Tổng quan
The VKL11B Type B and VKL11B+ Type B+ residual current circuit breakers provide residual-current protection in AC 50/60 Hz installations that may generate alternating, pulsating DC or smooth DC residual currents. Type B detects frequencies up to 1 kHz, while Type B+ extends detection up to 20 kHz. The range includes 16 A to 100 A ratings, 2P and 4P configurations, and instantaneous, K short-time-delayed or T selective versions. It is intended for installations using frequency converters, photovoltaic systems, UPS systems and other electronically controlled equipment. Suitable overload and short-circuit protection must be provided separately.
Đặc trưng
- Detects alternating, pulsating DC and smooth DC residual currents.
- High-frequency detection up to 1 kHz for Type B and 20 kHz for Type B+.
- Instantaneous, K short-time-delayed and T selective versions.
- Rated conditional short-circuit current of 10 kA.
- Mechanical red/green contact-position indicator.
- Top or bottom power entry and installation in any mounting position.
Mô hình
| Variant | Phát hiện dòng điện rò | 频率范围 | Additional characteristic |
|---|---|---|---|
| Loại B | Alternating, pulsating DC and smooth DC residual currents | Lên đến 1 kHz | Universal current-sensitive RCCB |
| Loại B+ | Full Type B detection capability | Lên đến 20 kHz | Additional tripping values below 420 mA |
Thông số kỹ thuật
Electrical Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Product versions | Type B and Type B+ RCCB |
| Dòng điện định mức (In) | 16, 25, 32, 40, 63, 80, 100 A |
| Rated voltage (Un) | 2P: 230/240 V AC; 4P: 400/415 V AC |
| Tần số định mức | 50/60 Hz |
| Electronic operating voltage | 50-264 V AC |
| Test circuit voltage range | 2P: 184-264 V AC; 4P: 184-440 V AC |
| Điện áp cách điện định mức (Ui) | 500 V |
| Điện áp chịu xung định mức (Uimp) | 4 kV (1.2/50 μs) |
| Rated conditional short-circuit current (Inc) | 10 kA |
| Rated making and breaking capacity (Im) | 1,500 A |
| Maximum backup fuse | 100 A gG/gL for short-circuit and overload protection |
Protection Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Detected residual currents | Alternating, pulsating DC and smooth DC residual currents |
| High-frequency detection | Type B: up to 1 kHz; Type B+: up to 20 kHz |
| Chế độ hoạt động | Type A functionality: voltage independent; Type B/B+ functionality: voltage dependent |
| Dòng điện chịu đựng cực đại | 3 kA (8/20 μs); 5 kA for the selective version |
| Cách ly điện | Contact gap greater than 4 mm |
| Mức độ bảo vệ | IP20 |
Mechanical Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Điện sức chịu đựng | ≥2,000 operating cycles |
| Cơ khí sức chịu đựng | ≥4,000 operating cycles |
| Chỉ báo vị trí tiếp điểm | Mechanical red/green indicator |
Installation Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Loại thiết bị đầu cuối | Open/lift terminals |
| Công suất thiết bị đầu cuối | 1-25 mm² |
| Terminal tightening torque | 2-2.5 N·m |
| Độ dày thanh cái | 0.8-2 mm |
| Power entry | Trên hoặc dưới |
| Vị trí lắp đặt | Mọi vị trí |
Environmental and Standards Data
| Tham số | Đặc điểm kỹ thuật |
|---|---|
| Nhiệt độ bảo quản và vận chuyển | -40°C đến +70°C |
| Climatic resistance | According to IEC/EN 61008 |
| Design standards | IEC/EN 62423, IEC/EN 61008-1, OVE E8601; Type B+ additionally references VDE 0664-400 |
Hướng dẫn lựa chọn
| Code position | Ý nghĩa | Catalog value or options |
|---|---|---|
| V | VIOX enterprise identification | V |
| KL | RCCB product family code | KL |
| 11 | Design serial number | 11 |
| B / B+ | Loại dòng rò | B or B+ |
| Rated-current code | Dòng điện định mức | 16, 25, 32, 40, 63, 80 or 100 A |
| Residual-current code | Dòng điện dư định mức khi vận hành | 30, 100, 300 or 500 mA, depending on variant and time characteristic |
| 2P / 4P | Số cực | 2P or 4P |
Type B or Type B+
Select Type B for residual-current detection up to 1 kHz or Type B+ for full Type B detection capability up to 20 kHz.
Bình Hiện Tại
Choose one of the listed ratings from 16 A to 100 A to match the circuit rating.
Tripping Option
Select an instantaneous, K short-time-delayed or T selective version with a compatible residual operating-current rating.
Poles and Voltage
Select 2P for 230/240 V AC or 4P for 400/415 V AC installations.
Đường cong chuyến đi
| Đặc tính thời gian | Type B rated IΔn | Type B+ rated IΔn |
|---|---|---|
| Tức thời | 30, 100, 300, 500 mA | 30, 100, 300 mA |
| K short-time delayed (G/ASi) | 30, 100, 300, 500 mA | 30, 100, 300 mA |
| T selective | 100, 300, 500 mA | 100, 300 mA |
Kích thước
Ứng dụng
- Frequency converters and variable-speed machinery.
- Photovoltaic and UPS systems.
- Electric vehicle charging equipment.
- Medical equipment.
Cài đặt
- Use the RCCB together with suitable overload and short-circuit protection.
- Use conductors within the listed terminal capacity of 1-25 mm².
- Apply the listed terminal tightening torque of 2-2.5 N·m.
- Use busbars within the listed thickness range of 0.8-2 mm.
- Power entry may be made from the top or bottom, and the device may be installed in any mounting position.
Câu hỏi thường gặp
Which residual currents can the VKL11B detect?
Type B and Type B+ detect alternating, pulsating DC and smooth DC residual currents.
What is the difference between Type B and Type B+?
Type B detects residual-current frequencies up to 1 kHz. Type B+ extends the frequency range up to 20 kHz and additionally references VDE 0664-400.
Which rated currents and pole configurations are available?
The range covers 16, 25, 32, 40, 63, 80 and 100 A in 2P and 4P configurations.
Which tripping options are offered?
The catalog lists instantaneous, K short-time-delayed and T selective versions. Available residual operating-current ratings depend on the selected variant and time characteristic.
Does the VKL11B provide overload and short-circuit protection?
The catalog specifies that the RCCB must be used together with suitable overload and short-circuit protection.
Which standards are listed?
Type B references IEC/EN 62423, IEC/EN 61008-1 and OVE E8601. Type B+ additionally references VDE 0664-400.