VIOX ELECTRIC
ພາສາ

VIOX KCQ7 ເຄື່ອງເລີ່ມຕົ້ນມໍເຕີແບບແມ່ເຫຼັກໄຟຟ້າ

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

ພາບລວມ

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

ຄຸນສົມບັດ

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    ປະຈຸບັນ.
  • Detachable cover for component inspection and maintenance.

ຂໍ້ມູນຈໍາເພາະ

ຕົວແບບ Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 A 5.5 kW 11 kW 15 kW
KCQ7-32 32 A 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 A 11 kW 18.5 kW 18.5 kW
KCQ7-50 50 A 15 kW 22 kW 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 kW 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
ພາລາມິເຕີ ຂໍ້ມູນຈໍາເພາະ
ຄໍາຮ້ອງສະຫມັກ Direct starting of three-phase squirrel-cage induction motors
ປະເພດການນໍາໃຊ້ AC-3
ຄວາມຖີ່ຂອງການສະໜອງໄຟ 50 Hz ຫຼື 60 Hz
ແຮງດັນໄຟຟ້າໃນການເຮັດວຽກທີ່ກຳນົດ (Rated operating voltage) Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
ມາດຕະຖານອ້າງອີງ IEC/EN 60947-4-1; GB/T 14048.4
ອຸນຫະພູມສະພາບແວດລ້ອມປົກກະຕິ −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

ການຄັດເລືອກ

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

ຂະໜາດ

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

ຂໍ້ມູນການສັ່ງຊື້

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

ຕ້ອງການໃບສະເໜີລາຄາສິນຄ້າບໍ?
ມາສ້າງສັນໄປພ້ອມກັນ.

ສົ່ງຮຸ່ນສິນຄ້າ, ຄ່າທາງເຕັກນິກ, ຈຳນວນ ແລະ ຄວາມຕ້ອງການ OEM ໃຫ້ພວກເຮົາ. ທີມງານຂອງພວກເຮົາຈະກວດສອບການນຳໃຊ້ຂອງທ່ານ ແລະ ຕອບກັບພາຍໃນໜຶ່ງມື້ເຮັດວຽກ.

ຂໍໃບສະເໜີລາຄາ