Vue d'ensemble
Modern utility-scale solar string inverters (800 V AC output), wind power converters, and mining/metallurgy power networks require molded case circuit breakers rated well above standard 400 V/690 V switchgear. The VIOX VM7 Series (VM7-320 and VM7-630, 3P, 16 A–630 A) is engineered specifically for AC 800 V, AC 1000 V, and AC 1140 V service with Ui = 1200 V, Uimp = 12 kV, 3500 V dielectric withstand, 100% Ics = Icu breaking performance, and modular snap-in internal accessories for rapid field replacement.
Caractéristiques
- Wide high-voltage AC ratings: 380/415 V, 690 V, 800 V, 1000 V, and 1140 V AC (50/60 Hz).
- 100% service breaking capacity (Ics = Icu): 100 kA @400V, 65 kA @690V, 50 kA @800V, 30 kA @1000V, and 20 kA @1140V (H tier).
- Reinforced insulation: Ui = 1200 V, Uimp = 12 kV, 1-minute power-frequency withstand = 3500 V.
- Two compact 3P frames: VM7-320 (16–320 A, 120×200×103 mm) and VM7-630 (225–630 A, 158×325×177 mm).
- High endurance: 15,000 mechanical operations, 50 mm arc distance, instantaneous release 10×In or 15×In.
- Modular internal accessories (codes 00–78) for fast, tool-light field replacement.
Modèles
| Modèle | Rated Current In (A) | Pôles | Rated Voltage Ue (AC) | Dimensions W×L×H (mm) |
|---|---|---|---|---|
| VM7-320 | 16, 20, 25, 32, 40, 50, 63, 75, 80, 100, 125, 140, 160, 180, 200, 225, 250, 320 A | 3P | 380/415 · 690 · 800 · 1000 · 1140 V | 120 × 200 × 103 |
| VM7-630 | 225, 250, 320, 350, 400, 500, 630 A | 3P | 380/415 · 690 · 800 · 1000 · 1140 V | 158 × 325 × 177 |
Spécifications
High-Voltage Breaking Capacity (Icu = Ics)
| Breaking Tier | AC 380/415 V | AC 690 V | AC 800 V | AC 1000 V | AC 1140 V |
|---|---|---|---|---|---|
| H Tier (Icu = Ics) | 100 kA | 65 kA | 50 kA | 30 kA | 20 kA |
| M Tier (Icu = Ics) | — | 60 kA | 50 kA | 20 kA | 12 kA |
| Electrical Life (Cycles) | 15,000 | 3,000 | 1,000 | 1,000 | 1,000 |
Insulation & Mechanical Specifications
| Paramètre | Spécification |
|---|---|
| Tension nominale d'isolation (Ui) | 1200 V |
| Tension nominale de tenue aux chocs (Uimp) | 12 kV |
| Power-frequency withstand voltage (1 min) | 3500 V |
| Durée de vie mécanique | 15,000 cycles |
| Arcing distance | 50 mm |
| Instantaneous release | 10×In or 15×In |
| Reference ambient temperature | 40 °C |
Guide de sélection
| Position du code | Signification | Catalog Value or Options |
|---|---|---|
| VM7 | Série | New energy high-voltage AC MCCB (up to AC 1140 V) |
| 320 / 630 | Courant de châssis | VM7-320 (16–320 A) or VM7-630 (225–630 A) |
| M / H | Breaking tier | M (up to 50 kA @800V) or H (50 kA @800V / 30 kA @1000V / 20 kA @1140V) |
| 3P | Pôles | 3-Pole high-voltage AC configuration |
| 00–78 | Internal accessory code | 00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux · 50 Shunt+UVT · 60–69 Multi-Aux · 70–78 UVT+Aux (DC 24/110/220 V, AC 230/400 V) |
1. Match Inverter AC Bus
Use VM7 on 800 V AC utility solar inverter AC combiner boxes where 690 V MCCBs are under-rated.
2. Verify 100% Ics = Icu
Both M and H tiers deliver Ics = 100% Icu across 690–1140 V AC for reliable post-fault re-energization.
3. Check Arc Clearance
Maintain the specified 50 mm arc distance above the breaker inside compact outdoor skid enclosures.
4. Pair with DC Protection
Combine VM7 on the AC side with VM7DC 1500 V DC on the PV array side.
Installation
- Verify 50 mm arc-zone clearance and phase barriers when installing in 800–1140 V AC cabinets.
- Confirm ambient derating if outdoor solar combiner cabinets exceed the 40 °C reference temperature.
- Modular internal accessories (shunt, UVT, aux, alarm) snap into dedicated left/right pockets.
- Explorez VIOX Solaire et stockage d'énergie et Boîte de raccordement solutions.
FAQ
Why do 1500 V DC solar plants need an 800 V AC MCCB like VM7?
Utility-scale 1500 V DC string inverters output 800 V AC to step-up transformers. Standard 400 V/690 V MCCBs lack the insulation (Ui 1200 V) and high-voltage arc-quenching capacity required at 800 V AC.
What is the breaking capacity of VM7 at 800 V, 1000 V, and 1140 V AC?
In the H tier, VM7 achieves Icu = Ics = 50 kA at 800 V AC, 30 kA at 1000 V AC, and 20 kA at 1140 V AC.
Where else is VM7 used besides solar PV?
VM7 is widely specified in wind turbine nacelles/towers, underground coal and metal mining (1140 V AC), and metallurgical heavy industrial drives.
What are the physical dimensions of VM7-320 and VM7-630?
VM7-320 measures 120 × 200 × 103 mm; VM7-630 measures 158 × 325 × 177 mm (W × L × H).
What instantaneous trip options are available?
VM7 offers 10×In or 15×In instantaneous magnetic release settings to coordinate with inverter or motor inrush.
Does VM7 support shunt trip and auxiliary contacts?
Yes. VM7 features modular internal accessory pockets supporting codes 00–78 (alarm, shunt, UVT, auxiliary contacts) for rapid field replacement.