بادئ محرك مغناطيسي VIOX KCQ7

Enclosed electromagnetic starters for direct starting of three-phase
motors.

  • 9–93 A AC-3 frame range
  • Contactor, thermal overload relay and start/stop buttons
  • AC coil options: 36, 110, 220 or 380 V
  • Model-specific enclosure protection and dimensions

نظرة عامة

VIOX KCQ7 electromagnetic motor starters combine an AC contactor,
thermal overload relay and start/stop push buttons in an enclosure. They
are designed for direct starting and stopping of three-phase
squirrel-cage induction motors, with AC-3 frame currents from 9 to 93 A
and rated operating voltages up to 660 V.

الميزات

  • Enclosed contactor and thermal overload relay assembly.
  • Green start and red stop push buttons.
  • CJX2-D or CJX2s contactor options with matching overload
    relays.
  • Adjustable overload protection selected to suit the motor
    بالتيار.
  • Detachable cover for component inspection and maintenance.

المواصفات الفنية

الطراز Frame current AC-3 motor power at 220 V At 380 V At 660 V
KCQ7-09 9 A 2.2 kW 4 kW 5.5 kW
KCQ7-12 12 A 3 kW 5.5 kW 7.5 kW
KCQ7-18 21.6 أمبير 4 kW 7.5 kW 10 kW
KCQ7-25 25 أمبير 5.5 kW 11 كيلوواط 15 kW
KCQ7-32 32 أمبير 7.5 kW 15 kW 18.5 kW
KCQ7-40 40 أمبير 11 كيلوواط 18.5 kW 18.5 kW
KCQ7-50 50 أمبير 15 kW 22 كيلوواط 37 kW
KCQ7-65 65 A 18.5 kW 30 kW 37 kW
KCQ7-80 80 A 22 كيلوواط 37 kW 45 kW
KCQ7-93 93 A 25 kW 45 kW 45 kW
المعلمة المواصفات
التطبيق Direct starting of three-phase squirrel-cage induction motors
فئة الاستخدام AC-3
تردد التغذية 50 هرتز أو 60 هرتز
جهد التشغيل المقنن Up to 660 V
AC coil voltage options 36 V, 110 V, 220 V, 380 V
Coil pull-in range 85%–110% Us
Coil release range 20%–75% Us
Enclosure protection, KCQ7-09–32 IP55
Enclosure protection, KCQ7-40–93 IP20, per detailed enclosure specification
المعايير المشار إليها IEC/EN 60947-4-1; GB/T 14048.4
درجة الحرارة المحيطة العادية −5°C to +40°C; 24-hour average ≤+35°C
Normal installation altitude ≤2000 m

الاختيار

Select the frame by motor voltage and AC-3 duty, then select an
overload-relay setting range that includes the motor nameplate current.
Frame current is not the relay adjustment setting. The overload relay
does not replace coordinated short-circuit protection.

The larger KCQ7-40–93 enclosures must not be treated as IP55. Choose
the enclosure protection appropriate to the installation environment and
specify it in the quotation request.

البعد

The catalogue provides separate enclosure drawings for KCQ7-09–18,
KCQ7-25–32 and KCQ7-40–93. The reference sheet below includes dimensions
and the model/relay selection table.

KCQ7 motor starter specifications and installation dimensions

معلومات الطلب

Provide the starter model, motor voltage, power and full-load
current, coil voltage and frequency, overload-relay setting range,
enclosure requirements and quantity.