VIOX ELECTRIC
言語

VIOX VOSA2-HK-1500V 1500V DC Compact Semiconductor Protection Fuse

VOSA2-HK-1500V VIOX 1500V DC Compact Semiconductor Protection Fuse: aR class, 200A-500A, 150kA breaking with a ≤15ms time constant, CE marked to IEC 60269-4 and GB/T 13539.4. Size code 2 body for drives, storage and charging.

VIOXシリーズ
VOSA2-HK-1500V
定格電圧
1500VDC
定格電流
200A
標準
GB/T 13539.4 / GB/T13539.4 / IEC 60269-4

概要

VOSA2-HK-1500V VIOX 1500V DC Compact Semiconductor Protection Fuse: aR class, 200A-500A, 150kA breaking with a ≤15ms time constant, CE marked to IEC 60269-4 and GB/T 13539.4. Size code 2 body for drives, storage and charging.

Mid-range DC links rarely get a fuse designed for them alone; most 1500V parts are scaled-down versions of larger frames, and the surplus volume then drives cabinet size. VIOX Electric built the 1500V DC Compact Semiconductor Protection Fuse around 200A to 500A instead, for IGBT modules, thyristors and rectifier diodes in rail traction, renewable power stations, telecom plants, metallurgy lines, charging piles and storage inverters.

特徴

  • Rated voltage 1500VDC and current capacity 200A for ess & semiconductor high-speed fuse applications.
  • High interrupting performance (150kA) with rapid current-limiting fault clearing.
  • Engineered and tested in accordance with GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 standards.
  • Precision-engineered low-power-loss silver-plated contacts and high-temperature ceramic or flame-retardant housing.
  • Direct OEM replacement geometry for standardized industrial, solar PV, ESS, and EV protection panels.

仕様

VOSA2-HK-1500V Technical Specifications

シリアル番号 Rated Current A Pre-arcing I²t A²s Melting I²t A²s Power dissipation W
1 200 10710 44800 90
2 250 18400 96400 98
3 315 35100 190000 110
4 350 46900 253000 119
5 400 78900 382000 127
6 450 96700 550000 135
7 500 105000 596000 144

VOSA2-HK-1500V Ratings & Dimensions Table 2

Rated Current (A) Conventional Time (h) Conventional Current
“gR”
Inf lf
ln≤63 1 1.13ln 1.6ln
63<In≤160 2
160<ln≤400 3
400<ln 4
Note:ln is the rated current of the fuse; lnf is the conventional non-fusing current; if is the conventional fusing current.

Selection & Installation Notes

  • Verify system maximum voltage (1500VDC) and prospective short-circuit fault current before selecting the fuse link or holder rating.
  • Apply ambient-temperature derating when operating inside sealed outdoor combiner boxes or high-density inverter cabinets above 40°C.
  • Always de-energize circuits before replacing cylindrical, blade, or bolted fuse links, and use insulated fuse pullers for NH/NT types.
  • Explore the complete VIOX Fuse & Fuse Holder catalog for matched holders, bases, and disconnectors.

よくあるご質問

What voltage and current ratings does the VIOX VOSA2-HK-1500V 1500V DC Compact Semiconductor Protection Fuse support?

This VIOX VOSA2-HK-1500V series is rated for 1500VDC with a current rating of 200A and 150kA breaking performance. Refer to the technical specification table above for individual part numbers and ampere steps.

Which international standards apply to VIOX VOSA2-HK-1500V 1500V DC Compact Semiconductor Protection Fuse?

The VOSA2-HK-1500V series is designed and verified to GB/T 13539.4 / GB/T13539.4 / IEC 60269-4 requirements for safe overcurrent and short-circuit protection.

Where is the VIOX VOSA2-HK-1500V 1500V DC Compact Semiconductor Protection Fuse typically installed?

It is engineered for ess & semiconductor high-speed fuse circuits, protecting cables, busbars, semiconductors, battery modules, or string feeders against thermal overload and high-energy short-circuit faults.

Can VIOX supply matched fuse holders, bases, or OEM private-label packaging?

Yes. VIOX Electric supplies matched DIN-rail fuse holders, NH/NT fuse bases, disconnectors, and OEM/ODM bulk packaging with technical datasheets upon RFQ.

製品の見積もりが必要ですか?
私たちと一緒に作り上げましょう。.

製品モデル、技術定格、数量、およびOEM要件をお送りください。当社のチームがお客様の用途を確認し、1営業日以内に回答いたします。.

見積依頼