VIOX VMM3-250 3P 250A AC400V/690V MCCB

VIOX VMM3-250 MCCB delivers robust protection for power distribution networks up to 250A. This IEC60947-2 compliant device features a 35kA breaking capacity at 400V AC and supports current ratings from 100A to 250A. Available in 2P, 3P, and 4P configurations, it operates at 400V/690V AC with 800V insulation voltage. Key advantages include compact size, high breaking capacity, and excellent anti-vibration properties. Suitable for various applications, it offers overload and short-circuit protection with inverse time and instantaneous tripping characteristics. Operating effectively from -5°C to +40°C and up to 2000m altitude, this MCCB ensures reliable performance in demanding electrical environments. Its versatile design, including multiple N-pole options and release configurations, makes it ideal for power distribution protection needs, offering superior safety features and compliance with international standards.

Send your requirements, we will quote for you within 12 hours​

VIOX VMM3-250 3P 250A AC400V/690V Moulded Case Circuit Breaker (MCCB)

Product Overview

The VIOX VMM3-250 Moulded Case Circuit Breaker (MCCB) is a high-performance device designed for power distribution networks with AC 50Hz, rated operating voltage up to 690V, and rated operating current up to 250A. It offers superior protection against overload, short circuit, and other faults while featuring compact size, high breaking capacity, short arcing time, and excellent anti-vibration properties.

Key Features

  • Rated Current: Up to 400A
  • Poles: Available in 2P, 3P, 4P configurations
  • Rated Working Voltage: 400V/690V AC
  • Rated Insulation Voltage: 800V
  • Breaking Capacity: Standard (S) and Higher (H) types available
  • Compliance: IEC60947-2 and GB/T14048.2 standards

Product Category

  • According to the breaking capacity of the circuit breaker, it is divided into: a standard type (S type); b higher type (H type);
  • According to the wiring method of the circuit breaker: a. Wiring in front of the board; b. Wiring behind the board; c. Plug-in type; d. Pull-out type;
  • According to the operation mode: a. Direct operation by handle; b. Operation by turning handle; c. Electric operation;
  • According to the number of poles: two poles; three poles; four poles;
  • According to accessories: alarm contacts, auxiliary contacts, shunt release, undervoltage release;

Technical Specifications

Circuit breaker rating

ModelFrame rating
rated current
In(mA)
Rated
current
In(A)
Rated
working
voltage (V)
Rated
Insulation
voltage (V)
Rated ultimate
short circuit
breaking
capacity Icu(kA)
Rated operating
short-circuit
breaking
capacity Ics(kA)
Number
of
poles
Flashover
distance
(mm)
VMM3-125S12516,20,25,32,
40,50,60,80,
100,125
400/415100025183P≤50
VMM3-125H12535253P
VMM3-250S250100,125,160,
180,200,225,
250
400/69080035/1025/52P,3P,4P≤50
VMM3-250S2506005035

 

Inverse time breaking action characteristics of overcurrent release of distribution circuit breaker when all poles are energized at the same time

Test current nameI/InAppointed timeStarting state
Agreed no tripping current1.052h(In>63A),1h(In≤63A)Cold state
Agreed tripping current1.32h(In>63A),1h(In≤63A)Immediately after the sequence 1 test, start

 

Inverse time breaking action characteristics of overcurrent release of circuit breaker for motor protection when all poles are energized at the same time

Setting currentAppointed timeStarting stateRemark
1.0In>2hCold state
1.2In≤2hImmediately after the sequence 1 test, start
1.5In≤4mincold state10 ≤ In ≤ 250
≤8mincold state250 ≤ In ≤ 630
7.2In4s≤T≤10scold state10 ≤ In ≤ 250
6s≤T≤20scold state250 ≤ In ≤ 800

The instantaneous operating characteristics of the circuit breaker for distribution are set to 10In±20%, and the instantaneous operating characteristics of the circuit breaker for motor protection are set to 12In±20%.

Operating Conditions

  • Altitude: Not exceeding 2000m
  • Ambient Temperature: -5°C to +40°C (24-hour average not exceeding +35°C)
  • Relative Humidity: Not exceeding 50% at +40°C, higher humidity allowed at lower temperatures
  • Pollution Level: 3

Product Model Coding System

The VMM3 series uses a comprehensive coding system to specify exact configurations:

  • V: Company code (Viox)
  • M: Moulded case circuit breaker
  • M3: Design code
  • -: Separator
  • □: Breaking capacity characteristic code (S for standard type, H for higher type)
  • □: Frame rating/rated current
  • /: Separator
  • □: Number of poles (2P, 3P, 4P)
  • □: Trip mode (2 for single magnetic, 3 for thermal magnetic)
  • □: Release code (see Table 1 for details)
  • □: Purpose code (2 for protecting power distribution)
  • □: N-pole type (see note for details)

N-pole Types

Four types of neutral pole (N pole) configurations are available for four-pole products:

  • A-type N pole: Not equipped with overcurrent tripping components, always connected
  • B-type N pole: Equipped with overcurrent tripping component, N pole is closed first and opened together with other poles
  • C-type N pole: Equipped with an overcurrent tripping component, N pole is closed and opened together with other poles
  • D-type N pole: Equipped with an overcurrent tripping component, always connected

Release Options (Table 1)

Attachment codeElectromagnetic releaseDuplex release
No accessories200300
Alarm contact208308
Shunt tripper210310
Auxiliary contacts220320

Shape Size and Installation Dimensions

CJMM3-125, 250 appearance and installation dimensions (Front panel wiring)
ModelDimensionsInstallation dimensions
LWHL1L2W1W2W3H1H2H3H4CEFGG1ABΦd
VMM3-125S15092762511323095.52618395492817.58301294
VMM3-125H15092762511323095.52618395492817.58301294
VMM3-250S165106873001443575110242031025724.523.511.5351265.5
VMM3-250H1651061053001443514275127242031025724.523.511.5351265.5

The Viox VMM3-400 3P 400A MCCB offers reliable circuit protection with its robust design and advanced features. It’s an excellent choice for demanding electrical environments where performance and safety are paramount.

Related Products