VIOX Điện
Language

Máy cắt điện dòng điện dư cho xe điện VKL11-EV

The VIOX VKL11-EV residual current circuit breaker series is designed for Mode 3 electric vehicle charging installations. VKL11A-EV provides instantaneous Type A EV protection, while VKL11F-EV adds mixed-frequency residual-current detection and short-time-delayed tripping. Both versions detect sinusoidal AC, pulsating DC and smooth DC residual currents with a maximum 6 mA DC tripping threshold, in 16-100 A and 2P or 4P configurations.

Bình Hiện Tại
16-100 A
Dòng rò (Residual Current)
A-EV: 10-300 mA; F-EV: 30 mA
DC Threshold
6 mA
Cấu hình cực
2P, 4P

Tổng quan

The VKL11-EV series comprises residual current circuit breakers designed for Mode 3 electric vehicle charging installations. VKL11A-EV provides instantaneous Type A EV protection for standard wall boxes and charging stations, while VKL11F-EV adds mixed-frequency residual-current detection and short-time-delayed operation. Both versions detect sinusoidal AC and pulsating DC residual currents and switch off at a maximum smooth DC threshold of 6 mA. The range covers rated currents from 16 A to 100 A in 2P and 4P configurations. Suitable overload and short-circuit protection must be installed separately.

Đặc trưng

  • Two EV protection versions: VKL11A-EV Type A EV and VKL11F-EV Type F EV.
  • Sinusoidal AC, pulsating DC and 6 mA smooth DC residual-current detection.
  • Available in 2P and 4P configurations from 16 A to 100 A.
  • Rated impulse withstand voltage of 6 kV.
  • IP20 protection with an integrated fault-current indicator.
  • Top or bottom power entry.

Mô hình

Variant Loại sản phẩm Dòng điện dư định mức khi vận hành Tripping characteristic Phát hiện dòng điện rò
VKL11A-EV Type A EV RCCB 10 mA for 2P/4P 16-40 A versions; 30, 100, 300 mA Tức thời Sinusoidal AC, pulsating DC and smooth DC switch-off at a maximum threshold of 6 mA
VKL11F-EV Type F EV RCCB 30 mA Trễ thời gian ngắn Sinusoidal AC, pulsating DC, mixed-frequency residual current and smooth DC switch-off at a maximum threshold of 6 mA

Thông số kỹ thuật

Electrical Data

Tham số Đặc điểm kỹ thuật
Dòng điện định mức (In) 16, 25, 32, 40, 63, 80, 100 A
Điện áp định mức (Ue) 2P: 240 V AC; 4P: 415 V AC
Tần số định mức 50/60 Hz
Điện áp cách điện định mức (Ui) 500 V
Điện áp chịu xung định mức (Uimp) 6 kV (1.2/50 μs)
Dielectric test voltage 2.5 kV for 1 minute
Rated conditional short-circuit current (Inc/IΔc) 6 kA, 10 kA
Ô nhiễm độ 2

Making and Breaking Data

Dòng điện định mức Rated residual making and breaking capacity (IΔm) VKL11F-EV additional ratings
16, 25, 32, 40 A 500 A Im: 1,500 A; peak withstand current: 3 kA (8/20 μs)
63 A 630 A Im: 1,500 A; peak withstand current: 3 kA (8/20 μs)
80 A 800 A Im: 1,500 A; peak withstand current: 3 kA (8/20 μs)
100 A 1,000 A Im: 1,500 A; peak withstand current: 3 kA (8/20 μs)

Protection Data

Tham số Đặc điểm kỹ thuật
Dòng điện dư xoay chiều hình sin Detected
Pulsating DC residual current Detected
Smooth DC tripping threshold 6 mA
Smooth DC residual current Switch-off at a maximum threshold of 6 mA
Fault-current indicator Yes
Mức độ bảo vệ IP20

Mechanical Data

Tham số Đặc điểm kỹ thuật
Điện sức chịu đựng ≥2,000 operating cycles
Cơ khí sức chịu đựng ≥2,000 operating cycles

Installation Data

Tham số Đặc điểm kỹ thuật
Loại kết nối đầu cuối Cable/pin-type busbar
Cable terminal capacity 25-35 mm²; 18-3/18-2 AWG
Busbar terminal capacity 10/16 mm²; 18-8/18-5 AWG
Terminal tightening torque 2.5 N·m; 22 in-lb
Lắp ráp 35 mm DIN rail according to EN 60715, with fast-clip device
Power entry Trên hoặc dưới

Environmental and Standards Data

Tham số Đặc điểm kỹ thuật
Nhiệt độ môi trường -25°C to +55°C, with daily average ≤35°C
Nhiệt độ lưu trữ -40°C đến +70°C
VKL11A-EV standards IEC/EN 61008-1, IEC 62955
VKL11F-EV standards IEC/EN 61008-1, EN 62423, OVE E8601

Hướng dẫn lựa chọn

Code position Ý nghĩa Catalog value or options
V VIOX enterprise identification V
KL RCCB product family code KL
11 Design serial number 11
A-EV / F-EV Residual-current protection type A-EV or F-EV
Rated-current code Dòng điện định mức 16, 25, 32, 40, 63, 80 or 100 A
Residual-current code Dòng điện dư định mức khi vận hành VKL11A-EV: 10 mA for 16-40 A versions, or 30, 100 and 300 mA; VKL11F-EV: 30 mA
2P / 4P Số cực 2P or 4P

Protection Version

Select VKL11A-EV for instantaneous Type A EV protection or VKL11F-EV for mixed-frequency detection with short-time-delayed operation.

Bình Hiện Tại

Choose one of the listed ratings from 16 A to 100 A to match the charging circuit rating.

Nhạy cảm

For VKL11A-EV, select 10 mA for 16-40 A versions or 30, 100 or 300 mA. VKL11F-EV is listed with 30 mA sensitivity.

Poles and Voltage

Select 2P for 240 V AC or 4P for 415 V AC charging installations.

Đường cong chuyến đi

Đặc trưng VKL11A-EV VKL11F-EV
Rated residual operating current (IΔn) 10 mA for 2P/4P 16-40 A versions; 30, 100, 300 mA 30 mA
Smooth DC tripping threshold 6 mA 6 mA
Mixed-frequency residual current Detected according to Type F / EN 62423
Thời gian vấp ngã Tức thời Trễ thời gian ngắn
Break time at IΔn ≤100 ms (normal type) 10-300 ms (G type)

Kích thước

VKL11-EV electric vehicle RCCB dimensional drawing
VKL11-EV 2P and 4P RCCB dimensional drawing.

Ứng dụng

  • Mode 3 electric vehicle charging installations.
  • Standard EV wall boxes using VKL11A-EV instantaneous protection.
  • EV charging stations using VKL11A-EV Type A EV protection.
  • EV charging circuits with mixed-frequency leakage currents using VKL11F-EV.

Cài đặt

  • Install the RCCB together with suitable overload and short-circuit protection.
  • Mount the device on a 35 mm DIN rail according to EN 60715 using the fast-clip device.
  • Use cable or a pin-type busbar within the listed terminal capacities.
  • Apply the listed terminal tightening torque of 2.5 N·m or 22 in-lb.
  • Power entry may be made from the top or bottom.

Câu hỏi thường gặp

What is the VKL11-EV series designed for?

It is designed for Mode 3 electric vehicle charging installations.

What is the difference between VKL11A-EV and VKL11F-EV?

VKL11A-EV provides instantaneous Type A EV protection. VKL11F-EV adds mixed-frequency residual-current detection and short-time-delayed tripping.

What is the smooth DC tripping threshold?

Both versions switch off at a maximum smooth DC residual-current threshold of 6 mA.

Which rated currents and pole configurations are available?

The series covers 16, 25, 32, 40, 63, 80 and 100 A in 2P and 4P configurations.

Does the VKL11-EV provide overload and short-circuit protection?

The catalog specifies that the RCCB must be installed together with suitable overload and short-circuit protection.

Which standards are listed for each version?

VKL11A-EV lists IEC/EN 61008-1 and IEC 62955. VKL11F-EV lists IEC/EN 61008-1, EN 62423 and OVE E8601.

Need a Product Quote?
Hãy cùng chúng tôi thực hiện dự án này.

Send us the product model, technical ratings, quantity, and OEM requirements. Our team will review your application and respond within one business day.

Yêu cầu báo giá