نمای کلی
VIOX KCQJ7 motor controllers combine motor switching, overload
protection and phase-loss protection in an IP55 enclosure with
start/stop buttons and status indicators. The range supports motors up
to 18.5 kW at 380 V, with model-specific current setting ranges up to 38
الف.
Versions and Features
| نسخه | عملکرد |
|---|---|
| KCQJ7 | Motor start/stop control with overload and phase-loss حفاظت |
| KCQJ7-W | Adds liquid-level relay control for automatic water pumping and draining |
- CJX2s contactor with a matched JD-8 motor protector.
- Front-panel start/stop buttons and circuit-status indicators.
- AC 220 V or AC 380 V control supply options.
- Detachable cover and connector-based wiring for maintenance
access.
Liquid-level control is intended for suitable conductive water
applications such as water tanks and reservoirs. It is not suitable for
low-conductivity liquids such as petroleum or purified water, flammable
or explosive chemical liquids, or high-density sewage.
مشخصات فنی
| محدوده تنظیم جریان | جریان نامی فریم | AC-3 power at 380 V | AC-3 power at 220 V | کنتاکتور |
|---|---|---|---|---|
| 0.72–2.4 A | 2.4 A | 1.1 kW | 0.55 kW | CJX2s-09 |
| 3.5–11 A | 12 A | 5.5 kW | 3 kW | CJX2s-12 |
| 10–16 A | ۱۶ الف | 7.5 kW | 4 kW | CJX2s-18 |
| 20–25 A | 25 آمپر | 11 کیلووات | 5.5 kW | CJX2s-25 |
| 30–38 A | 38 A | 18.5 kW | 9 kW | CJX2s-38 |
Select KCQJ7 or KCQJ7-W together with the required current range. The
listed ranges are separate selections, not one continuously adjustable
0.72–38 A device.
| پارامتر | مشخصات |
|---|---|
| Main-circuit voltage described in application section | AC 380 V |
| فرکانس | 50 هرتز یا 60 هرتز |
| Control supply options | AC 220 V; AC 380 V |
| Enclosure protection | IP55 |
| Phase-loss operating time | ≤5 s under the specified three-phase monitoring condition |
| Liquid-level electrode lead distance | Up to 200 m for applicable liquid-level configuration |
| دمای محیط | −5°C to +40°C; 24-hour average ≤+35°C |
| Installation altitude | ≤2000 m |
| درجه آلودگی | 3 |
| دسته بندی نصب | دوم |
Configure the motor protector for the motor nameplate current before
commissioning. Frame current, protector adjustment range and motor
operating current are distinct selection values. Motor overload
protection does not replace coordinated short-circuit protection.
Wiring and Dimensions
The supplied sheet shows KCQJ7 and KCQJ7-W circuits with a 380 V main
supply and either 380 V or 220 V control supply. Match the diagram to
the supplied version and control voltage. The enclosure maximum outline
is 118 mm wide × 200 mm high × 127 mm deep.
اطلاعات سفارش
Specify KCQJ7 or KCQJ7-W, motor voltage and power, motor nameplate
current, required current setting range, control supply voltage,
liquid-level control requirements and quantity.