VIOX ELECTRIC
言語

VIOX VSP-X15 / VSP-X30 / VSP-X50 Graphite Spark-Gap AC Type 1 Lightning Arrester

The VIOX VSP-X15, VSP-X30, and VSP-X50 are encapsulated multi-layer graphite spark-gap AC Type 1 lightning current arresters engineered for direct lightning strike protection (Iimp 15 kA, 30 kA, and 50 kA at 10/350 μs). Featuring zero leakage current, 50 kA follow-current extinguishing capability (Ifi), and 50 kA short-circuit withstand, they are built for heavy industrial substations and telecom main incoming switchboards.

VIOXシリーズ
VSP-X15 / VSP-X30 / VSP-X50
定格電圧
AC 275V / 320V / 385V / 440V
Surge Rating
Iimp 15 / 30 / 50 kA (10/350μs)
標準
IEC 61643-11 · Type 1 · 50kA Ifi

概要

The VIOX VSP-X15, VSP-X30, and VSP-X50 are encapsulated multi-layer graphite spark-gap AC Type 1 lightning current arresters engineered for direct lightning strike protection (Iimp 15 kA, 30 kA, and 50 kA at 10/350 μs). Featuring zero leakage current, 50 kA follow-current extinguishing capability (Ifi), and 50 kA short-circuit withstand, they are built for heavy industrial substations and telecom main incoming switchboards.

特徴

  • Multi-layer encapsulated graphite spark-gap technology handles extreme 15 kA, 30 kA, and 50 kA (10/350 μs) direct lightning currents.
  • High 50 kA follow-current interrupt rating (Ifi) and 50,000 A short-circuit rating (Isccr) with zero standby leakage (Ipe = NONE).
  • Constant Up 2.5 kV clamping level across Uc 275 V, 320 V, 385 V, and 440 V AC systems.
  • No blowout arc emission — safely mounts inside compact metal distribution panels on a standard 35 mm DIN rail.

仕様

VSP-X15 / VSP-X30 / VSP-X50 Electrical & Mechanical Specifications

パラメータ仕様
SPD ClassificationType 1 (Class I) Graphite Spark-Gap · IEC 61643-11
Max Continuous Operating Voltage (Uc)275 V / 320 V / 385 V / 440 V AC
Lightning Impulse Current (Iimp, 10/350 μs)VSP-X15: 15 kA · VSP-X30: 30 kA · VSP-X50: 50 kA
電圧保護レベル(Up)2.5 kV (L-N & N-PE) · Response Time: ≤100 ns
Follow Current Interrupt Rating (Ifi)50 kA · Isccr: 50,000 A · Leakage Ipe: NONE
Recommended Backup SCBVIOX VSP-SSD50X
Terminals & Housing6–35 mm² (2.5 N·m) · PBT/PA UL94 V-0 · IP20 · 35 mm DIN rail

VSP-X15 / VSP-X30 / VSP-X50 Available Poles & Dimensions

ポール1P1+NPE / 2P3P4P / 3+NPE
Dimensions (W × H × D)36 × 90 × 68 mm72 × 90 × 68 mm108 × 90 × 68 mm144 × 90 × 68 mm

寸法と設置

VIOX VSP-X15 / VSP-X30 / VSP-X50 Graphite Spark-Gap AC Type 1 Lightning Arrester Dimensional Drawing (mm)
VSP-X15 / VSP-X30 / VSP-X50 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Install at LPZ 0A → LPZ 1 main incoming switchgear where maximum 50 kA (10/350 μs) lightning current capacity is mandated.
  • Coordinate downstream with VIOX VSP-40 Type 2 SPD for sensitive equipment requiring Up ≤1.5 kV.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

よくあるご質問

What is the benefit of a graphite spark-gap Type 1 SPD over an MOV-only SPD?

Encapsulated graphite spark gaps withstand massive 50 kA (10/350 μs) direct lightning energy with zero standby leakage current and virtually no thermal aging over decades of service.

製品の見積もりが必要ですか?
私たちと一緒に作り上げましょう。.

製品モデル、技術定格、数量、およびOEM要件をお送りください。当社のチームがお客様の用途を確認し、1営業日以内に回答いたします。.

見積依頼