The VIOX VOPD3-63VAS (63 A) and VOPD3-100VAS (100 A) introduce selectable Synchronous (SYN) and Asynchronous (ASY) three-phase protection via menu parameter CEL. In SYN mode, all three phases disconnect together to protect 3-phase motors; in ASY mode, each phase operates independently so a fault on one phase never blacks out healthy single-phase loads on the remaining two phases.
Características
- Dual-mode CEL setting: SYN (synchronous 3-phase trip for motors/pumps) or ASY (independent per-phase trip for mixed commercial/residential loads).
- Full adjustable protection: over-voltage (230–300 V), under-voltage (140–210 V), over-current (1–63 A or 1–100 A), phase unbalance (20–99 V), and phase-sequence protection (U12).
- Clear per-phase fault indicators (>U, <U, >I, SYN/ASY asymmetry LED, and L1/L2/L3 disconnect LEDs in ASY mode).
- ±9.5% manual voltage and current calibration, automatic reset, and continuous over-current fault lockout (C5).
- Standard 35 mm DIN-rail snap mounting, CE certified.
Especificaciones
VOPD3-63VAS / VOPD3-100VAS Technical Specifications
| Parámetro | Especificación |
|---|---|
| Tensión nominal | 3×230 V (220/380 V AC, 3P+N) |
| Rango de corriente nominal | VOPD3-63VAS: 1–63 A · VOPD3-100VAS: 1–100 A (default 30 A) |
| Working Mode (CEL) | SYN (Synchronous 3-phase trip, default) / ASY (Independent per-phase trip) |
| Over-Voltage / Recovery | 230–300 V (default 270 V) / 220–295 V (default 265 V) |
| Under-Voltage / Recovery | 140–210 V (default 170 V) / 145–215 V (default 175 V) |
| Phase Sequence & Unbalance | Phase Sequence ON/OFF (U12, default ON) · Unbalance 20–99 V (active in SYN mode) |
| Calibration & Lockout | Voltage/Current ±9.5% · Continuous over-current lockout 0–20 / OFF |
| Dimensions & Certification | 91 × 52 × 102 mm · 35 mm DIN rail · CE |
VOPD3-63VAS / VOPD3-100VAS Programmable Menu Parameters
| Código | Parámetro | Gama | Factory Default |
|---|---|---|---|
| P1 | Power-On Delay | 1–500 s | 10 s |
| U1–U8 | Over/Under-Voltage Trip, Recovery, Delay & Action | 230–300 V / 140–210 V / 1–500 s / 0.1–30 s | 270 V / 170 V / 30 s / 1.0 s |
| U9 / C4 | 3-Phase Voltage & Current Calibration | -9.5% to +9.5% | 0% |
| U10 / U11 / U12 | Voltage Unbalance / Recovery / Phase Sequence | 20–99 V / 15–94 V / ON–OFF | 20 V / 15 V / ON |
| C1 / C2 / C3 / C5 | Over-Current Trip / Delay / Action / Lockout | 1–63 A or 1–100 A / 1–500 s / 0.1–30 s / 0–20 | 30 A / 30 s / 1.0 s / OFF |
| CEL | Synchronous vs. Asynchronous Operating Mode | SYN / ASY | SYN |
Wiring & Setup Guide
- Wire 3P+N (L1, L2, L3, N) strictly according to the housing IN/OUT diagram before energizing.
- IMPORTANT: In ASY (asynchronous) mode, phase-sequence protection and 3-phase voltage-unbalance protection are automatically disabled because each phase switches independently. Use SYN mode for 3-phase motors.
- Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.
PREGUNTAS FRECUENTES
When should I select SYN vs. ASY mode on VOPD3-63VAS?
Select SYN mode when feeding 3-phase motors, chillers, or compressors that must disconnect all 3 phases simultaneously to prevent single-phasing damage. Select ASY mode when a 3-phase panel feeds independent single-phase apartment or lighting circuits so a fault on L1 does not cut power to L2 and L3.