VIOX ELECTRIC
زبان

استارتر موتور الکترومغناطیسی VIOX KCQ7

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

نمای کلی

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

ویژگی‌ها

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    جریان را.
  • Detachable cover for component inspection and maintenance.

مشخصات فنی

مدل Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 آمپر 5.5 kW 11 کیلووات 15 kW
KCQ7-32 32 آمپر 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 آمپر 11 کیلووات 18.5 kW 18.5 kW
KCQ7-50 50 آمپر 15 kW 22 کیلووات 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 کیلووات 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
پارامتر مشخصات
کاربرد Direct starting of three-phase squirrel-cage induction motors
دسته بندی استفاده ای‌سی-۳
فرکانس تغذیه 50 هرتز یا 60 هرتز
ولتاژ کاری نامی Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
استانداردهای مرجع IEC/EN 60947-4-1; GB/T 14048.4
دمای محیطی عادی −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

انتخاب

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

ابعاد

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

اطلاعات سفارش

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

نیاز به استعلام قیمت محصول دارید؟
بیایید با هم بسازیم.

مدل محصول، مشخصات فنی، تعداد و الزامات OEM خود را برای ما ارسال کنید. تیم ما درخواست شما را بررسی کرده و ظرف یک روز کاری پاسخ خواهد داد.

درخواست قیمت