VIOX VOPD3-63VAS / VOPD3-100VAS Three-Phase SYN / ASY Dual-Mode Voltage & Current Protector (63A / 100A)

The VIOX VOPD3-63VAS (63 A) and VOPD3-100VAS (100 A) introduce selectable Synchronous (SYN) and Asynchronous (ASY) three-phase protection via menu parameter CEL. In SYN mode, all three phases disconnect together to protect 3-phase motors; in ASY mode, each phase operates independently so a fault on one phase never blacks out healthy single-phase loads on the remaining two phases.

Modèle VIOX
VOPD3-63VAS / VOPD3-100VAS
Tension
3×230 V (220/380 V AC)
Actuel
1–63 A / 1–100 A
Format
91 × 102 × 52 mm

Vue d'ensemble

The VIOX VOPD3-63VAS (63 A) and VOPD3-100VAS (100 A) introduce selectable Synchronous (SYN) and Asynchronous (ASY) three-phase protection via menu parameter CEL. In SYN mode, all three phases disconnect together to protect 3-phase motors; in ASY mode, each phase operates independently so a fault on one phase never blacks out healthy single-phase loads on the remaining two phases.

Caractéristiques

  • Dual-mode CEL setting: SYN (synchronous 3-phase trip for motors/pumps) or ASY (independent per-phase trip for mixed commercial/residential loads).
  • Full adjustable protection: over-voltage (230–300 V), under-voltage (140–210 V), over-current (1–63 A or 1–100 A), phase unbalance (20–99 V), and phase-sequence protection (U12).
  • Clear per-phase fault indicators (>U, <U, >I, SYN/ASY asymmetry LED, and L1/L2/L3 disconnect LEDs in ASY mode).
  • ±9.5% manual voltage and current calibration, automatic reset, and continuous over-current fault lockout (C5).
  • Standard 35 mm DIN-rail snap mounting, CE certified.

Spécifications

VOPD3-63VAS / VOPD3-100VAS Technical Specifications

ParamètreSpécification
Tension nominale3×230 V (220/380 V AC, 3P+N)
Plage de courant nominalVOPD3-63VAS: 1–63 A · VOPD3-100VAS: 1–100 A (default 30 A)
Working Mode (CEL)SYN (Synchronous 3-phase trip, default) / ASY (Independent per-phase trip)
Over-Voltage / Recovery230–300 V (default 270 V) / 220–295 V (default 265 V)
Under-Voltage / Recovery140–210 V (default 170 V) / 145–215 V (default 175 V)
Phase Sequence & UnbalancePhase Sequence ON/OFF (U12, default ON) · Unbalance 20–99 V (active in SYN mode)
Calibration & LockoutVoltage/Current ±9.5% · Continuous over-current lockout 0–20 / OFF
Dimensions & Certification91 × 52 × 102 mm · 35 mm DIN rail · CE

VOPD3-63VAS / VOPD3-100VAS Programmable Menu Parameters

CodeParamètreGammeFactory Default
P1Power-On Delay1–500 s10 s
U1–U8Over/Under-Voltage Trip, Recovery, Delay & Action230–300 V / 140–210 V / 1–500 s / 0.1–30 s270 V / 170 V / 30 s / 1.0 s
U9 / C43-Phase Voltage & Current Calibration-9.5% to +9.5%0%
U10 / U11 / U12Voltage Unbalance / Recovery / Phase Sequence20–99 V / 15–94 V / ON–OFF20 V / 15 V / ON
C1 / C2 / C3 / C5Over-Current Trip / Delay / Action / Lockout1–63 A or 1–100 A / 1–500 s / 0.1–30 s / 0–2030 A / 30 s / 1.0 s / OFF
CELSynchronous vs. Asynchronous Operating ModeSYN / ASYSYN

Wiring & Setup Guide

  • Wire 3P+N (L1, L2, L3, N) strictly according to the housing IN/OUT diagram before energizing.
  • IMPORTANT: In ASY (asynchronous) mode, phase-sequence protection and 3-phase voltage-unbalance protection are automatically disabled because each phase switches independently. Use SYN mode for 3-phase motors.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

FAQ

When should I select SYN vs. ASY mode on VOPD3-63VAS?

Select SYN mode when feeding 3-phase motors, chillers, or compressors that must disconnect all 3 phases simultaneously to prevent single-phasing damage. Select ASY mode when a 3-phase panel feeds independent single-phase apartment or lighting circuits so a fault on L1 does not cut power to L2 and L3.