VIOX ELECTRIC
ភាសា

ឧបករណ៍ចាប់ផ្តើមម៉ូទ័រអេឡិចត្រូម៉ាញ៉េទិច VIOX KCQ7

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

ទិដ្ឋភាពទូទៅ

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

លក្ខណៈពិសេស

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    ចរន្ត។.
  • Detachable cover for component inspection and maintenance.

លក្ខណៈបច្ចេកទេស

គំរូ Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 18 A 4 kW 7.5 kW 10 kW
KCQ7-25 25 A 5.5 kW 11 kW 15 kW
KCQ7-32 32 A 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 A 11 kW 18.5 kW 18.5 kW
KCQ7-50 50 A 15 kW 22 kW 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 kW 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
ប៉ារ៉ាម៉ែត្រ ការបញ្ជាក់
កម្មវិធី Direct starting of three-phase squirrel-cage induction motors
ប្រភេទនៃការប្រើប្រាស់ -ក្រុម ៣
ប្រេកង់ផ្គត់ផ្គង់ 50 Hz ឬ 60 Hz
តង់ស្យុងប្រតិបត្តិការដែលបានកំណត់ (Rated operating voltage) Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
បទដ្ឋានដែលបានយោង IEC/EN 60947-4-1; GB/T 14048.4
សីតុណ្ហភាពព័ទ្ធជុំវិញធម្មតា −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

ការជ្រើសរើស

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

វិមាត្រ

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

ព័ត៌មានបញ្ជាទិញ

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.

ត្រូវការសម្រង់តម្លៃផលិតផលមែនទេ?
តោះសហការកសាងវាជាមួយគ្នា។.

សូមផ្ញើមូដែលផលិតផល ការវាយតម្លៃបច្ចេកទេស បរិមាណ និងតម្រូវការ OEM មកកាន់យើង។ ក្រុមការងាររបស់យើងនឹងពិនិត្យមើលកម្មវិធីរបស់អ្នក ហើយឆ្លើយតបក្នុងរយៈពេលមួយថ្ងៃធ្វើការ។.

ស្នើសុំសម្រង់