VIOX KCQJ7 モーターコントローラー

Enclosed motor controllers with overload and phase-loss
保護機能を無効にすることで。.

  • 380 Vで最大18.5 kW
  • Five current setting ranges from 0.72–2.4 A to 30–38 A
  • KCQJ7-W option for automatic liquid-level control
  • IP55 enclosure with start/stop buttons and status indicators

概要

VIOX KCQJ7 motor controllers combine motor switching, overload
protection and phase-loss protection in an IP55 enclosure with
start/stop buttons and status indicators. The range supports motors up
to 18.5 kW at 380 V, with model-specific current setting ranges up to 38
A.

Versions and Features

バージョン 機能
KCQJ7 Motor start/stop control with overload and phase-loss
保護
KCQJ7-W Adds liquid-level relay control for automatic water pumping and
draining
  • CJX2s contactor with a matched JD-8 motor protector.
  • Front-panel start/stop buttons and circuit-status indicators.
  • AC 220 V or AC 380 V control supply options.
  • Detachable cover and connector-based wiring for maintenance
    access.

Liquid-level control is intended for suitable conductive water
applications such as water tanks and reservoirs. It is not suitable for
low-conductivity liquids such as petroleum or purified water, flammable
or explosive chemical liquids, or high-density sewage.

技術仕様

電流設定範囲 定格フレーム電流 AC-3 power at 380 V AC-3 power at 220 V 電磁接触器
0.72–2.4 A 2.4 A 1.1 kW 0.55 kW CJX2s-09
3.5–11 A 12 A 5.5 kW 3 kW CJX2s-12
10–16 A 16 A 7.5 kW 4 kW CJX2s-18
20–25 A 25 A 7 kW 5.5 kW CJX2s-25
30–38 A 38 A 18.5 kW 9 kW CJX2s-38

Select KCQJ7 or KCQJ7-W together with the required current range. The
listed ranges are separate selections, not one continuously adjustable
0.72–38 A device.

パラメータ 仕様
Main-circuit voltage described in application section AC 380 V
頻度 50 Hz または 60 Hz
Control supply options AC 220 V; AC 380 V
エンクロージャー保護(筐体保護等級) IP55
Phase-loss operating time ≤5 s under the specified three-phase monitoring condition
Liquid-level electrode lead distance Up to 200 m for applicable liquid-level configuration
周囲温度 −5°C to +40°C; 24-hour average ≤+35°C
Installation altitude ≤2000 m
汚染度 3
設置カテゴリー II

Configure the motor protector for the motor nameplate current before
commissioning. Frame current, protector adjustment range and motor
operating current are distinct selection values. Motor overload
protection does not replace coordinated short-circuit protection.

Wiring and Dimensions

The supplied sheet shows KCQJ7 and KCQJ7-W circuits with a 380 V main
supply and either 380 V or 220 V control supply. Match the diagram to
the supplied version and control voltage. The enclosure maximum outline
is 118 mm wide × 200 mm high × 127 mm deep.

KCQJ7 and KCQJ7-W wiring diagrams and enclosure dimensions

ご注文について

Specify KCQJ7 or KCQJ7-W, motor voltage and power, motor nameplate
current, required current setting range, control supply voltage,
liquid-level control requirements and quantity.