HRC Industrial Fuse Manufacturer (NH000–NH3 · NT00–NT4 · BS88 · Africa J-Type · 12–40.5 kV MV)
High Rupturing Capacity (HRC) ceramic fuses engineered to clear up to 120 kA prospective short-circuit faults safely across industrial switchgear, motor feeders, utility feeder pillars, and medium-voltage transformers.
Explore All VIOX HRC Industrial Fuses Series
Click any ampere or voltage rating pill below to open its full IEC technical specification table and dimensional datasheet.
NH000 – NH3 Blade HRC Fuses
Full 5-frame low-voltage feeder HRC protection (100A–630A)
- Voltage
- 690 V AC
- Current
- 4–630 A
- Standard
- IEC 60269-2 · gG/aM
NT00 – NT4 High-Current HRC
5-frame industrial distribution blade fuses up to 1250A
- Voltage
- 690 V AC
- Current
- 16–1250 A
- Standard
- IEC 60269-2 · gG
VIOX NT / NH Fuse Extractor
Insulated heavy-duty puller handle for safe NH/NT link swaps
- Voltage
- Up to 690 V AC
- Current
- NH000–NT4
- Standard
- IEC 60269 Accessory
VOG00 / VOG0K / VOG10C BS88
Offset-bladed, offset-slotted & center-bolted BS88 HRC links
- Voltage
- 240–550 V AC
- Current
- 2–400 A
- Standard
- BS 88 / IEC 60269
JPU / JSU / VOJPU31 Outdoor HRC
82 mm & 92 mm wedge-type links + 630A pole-mounted carrier
- Voltage
- 415 V AC
- Current
- 20–630 A
- Standard
- BS 88 Part 5 · J-Type
VO-AUS-100B / 100C Service Cutout
Black service & clear cutout 100A Australian HRC fuses
- Voltage
- 690 V AC
- Current
- 10–100 A
- Standard
- AS / IEC 60269
HR17 Horizontal 3P Disconnector
4-frame AC-22B/23B load-break NH fuse switch (160A–630A)
XRNP / XRNT / XRNC MV Fuses
Current-limiting HRC fuses for PT/VT, transformers & capacitors
- Voltage
- 12–40.5 kV AC
- Current
- 15–240 A
- Standard
- IEC 60282-1 · MV HRC
Match the Right NH, NT, BS88, J-Type or MV HRC Fuse to Your Feeder
Select your application tier and current range to match the exact VIOX series, mounting base, and safety verification rule.
Protection Physics & 4 Field Failure Modes in HRC Industrial Fuses
Technical architecture and field-proven failure prevention engineered directly into VIOX production.
Failure Mode 01 · Low-Density Sand Causing HRC Rupture
Under-filled ceramic tubes fail to absorb 100 kA+ arc energy and shatter inside switchboards. VIOX Fix: 99%+ compacted high-purity quartz sand & steatite ceramic bodies.
Failure Mode 02 · Nuisance Blowing on Motor Startups
Using gG links instead of aM on DOL motors causes repeated tripping during 6–8× startup inrush. VIOX Fix: Specify VIOX NH/NT aM partial-range motor backup links.
Low-Density Sand Causing HRC Rupture
Under-filled ceramic tubes fail to absorb 100 kA+ arc energy and shatter inside switchboards.
Nuisance Blowing on Motor Startups
Using gG links instead of aM on DOL motors causes repeated tripping during 6–8× startup inrush.
Live Arc Flash When Pulling Open NH Blades
Pulling NH00–NH3 links with pliers under load triggers severe phase-to-phase arc flash.
Wrong Fixing Center on Utility J-Type Pillars
Ordering 82 mm JPU links for 92 mm JSU feeder pillars halts field commissioning.
HRC Fuse Cross-Reference: VIOX vs. Siemens 3NA3, Bussmann & Mersen
Direct mechanical and IEC standard cross-reference for panel builders, EPCs, and distributors converting Tier-1 BOMs.
| Footprint / Rating Tier | Eaton Bussmann | Mersen / Ferraz | Siemens / Littelfuse | VIOX Direct Equivalent |
|---|---|---|---|---|
| DIN 43620 NH000–NH3 (100–630A) | Bussmann NH000–NH3 gG/aM |
Mersen NH000–NH3 |
Siemens 3NA3 / 3ND |
VIOX NH000 / NH00 / NH1 / NH2 / NH3 |
| High-Current NT00–NT4 (160–1250A) | Bussmann NH4 / NT |
Mersen NH00–NH4 |
Siemens 3NA3 1250A |
VIOX NT00 / NT1 / NT2 / NT3 / NT4 |
| British BS88 Bolted Tags | Bussmann NITD / ESD / CD |
Mersen BS88 gG |
Lawson / GEC BS88 |
VIOX VOG00 / VOG0K / VOG10C |
| Africa J-Type Outdoor (82 / 92mm) | Bussmann J-Type Wedge |
Mersen J-Type 415V |
Utility 82mm / 92mm |
VIOX JPU (82mm) / JSU (92mm) / VOJPU31 |
| MV Transformer / PT / Capacitor | Bussmann 12kV–36kV DIN |
Mersen Limitor® MV |
Siemens 3GD MV HRC |
VIOX XRNP / XRNT (12kV) / XRNC (40.5kV) |
I²t, breaking capacity, and project UL/IEC certification before substitution. Send your Tier-1 BOM via the RFQ builder below for rapid VIOX engineering verification.
Configure Your HRC Industrial Fuses Specification in 20 Seconds
Select your technical options below and prefill the VIOX engineering quote form with one click.
HRC Industrial Fuses Technical FAQ
Direct answers on standards, sizing, Tier-1 interchangeability, and factory OEM kitting.
gG vs aM What is the difference between NH/NT gG and aM HRC fuses?
gG HRC fuses provide full-range overload and short-circuit protection for general feeders and cables. aM HRC fuses are partial-range motor-circuit backup fuses designed to withstand high motor startup currents while clearing short circuits.
Breaking What breaking capacity do VIOX NH000–NH3 and NT00–NT4 HRC fuses achieve?
VIOX low-voltage NH and NT ceramic HRC fuses are rated up to 690 V AC with high rupturing capacity up to 120 kA per IEC 60269-2 and DIN 43620.
Cross-Ref Are VIOX NH fuses dimensionally interchangeable with Siemens 3NA3 and Bussmann NH?
Yes. All VIOX NH000, NH00, NH1, NH2, and NH3 blade dimensions and knife-contact spacing conform to DIN 43620 / IEC 60269-2 for drop-in replacement in standard NH bases and HR17 disconnectors.
MV HRC How do XRNP, XRNT, and XRNC medium-voltage fuses differ?
XRNP (12 kV, up to 15 A) protects voltage/potential transformers (PT/VT); XRNT (12 kV, up to 200 A) protects distribution power transformers; XRNC (40.5 kV, up to 240 A) is engineered for high-voltage capacitor bank protection.
Need HRC Industrial Fuses Datasheets or BOM Cross-Ref?
Talk Directly with VIOX Engineers.
Send your rated voltage, ampere steps, breaking capacity, or Tier-1 part numbers for rapid factory pricing and evaluation samples.
Request HRC Industrial Fuses Quote