Why Do MCCBs Offer Short-Time Delay Protection Without a Rated Short-Time Withstand Current (Icw)

Why Do MCCBs Offer Short-Time Delay Protection Without a Rated Short-Time Withstand Current (Icw)
MCCB electronic trip unit in industrial panel showing 400A rating and current display - VIOX Electric
MCCB electronic trip unit in industrial panel showing 400A rating and current display – VIOX Electric

Direct Answer

Molded Case Circuit Breakers (MCCBs) can provide short-time delay protection without a rated short-time withstand current (Icw) because they belong to IEC 60947-2 Category A, where selectivity is achieved through current-limiting technology rather than intentional time delays. Unlike Category B Air Circuit Breakers (ACBs) that “wait out” fault currents using high Icw ratings, MCCBs use electromagnetic contact repulsion and ultra-fast arc interruption to limit fault energy—protecting themselves while still coordinating with downstream devices through their inherent short-delay characteristics (typically 10-12× In) below the instantaneous trip threshold.


Key Takeaways

  • Category A vs. B: MCCBs (Category A) lack declared Icw ratings but possess inherent short-time withstand capability below their contact repulsion threshold (typically >12-14× In)
  • Current-Limiting Physics: Contact spring pressure is intentionally low in MCCBs to enable rapid electromagnetic repulsion at high fault currents (>25× In), preventing damage through fast interruption rather than prolonged withstand
  • Short-Delay Reality: MCCB short-delay settings (e.g., 10× In, 0.4s) only function when fault current stays below the instantaneous trip threshold—exceeding this triggers immediate action via magnetic trip or energy-based mechanisms
  • Selectivity Limitations: Full selectivity between MCCBs requires careful coordination tables; ACB-to-MCCB cascades achieve better results because ACBs can truly delay (Icw = Icu capability) while MCCBs handle downstream faults
  • Safety Override: Advanced MCCBs with defeatable instantaneous trips (e.g., Schneider NSX) incorporate “energy trip” or “instantaneous override” functions—if fault current exceeds ~25× In, gas-actuated mechanisms force immediate tripping regardless of settings

Understanding IEC 60947-2 Selectivity Categories

Size and construction comparison between ACB with Icw rating and compact MCCB Category A breaker - VIOX Electric
Size and construction comparison between ACB with Icw rating and compact MCCB Category A breaker – VIOX Electric

Category B: ACBs with Declared Icw

Air Circuit Breakers (ACBs) are designed for Category B applications where selectivity is achieved through intentional short-time delays. According to IEC 60947-2, these devices must declare a rated short-time withstand current (Icw)—the maximum fault current the breaker can carry in the closed position for a specified duration (0.05s, 0.1s, 0.25s, 0.5s, or 1.0s) without sustaining damage.

Key characteristics of Category B breakers:

Parameter Specification Purpose
Icw Rating Minimum 12× In or 5kA (≤2500A frames)
Minimum 30kA (>2500A frames)
Enables intentional delay during faults
Contact Design High spring pressure Prevents contact repulsion during delay period
Trip Deferrability Instantaneous trip can be disabled Allows pure time-based coordination
Typical Application Main incomers, distribution feeders Coordinates with downstream MCCBs

For example, an 800A ACB with Icw = 85kA/1s can withstand 85kA fault current for up to 1 second while the short-time delay relay “waits” for downstream devices to clear the fault. This capability requires robust mechanical construction—reinforced contact arms, high contact pressure (preventing electromagnetic repulsion), and thermal mass to absorb I2t energy.

Category A: MCCBs Without Declared Icw

Molded Case Circuit Breakers (MCCBs) typically fall under Category A—devices “not specifically intended for selectivity under short-circuit conditions” per IEC 60947-2. These breakers do not declare Icw values because their design philosophy prioritizes rapid fault interruption over prolonged fault withstand.

Why MCCBs don’t declare Icw:

  1. Current-Limiting Design: Contact spring pressure is intentionally low to facilitate rapid electromagnetic repulsion when fault current exceeds ~10-14× In
  2. Instantaneous Trip Mandate: Most MCCBs cannot disable instantaneous protection—any fault exceeding the instantaneous threshold triggers immediate tripping
  3. Thermal Limitations: Compact molded construction cannot dissipate the thermal energy (I2t) associated with prolonged high-current withstand

However, this does not mean MCCBs lack short-time withstand capability entirely—they possess an inherent, undeclared threshold below which contacts remain closed.


The Physics of MCCB Contact Repulsion

MCCB electromagnetic contact repulsion mechanism diagram showing force balance and current thresholds - VIOX Electric
MCCB electromagnetic contact repulsion mechanism diagram showing force balance and current thresholds – VIOX Electric

Electromagnetic Repulsion Threshold

When fault current flows through parallel contact paths in an MCCB, it generates opposing magnetic fields that create electrodynamic repulsion forces (Lorentz force). The contact spring must counteract this force to keep contacts closed.

Force balance equation:

Fspring > Frepulsion = k · I2

Where:

  • Fspring = Contact spring compression force
  • Frepulsion = Electromagnetic repulsion force (proportional to I2)
  • k = Geometric constant (contact spacing, conductor configuration)
MCCB Design Parameter Category A (MCCB) Category B (ACB)
Contact Spring Pressure Low (2-5 N/mm) High (10-20 N/mm)
Repulsion Threshold 12-14× In >50× In
Contact Opening Speed 3-7 ms (ultra-fast) 20-50 ms (controlled)
Design Priority Limit fault energy (I2t) Withstand fault duration

Motor Starting Considerations

Research by Shanghai Electrical Research Institute on 52 motor samples revealed that direct-on-line (DOL) starting produces first-peak inrush currents of 8-12× In for most motors, with outliers reaching 13× In.

This data drives MCCB design constraints:

  • Distribution MCCBs: Instantaneous trip set at 10-12× In (must not trip on capacitor inrush or transformer energization)
  • Motor-Rated MCCBs: Instantaneous trip set at 13-14× In (must ride through DOL starting)
  • Contact Repulsion Threshold: Must exceed instantaneous trip setting by 15-20% margin to prevent nuisance contact opening during starting transients

Example calculation for a 100A motor-rated MCCB:

Instantaneous trip setting: 13 × 100A = 1,300A
Contact repulsion threshold: 1,300A × 1.2 = 1,560A (design target)
Undeclared “Icw” capability: ~1,500A (below repulsion threshold)

This 1,500A threshold represents the MCCB’s inherent short-time withstand capability—sufficient for coordination with downstream devices in the 1,000-1,500A fault range, but far below the declared Icw values of ACBs (typically 30-85kA).


How MCCB Short-Time Delay Actually Works

MCCB three-zone protection logic diagram showing overload, short-time delay, and instantaneous trip thresholds - VIOX Electric
MCCB three-zone protection logic diagram showing overload, short-time delay, and instantaneous trip thresholds – VIOX Electric

The Three Operating Zones

Modern electronic-trip MCCBs feature three protection zones, but their interaction differs fundamentally from ACBs:

Protection Zone Setting Range Actual Behavior
Long-Time (Overload) 0.4-1.0× In, 3-30s Thermal protection via I2t calculation
Short-Time Delay 2-12× In, 0.1-0.5s Only active below instantaneous threshold
Instantaneous 10-14× In (fixed or adjustable) Cannot be disabled in most MCCBs

Scenario 1: Fault Current Below Instantaneous Threshold

Conditions: Fault current = 8× In (800A for a 100A breaker)

  1. Current exceeds long-time zone → Short-time delay activates
  2. Electronic trip unit starts countdown (e.g., 0.4s)
  3. If fault persists, trip coil energizes after delay
  4. Contacts open via stored-energy mechanism (~20-30 ms opening time)

Result: True time-delayed coordination with downstream devices

Scenario 2: Fault Current Above Instantaneous Threshold

Conditions: Fault current = 15× In (1,500A for a 100A breaker)

  1. Current exceeds instantaneous threshold → Magnetic trip actuates immediately
  2. Short-time delay setting is bypassed
  3. Trip coil energizes within 5-10 ms
  4. Contacts open, but fault current may have already caused electromagnetic repulsion

Result: No intentional delay—MCCB trips as fast as possible

Scenario 3: Fault Current Far Exceeds Repulsion Threshold

Conditions: Fault current = 50× In (5,000A for a 100A breaker, approaching Icu)

  1. Electromagnetic repulsion force exceeds spring pressure
  2. Contacts blow apart within 3-7 ms (faster than trip mechanism)
  3. Arc voltage rises rapidly, limiting peak current (current-limiting action)
  4. Arc energy may trigger trip mechanism, or breaker relies on arc extinction alone

Result: Ultra-fast current limiting—no coordination, but equipment protection via I2t reduction


Special Case: MCCBs with Defeatable Instantaneous Trip

Schneider NSX “Energy Trip” Mechanism

Some high-end MCCBs (e.g., Schneider Electric NSX with Micrologic trip units) allow instantaneous protection to be disabled for improved selectivity. However, these devices incorporate a mandatory safety override called “energy trip” or “instantaneous override.”

How it works:

  1. User disables instantaneous trip, enables short-time delay (e.g., 10× In, 0.4s)
  2. Fault current reaches 30× In (3,000A for a 100A breaker)
  3. Contacts repel, arc forms
  4. Arc energy ionizes gas-generating material in arc chamber
  5. Pressure rise actuates pneumatic trip mechanism within 10-15 ms
  6. Breaker trips regardless of electronic trip unit settings
Fault Current Level NSX Response Standard MCCB Response
8× In Short-time delay functions normally Short-time delay functions
15× In Short-time delay functions (inst. disabled) Instantaneous trip (cannot disable)
>25× In Energy trip overrides delay Contact repulsion + instant trip

This design prevents catastrophic failure when users misconfigure protection settings—the MCCB will always self-protect at extreme fault levels, even if it compromises selectivity.


Practical Coordination Strategies

Time-current coordination diagram showing ACB and MCCB selectivity zones with fault scenario analysis - VIOX Electric
Time-current coordination diagram showing ACB and MCCB selectivity zones with fault scenario analysis – VIOX Electric

Strategy 1: ACB-to-MCCB Cascade (Recommended)

Configuration:

  • Upstream: 1600A ACB, Icw = 65kA/0.5s, short-time delay = 0.4s
  • Downstream: 400A MCCB, Icu = 50kA, instantaneous = 5,000A (12.5× In)

Coordination analysis:

Fault Location Fault Current Upstream ACB Action Downstream MCCB Action
Downstream feeder 8 kA Waits 0.4s (within Icw) Trips instantly (>12.5× In)
Downstream feeder 45 kA Waits 0.4s (within Icw) Trips instantly (current-limiting)
Main busbar 60 kA Trips after 0.4s Not affected

Result: Full selectivity up to 50kA (MCCB Icu limit)

Strategy 2: MCCB-to-MCCB Coordination (Limited)

Configuration:

  • Upstream: 400A MCCB, instantaneous = 5,000A (12.5× In)
  • Downstream: 100A MCCB, instantaneous = 1,300A (13× In)

Coordination analysis:

Fault Current Upstream MCCB Downstream MCCB Selectivity?
1,500A Short-delay (0.3s) Instant trip ✅ Yes
4,000A Short-delay (0.3s) Instant trip ✅ Yes
6,000A Instant trip Instant trip ❌ No (both trip)

Selectivity limit: ~4,500A (90% of upstream instantaneous setting)

Improvement: Use manufacturer coordination tables to verify actual let-through energy—current-limiting MCCBs may still achieve selectivity at higher fault levels through I2t discrimination.


Comparison Table: ACB vs. MCCB Short-Time Characteristics

Feature ACB (Category B) MCCB (Category A)
Icw Declaration ✅ Yes (30-85 kA, 0.05-1.0s) ❌ No (undeclared)
Inherent Withstand Very high (>50× In) Limited (12-14× In)
Contact Spring Pressure High (prevents repulsion) Low (enables current limiting)
Instantaneous Trip Can be disabled Usually fixed (cannot disable)
Short-Time Delay Range 0.05-1.0s (adjustable) 0.1-0.5s (only below inst. threshold)
Coordination Method Time-based (true delay) Current-based (limitation + delay)
Typical Application Main incomer (1000-6300A) Feeder protection (16-1600A)
Selectivity with Downstream Full (up to Icw) Partial (up to inst. threshold)
Self-Protection Mechanism Thermal mass + mechanical strength Contact repulsion + arc limiting

Why This Matters for System Design

Misconception 1: “MCCB Short-Delay = ACB Short-Delay”

Reality: MCCB short-delay only functions within a narrow current window (between long-time and instantaneous thresholds). For faults exceeding instantaneous settings, MCCBs trip immediately—no delay occurs.

Design impact: When specifying MCCB protection, always verify:

  1. Downstream device instantaneous settings
  2. Maximum fault current at coordination point
  3. Whether fault current will exceed upstream MCCB instantaneous threshold

Misconception 2: “No Icw Rating = No Short-Time Capability”

Reality: MCCBs possess inherent short-time withstand up to their contact repulsion threshold (~12-14× In). This capability enables limited coordination with downstream devices, though not to the extent of ACBs.

Design impact: MCCB-to-MCCB coordination is possible but requires:

  • Careful instantaneous setting separation (minimum 1.5:1 ratio)
  • Manufacturer-provided selectivity tables
  • Consideration of current-limiting effects on let-through energy

Misconception 3: “Disabling Instantaneous Trip Makes MCCB = ACB”

Reality: Even MCCBs with defeatable instantaneous trips (e.g., NSX) incorporate energy-based override mechanisms that force tripping at extreme fault levels (>25× In). They cannot “wait out” high fault currents like ACBs.

Design impact: When using MCCBs with adjustable instantaneous:

  • Verify energy trip threshold with manufacturer
  • Do not assume ACB-like behavior at fault currents approaching Icu
  • Consider arc flash energy implications of delayed tripping

Internal Links & Related Resources

For deeper understanding of related protection concepts, explore these VIOX technical guides:


FAQ: MCCB Short-Time Protection

Q1: Can I use an MCCB as a main incomer instead of an ACB?

A: Possible but not recommended for systems requiring full selectivity. MCCBs lack declared Icw ratings, so they cannot reliably delay tripping for downstream coordination at high fault currents (>10× In). Use ACBs for main incomers in industrial facilities where selectivity is critical, or verify coordination limits with manufacturer tables for commercial applications.

Q2: What happens if I set MCCB short-time delay to 0.5s but fault current is 20× In?

A: The breaker will trip instantly via magnetic trip, ignoring the 0.5s delay setting. MCCB short-time delays only function when fault current stays between the short-time pickup (e.g., 2-10× In) and instantaneous threshold (e.g., 12× In). Above instantaneous, the magnetic element overrides electronic settings.

Q3: Do all MCCBs use current-limiting technology?

A: No. Thermal-magnetic MCCBs (fixed trip, no adjustability) typically use slower bimetallic overload elements and may not achieve true current limitation. Electronic-trip MCCBs with fast-acting contacts and optimized arc chutes are more likely to be current-limiting (verify with manufacturer’s let-through curves showing Ip and I2t values below prospective fault levels).

Q4: How do I verify selectivity between two MCCBs?

A: Use manufacturer coordination tables (not just time-current curves). Tables account for:

  • Let-through energy (I2t) of downstream breaker
  • Non-tripping energy threshold of upstream breaker
  • Current-limiting effects at various fault levels
    Example: Schneider Electric provides detailed selectivity tables in their coordination guides showing maximum selectivity limits (e.g., “Selective up to 15kA” between specific MCCB models).

Q5: Why do motor-rated MCCBs have higher instantaneous settings (13-14× In)?

A: To prevent nuisance tripping during direct-on-line (DOL) motor starting. Research shows motor inrush can reach 12-13× In for the first peak. Motor-rated MCCBs also have higher contact repulsion thresholds (>14× In) to ensure contacts don’t blow open during starting transients, which would cause unnecessary wear and potential welding upon reclosure.


Conclusion

The apparent paradox of MCCBs offering short-time delay protection without rated Icw values stems from a fundamental difference in protection philosophy: ACBs withstand faults through mechanical strength and thermal mass, while MCCBs limit faults through electromagnetic physics and rapid arc interruption.

Understanding this distinction is critical for electrical engineers designing coordination schemes. MCCBs can achieve selective coordination with downstream devices within their inherent short-time withstand capability (typically 12-14× In), but they cannot replicate ACB behavior at high fault currents approaching their breaking capacity. For applications requiring full selectivity across the entire fault current range, ACB main incomers coordinating with MCCB feeders remain the gold standard—leveraging Category B time-delay capabilities upstream while exploiting Category A current-limiting benefits downstream.

Key design principle: Match the breaker category to the application—use ACBs where you need to “wait out” faults, use MCCBs where you need to “kill faults fast.”


About VIOX Electric: VIOX Electric is a leading B2B manufacturer of electrical equipment, specializing in molded case circuit breakers (MCCBs), air circuit breakers (ACBs), and comprehensive protection solutions for industrial and commercial applications. Our engineering team provides technical support for complex coordination studies and system design optimization. Contact us for application-specific guidance.

Author picture

Hi, I’m Joe, a dedicated professional with 12 years of experience in the electrical industry. At VIOX Electric, my focus is on delivering high-quality electrical solutions tailored to meet the needs of our clients. My expertise spans industrial automation, residential wiring, and commercial electrical systems.Contact me [email protected] if u have any questions.

Table of Contents
    Agregar un encabezado para empezar a generar la tabla de contenido
    Ask for Quote Now