VIOX Eléctrico
Language

RCBO Tipo F VRL22F

The VIOX VRL22F Type F RCBO provides residual-current, overload and short-circuit protection for AC 50/60 Hz circuits supplying inverter-controlled equipment. It detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz. The series offers 2-63 A ratings, 2P and 4P configurations, B/C/D curves, 10-300 mA sensitivities and 6 kA or 10 kA short-circuit ratings.

Corriente Nominal
2-63 A
Corriente Residual
10-300 mA
Configuración de postes
2P, 4P
Clasificación de cortocircuito
6 kA o 10 kA

Visión general

The VIOX VRL22F is a Type F residual current circuit breaker with overcurrent protection for AC 50/60 Hz circuits. It provides residual-current, overload and short-circuit protection while detecting sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz. Its protective functionality is maintained with superimposed smooth DC up to 10 mA, although smooth DC fault currents are not detected. Available 2P and 4P configurations support residential, commercial and light industrial circuits supplying single-phase inverter-controlled equipment.

Características

  • Type F detection for sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz.
  • Voltage-independent electromagnetic operation.
  • Functionality maintained with superimposed smooth DC up to 10 mA.
  • Curvas de disparo por sobrecorriente B, C y D.
  • Corriente de cortocircuito condicional nominal de 6 kA o 10 kA.
  • 3 kA peak withstand current with an 8/20 μs waveform.
  • Indicador mecánico de posición de contactos rojo/verde.
  • Entrada de alimentación superior o inferior e instalación en cualquier posición de montaje.

Modelos

Modelo Polos Corriente nominal máxima Tensión nominal
VRL22F 2P 63 A 230/240 V AC
VRL22-40F 4P 40 A 400/415 V AC
VRL22-63F 4P 63 A 400/415 V AC

Especificaciones

Datos eléctricos

Parámetro Especificación
Corriente Nominal 2, 4, 5, 6, 8, 10, 13, 15, 16, 20, 25, 30, 32, 35, 40, 45, 50, 60, 63 A
Tensión nominal 2P: 230/240 V AC; 4P: 400/415 V AC
Frecuencia nominal 50/60 Hz
Rango de tensión del circuito de prueba 2P: 184-264 V AC; 4P: 184-440 V AC
Tensión nominal de aislamiento 500 V
Tensión nominal soportada al impulso 4 kV, 1.2/50 μs
Modo de funcionamiento Voltage-independent

Datos de protección

Parámetro Especificación
Residual-Current Type Tipo F
Sensibilidad de Corriente Residual Sinusoidal AC and pulsating DC residual currents; mixed-frequency residual currents up to 1 kHz
Superimposed Smooth DC Functionality maintained up to 10 mA; smooth DC fault currents are not detected
Corriente residual de funcionamiento nominal 10 mA for 2P up to 32 A only; 30, 100, 300 mA
Overcurrent Tripping Curves B: 3-5 In; C: 5-10 In; D: 10-20 In
Corriente condicional de cortocircuito nominal 6,000 A or 10,000 A; energy-limiting class 3 for B and C curves
Capacidad nominal de cierre y corte 3,000 A
Corriente de cresta soportada 3 kA, 8/20 μs

Datos de instalación y ambientales

Parámetro Especificación
Grado de protección IP20
Tipo de terminal Montaje abierto / bornes de elevación
Capacidad de la terminal 1-25 mm²
Par de apriete del borne 2-2.5 N·m
Grosor de la barra colectora 0.8-2 mm
Aislamiento eléctrico Distancia de contacto > 4 mm
Temperatura de funcionamiento -25 °C a +55 °C
Temperatura de almacenamiento y transporte -40 °C a +70 °C
Posición de montaje Cualquier posición
Entrada de alimentación Arriba o abajo

Datos mecánicos

Parámetro Especificación
Resistencia eléctrica ≥ 5.000 ciclos de operación
Resistencia mecánica ≥ 5.000 ciclos de operación
Contact-Position Indicator Indicador mecánico rojo/verde

Normas

Parámetro Especificación
Design Standards IEC/EN 62423; IEC/EN 61009-1; OVE E 8601
Resistance to Climatic Conditions IEC/EN 61009

Guía de selección

Elemento de código Significado Valores disponibles
V Identificación de empresa VIOX V
RL Familia de productos RCBO RL
22 Serie de diseño 22
F Tipo de corriente residual F
Curva Curva de disparo por sobreintensidad B, C o D
Actual Corriente nominal 2-63 A
Sensibilidad Corriente residual de funcionamiento nominal 10, 30, 100 o 300 mA
Polos Número de polos 2P o 4P
Ejemplo de configuración de catálogo: V-RL-22-F-C-32A-30mA-2P

Aplicación

Select Type F where the circuit supplies compatible single-phase inverter-controlled equipment and requires mixed-frequency residual-current detection up to 1 kHz.

Corriente Nominal

Select from the listed 2-63 A ratings, observing the 40 A limit of the VRL22-40F model.

Sensibilidad residual

Select 10, 30, 100 or 300 mA. The 10 mA option is limited to 2P models rated up to 32 A.

Polos y tensión

Seleccione 2P para circuitos de 230/240 V AC o 4P para circuitos de 400/415 V AC.

Curvas de viaje

Corriente de prueba Tiempo especificado Resultado Curva
1,13 En t ≥ 1 h Sin disparo B, C
1.45 In t < 1 h Tropezar B, C
2,55 pulgadas 1 s < t < 60 s Tropezar B, C
3 In t ≥ 0.1 s Sin disparo B
5 In t < 0.1 s Tropezar B
5 In t ≥ 0.1 s Sin disparo C
10 In t < 0.1 s Tropezar C
El catálogo indica la disponibilidad de la curva D, pero solo proporciona criterios detallados de prueba instantánea para las curvas B y C.

Dimensiones

VRL22F Type F RCBO dimensional drawing
VRL22F Type F RCBO dimensional drawing.

Aplicaciones

  • Lavadoras y lavavajillas.
  • Bombas de calor y aires acondicionados.
  • Lighting-control equipment and power tools.
  • Other compatible single-phase inverter-controlled loads.

Instalación

  • Utilice bornes de montaje abierto o de elevación con conductores de 1 mm² a 25 mm².
  • Tighten terminals to the specified torque of 2-2.5 N·m.
  • Utilice barras colectoras con un espesor de 0.8-2 mm cuando sea aplicable.
  • Power may enter from the top or bottom, and the device may be installed in any mounting position.
  • Haga coincidir la configuración 2P o 4P con la tensión del circuito especificada.

PREGUNTAS FRECUENTES

What residual currents can the VRL22F detect?
It detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz.
Does the VRL22F detect smooth DC fault current?
No. Its protective functionality is maintained with superimposed smooth DC up to 10 mA, but smooth DC fault currents themselves are not detected.
¿Qué corrientes nominales y configuraciones de polos están disponibles?
The series covers 2-63 A and is available in 2P and 4P configurations, subject to the limits of each model.
Which tripping curves are available?
B, C and D overcurrent tripping curves are listed.
What short-circuit ratings are available?
The rated conditional short-circuit current is 6,000 A or 10,000 A.

¿Necesita una cotización de producto?
Construyámoslo juntos.

Envíenos el modelo del producto, las especificaciones técnicas, la cantidad y los requisitos de OEM. Nuestro equipo revisará su solicitud y responderá en el plazo de un día hábil.

Solicitar presupuesto