage (12VDC to 240VAC)
  • Contact rating: Ensure adequate capacity with 20-30% safety margin
  • Time range: Verify preset range covers your application (0.1s to 999h)
  • Environmental conditions: Select appropriate IP rating and temperature range
  • Standards compliance: Verify IEC 61812-1, UL 508, or equivalent certification

VIOX Time Delay Relays offer comprehensive solutions for both on delay and off delay applications, featuring:

  • Universal voltage inputs (90-265VAC/DC) for installation flexibility
  • Wide timing ranges (0.05s to 999h) covering virtually all industrial applications
  • High-capacity contacts (10A @ 250VAC) with extended electrical life
  • IEC 61812-1 and UL 508 certified for global compliance
  • DIN rail mounting for rapid installation and maintenance

For technical consultation on timer relay selection for your specific application, contact VIOX technical support at [email protected] or visit our product selection guide.


Related Resources:

Author picture

Hi, I’m Joe, a dedicated professional with 12 years of experience in the electrical industry. At VIOX Electric, my focus is on delivering high-quality electrical solutions tailored to meet the needs of our clients. My expertise spans industrial automation, residential wiring, and commercial electrical systems.Contact me [email protected] if u have any questions.

Table of Contents
    Menambah satu kepala untuk mulai menghasilkan isi kandungan
    Ask for Quote Now