The VIOX VRL22F Type F RCBO provides residual-current, overload and short-circuit protection for AC 50/60 Hz circuits supplying inverter-controlled equipment. It detects sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz. The series offers 2-63 A ratings, 2P and 4P configurations, B/C/D curves, 10-300 mA sensitivities and 6 kA or 10 kA short-circuit ratings.
The VIOX VRL22F is a Type F residual current circuit breaker with overcurrent protection for AC 50/60 Hz circuits. It provides residual-current, overload and short-circuit protection while detecting sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz. Its protective functionality is maintained with superimposed smooth DC up to 10 mA, although smooth DC fault currents are not detected. Available 2P and 4P configurations support residential, commercial and light industrial circuits supplying single-phase inverter-controlled equipment.
Jellemzők
Type F detection for sinusoidal AC, pulsating DC and mixed-frequency residual currents up to 1 kHz.
Voltage-independent electromagnetic operation.
Functionality maintained with superimposed smooth DC up to 10 mA.
B, C és D túláram-kioldási jelleggörbék.
6 kA vagy 10 kA névleges feltételes rövidzárlati áram.
3 kA peak withstand current with an 8/20 μs waveform.
Mechanikus piros/zöld érintkezőállás-jelző.
Felső vagy alsó betáplálás és beépítés bármilyen szerelési helyzetben.
Select Type F where the circuit supplies compatible single-phase inverter-controlled equipment and requires mixed-frequency residual-current detection up to 1 kHz.
Névleges áram
Select from the listed 2-63 A ratings, observing the 40 A limit of the VRL22-40F model.
Maradékáram-érzékenység
Select 10, 30, 100 or 300 mA. The 10 mA option is limited to 2P models rated up to 32 A.
Pólusok és feszültség
Válasszon 2P-t 230/240 V AC, vagy 4P-t 400/415 V AC áramkörökhöz.
Utazási görbék
Tesztáram
Meghatározott idő
Eredmény
Karakterisztika
1.13 In
t ≥ 1 h
Nem kioldó
B, C
1.45 In
t < 1 h
Tripping
B, C
2.55 In
1 s < t < 60 s
Tripping
B, C
3 In
t ≥ 0.1 s
Nem kioldó
B
5 In
t < 0.1 s
Tripping
B
5 In
t ≥ 0.1 s
Nem kioldó
C
10 In
t < 0.1 s
Tripping
C
A katalógus felsorolja a D-karakterisztika elérhetőségét, de részletes pillanatnyi kioldási vizsgálati kritériumokat csak a B és C karakterisztikákhoz biztosít.
Méretek
VRL22F Type F RCBO dimensional drawing.
Alkalmazások
Mosógépek és mosogatógépek.
Hőszivattyúk és légkondicionálók.
Lighting-control equipment and power tools.
Other compatible single-phase inverter-controlled loads.
Telepítés
Használjon nyitott vagy emelőkapcsokat 1 mm² és 25 mm² közötti vezetékekhez.
Tighten terminals to the specified torque of 2-2.5 N·m.
Adott esetben használjon 0,8-2 mm vastagságú gyűjtősíneket.
Power may enter from the top or bottom, and the device may be installed in any mounting position.
Igazítsa a 2P vagy 4P konfigurációt a megadott áramköri feszültséghez.
Küldje el nekünk a termékmodelljét, a műszaki jellemzőket, a mennyiséget és az OEM-követelményeket. Csapatunk áttekinti az alkalmazást, és egy munkanapon belül válaszol.