VIOX ELECTRIC
Ngôn ngữ

Bộ khởi động động cơ điện từ VIOX KCQ7

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

Tổng quan

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

Đặc trưng

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    dòng điện.
  • Detachable cover for component inspection and maintenance.

Thông số kỹ thuật

Người mẫu Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 A 5.5 kW 11 kW 15 kW
KCQ7-32 32 A 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 A 11 kW 18.5 kW 18.5 kW
KCQ7-50 50 A 15 kW 22 kW 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 kW 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
Tham số Đặc điểm kỹ thuật
Ứng dụng Direct starting of three-phase squirrel-cage induction motors
Thể loại sử dụng AC-3
Tần số nguồn 50 Hz hoặc 60 Hz
Điện áp vận hành định mức Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
Các tiêu chuẩn tham chiếu IEC/EN 60947-4-1; GB/T 14048.4
Nhiệt độ môi trường bình thường −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

Lựa chọn

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

Kích thước

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

Thông tin đặt hàng

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

Cần báo giá sản phẩm?
Hãy cùng chúng tôi thực hiện dự án này.

Gửi cho chúng tôi mã sản phẩm, các định mức kỹ thuật, số lượng và yêu cầu OEM. Đội ngũ của chúng tôi sẽ xem xét ứng dụng của bạn và phản hồi trong vòng một ngày làm việc.

Yêu cầu báo giá