Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

Обзор

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

Характеристики

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    током.
  • Detachable cover for component inspection and maintenance.

Технические характеристики

Модель Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 A 5.5 kW 11 кВт 15 kW
KCQ7-32 32 A 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 A 11 кВт 18.5 kW 18.5 kW
KCQ7-50 50 А 15 kW 22 кВт 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 кВт 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
Параметр Спецификация
Приложение Direct starting of three-phase squirrel-cage induction motors
Категория использования АС-3
Частота питающей сети 50 Гц или 60 Гц
Номинальное рабочее напряжение Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
Стандарты, на которые есть ссылки IEC/EN 60947-4-1; GB/T 14048.4
Нормальная температура окружающей среды −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

Выбор

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

Размер

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

Информация для заказа

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

Нужен расчет стоимости продукции?
Давайте создавать вместе.

Отправьте нам модель изделия, технические характеристики, количество и требования OEM. Наша команда рассмотрит вашу заявку и ответит в течение одного рабочего дня.

Запрос Цитировать