VIOX ELECTRIC
Dil

VIOX KCQ7 Elektromanyetik Motor Starter

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

Genel Bakış

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

Özellikler

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    akım.
  • Detachable cover for component inspection and maintenance.

Teknik Özellikler

Model Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 A 5.5 kW 11 kW 15 kW
KCQ7-32 32 A 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 A 11 kW 18.5 kW 18.5 kW
KCQ7-50 50 A 15 kW 22 kW 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 kW 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
Parametre Şartname
Uygulama Direct starting of three-phase squirrel-cage induction motors
Kullanım kategorisi AC-3
Besleme frekansı 50 Hz veya 60 Hz
Anma çalışma gerilimi Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
Referans alınan standartlar IEC/EN 60947-4-1; GB/T 14048.4
Normal ortam sıcaklığı −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

Seçim

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

Boyut

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

Sipariş Bilgileri

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

Ürün Teklifi mi İstiyorsunuz?
Birlikte İnşa Edelim.

Bize ürün modelini, teknik değerleri, miktarı ve OEM gereksinimlerini gönderin. Ekibimiz başvurunuzu inceleyecek ve bir iş günü içinde yanıt verecektir.

Teklif İsteyin