VIOX ELECTRIC
Sprache

VIOX VOPD3-63VAS / VOPD3-100VAS Three-Phase SYN / ASY Dual-Mode Voltage & Current Protector (63A / 100A)

The VIOX VOPD3-63VAS (63 A) and VOPD3-100VAS (100 A) introduce selectable Synchronous (SYN) and Asynchronous (ASY) three-phase protection via menu parameter CEL. In SYN mode, all three phases disconnect together to protect 3-phase motors; in ASY mode, each phase operates independently so a fault on one phase never blacks out healthy single-phase loads on the remaining two phases.

VIOX Modell
VOPD3-63VAS / VOPD3-100VAS
Spannung
3×230 V (220/380 V AC)
Aktuell
1–63 A / 1–100 A
Format
91 × 102 × 52 mm

Übersicht

The VIOX VOPD3-63VAS (63 A) and VOPD3-100VAS (100 A) introduce selectable Synchronous (SYN) and Asynchronous (ASY) three-phase protection via menu parameter CEL. In SYN mode, all three phases disconnect together to protect 3-phase motors; in ASY mode, each phase operates independently so a fault on one phase never blacks out healthy single-phase loads on the remaining two phases.

Eigenschaften

  • Dual-mode CEL setting: SYN (synchronous 3-phase trip for motors/pumps) or ASY (independent per-phase trip for mixed commercial/residential loads).
  • Full adjustable protection: over-voltage (230–300 V), under-voltage (140–210 V), over-current (1–63 A or 1–100 A), phase unbalance (20–99 V), and phase-sequence protection (U12).
  • Clear per-phase fault indicators (>U, <U, >I, SYN/ASY asymmetry LED, and L1/L2/L3 disconnect LEDs in ASY mode).
  • ±9.5% manual voltage and current calibration, automatic reset, and continuous over-current fault lockout (C5).
  • Standard 35 mm DIN-rail snap mounting, CE certified.

Spezifikationen

VOPD3-63VAS / VOPD3-100VAS Technical Specifications

ParameterSpezifikation
Nennspannung3×230 V (220/380 V AC, 3P+N)
NennstrombereichVOPD3-63VAS: 1–63 A · VOPD3-100VAS: 1–100 A (default 30 A)
Working Mode (CEL)SYN (Synchronous 3-phase trip, default) / ASY (Independent per-phase trip)
Over-Voltage / Recovery230–300 V (default 270 V) / 220–295 V (default 265 V)
Under-Voltage / Recovery140–210 V (default 170 V) / 145–215 V (default 175 V)
Phase Sequence & UnbalancePhase Sequence ON/OFF (U12, default ON) · Unbalance 20–99 V (active in SYN mode)
Calibration & LockoutVoltage/Current ±9.5% · Continuous over-current lockout 0–20 / OFF
Dimensions & Certification91 × 52 × 102 mm · 35 mm DIN rail · CE

VOPD3-63VAS / VOPD3-100VAS Programmable Menu Parameters

CodeParameterBereichFactory Default
P1Power-On Delay1–500 s10 s
U1–U8Over/Under-Voltage Trip, Recovery, Delay & Action230–300 V / 140–210 V / 1–500 s / 0.1–30 s270 V / 170 V / 30 s / 1.0 s
U9 / C43-Phase Voltage & Current Calibration-9.5% to +9.5%0%
U10 / U11 / U12Voltage Unbalance / Recovery / Phase Sequence20–99 V / 15–94 V / ON–OFF20 V / 15 V / ON
C1 / C2 / C3 / C5Over-Current Trip / Delay / Action / Lockout1–63 A or 1–100 A / 1–500 s / 0.1–30 s / 0–2030 A / 30 s / 1.0 s / OFF
CELSynchronous vs. Asynchronous Operating ModeSYN / ASYSYN

Wiring & Setup Guide

  • Wire 3P+N (L1, L2, L3, N) strictly according to the housing IN/OUT diagram before energizing.
  • IMPORTANT: In ASY (asynchronous) mode, phase-sequence protection and 3-phase voltage-unbalance protection are automatically disabled because each phase switches independently. Use SYN mode for 3-phase motors.
  • Explore the complete VIOX Voltage Protectors catalog for matched DIN-rail switchgear.

FAQ

When should I select SYN vs. ASY mode on VOPD3-63VAS?

Select SYN mode when feeding 3-phase motors, chillers, or compressors that must disconnect all 3 phases simultaneously to prevent single-phasing damage. Select ASY mode when a 3-phase panel feeds independent single-phase apartment or lighting circuits so a fault on L1 does not cut power to L2 and L3.

Benötigen Sie ein Produktangebot?
Lassen Sie es uns gemeinsam aufbauen.

Senden Sie uns das Produktmodell, die technischen Nennwerte, die Menge und die OEM-Anforderungen. Unser Team wird Ihre Anwendung prüfen und innerhalb eines Werktages antworten.

Angebot anfordern