VIOX VM6E Series Electronic MCCB (160A–2000A, Class B)

VIOX VM6E Series Electronic MCCB spans 7 frames from 160 A to 2000 A (3P/4P, AC 400 V / 690 V, 50/60 Hz, Ui 1000 V, Uimp 8 kV) with wide 0.4–1.0×In electronic trip adjustment (3-knob or 6-knob), Class B short-time withstand (Icw 10–20 kA/1s), and breaking capacity up to 100 kA Icu / 85 kA Ics.

Frame Range
160–2000 A (7 Frames)
전자 여행
0.4–1.0×In · 3 or 6 Knobs
Class B Icw
10 kA/1s (400–630) · 20 kA/1s (800+)
Max Breaking (400V)
Up to 100 kA Icu / 85 kA Ics

개요

The VIOX VM6E Series is a microprocessor-based electronic molded case circuit breaker engineered for high-selectivity industrial switchgear across AC 400 V and AC 690 V networks (50/60 Hz). Spanning 7 frames from 160 A to 2000 A (12 A–2000 A adjustable, 3P/4P), VM6E delivers Class B selectivity with rated short-time withstand current Icw up to 20 kA/1s, 3-knob or 6-knob LSIG protection, optional ground-fault (Code G), overload-alarm-without-trip (Code III), thermomagnetic dual backup (Code R), and low-temperature-rise builds (40 K / 50 K / 60 K).

특징

  • Wide 0.4–1.0×In electronic current adjustment (12 A to 2000 A) with 3-knob or 6-knob precision settings.
  • True Class B selectivity (400–2000 A): Icw = 10 kA/1s (400–630 A) and 20 kA/1s (800–2000 A).
  • Dual-voltage AC 400 V / AC 690 V operation (50/60 Hz) with up to 100 kA Icu / 85 kA Ics at 400 V.
  • Optional grounding protection (Code G), overload alarm without trip (Code III), and dual electronic + thermomagnetic backup (Code R).
  • Low-temperature-rise options: Type V (40 K), Type VI (50 K), and Type VII (60 K).
  • Full compatibility with DC3/DC6 motor operators, rotary handles, plug-in/draw-out bases, and internal accessory codes 00–78.

모델

Frame SeriesAdjustable In Range (A)Breaking TiersIcw (1s) & CategoryMax Icu / Ics (400 V AC)
VM6E-16012–32 A · 40–100 A · 63–160 AS, M, HClass A65 kA / 65 kA
VM6E-250100–250 AS, M, HClass A65 kA / 65 kA
VM6E-400160–400 A · 200–400 AM, H10 kA/1s · Class B70 kA / 70 kA
VM6E-630250–630 A · 400–630 AM, H10 kA/1s · Class B70 kA / 70 kA
VM6E-800400–630 A · 500–800 AM, H20 kA/1s · Class B65 kA / 50 kA
VM6E-1250630–1000 A · 850–1250 AM, H20 kA/1s · Class B65 kA / 50 kA
VM6E-2000500–1250 A · 630–1600 A · 800–2000 AM, H20 kA/1s · Class B100 kA / 85 kA

사양

Electrical & Breaking Capacity (400 V / 690 V AC)

Frame & TiersIcs (400 V / 690 V)Icu (400 V / 690 V)Icw (1s)
VM6E-160 S / M / H18 / 35 / 65 kA · 4 / 8 / 8 kA25 / 50 / 65 kA · 8 / 8 / 8 kA—
VM6E-250 S / M / H18 / 35 / 65 kA · 8 / 8 / 8 kA25 / 50 / 65 kA · 4 / 8 / 8 kA—
VM6E-400 M / H35 / 70 kA · 8 / 8 kA50 / 70 kA · 8 / 8 kA10 kA/1s
VM6E-630 M / H35 / 70 kA · 8 / 8 kA50 / 70 kA · 8 / 8 kA10 kA/1s
VM6E-800 M / H50 / 50 kA · 10 / 10 kA65 / 65 kA · 20 / 20 kA20 kA/1s
VM6E-1250 M / H50 / 50 kA · 10 / 10 kA65 / 65 kA · 20 / 20 kA20 kA/1s
VM6E-2000 M / H50 / 85 kA · 20 / 20 kA50 / 100 kA · 20 / 20 kA20 kA/1s

Outline Dimensions (mm)

액자폴란드Width W (mm)Length L (mm)Height Cover / Handle (mm)
VM6E-1603P / 4P90 / 12015568–82 / 94–108
VM6E-2503P / 4P105 / 14016568–88 / 96–116
VM6E-400 / 6303P / 4P140 / 184257103 / 152
VM6E-800 / 12503P / 4P210 / 280275.5103 / 152
VM6E-20003P / 4P210 / 280340141 / 244

External Accessories Compatibility

액세서리Supported Frames & Poles
Electric Motor Operation3P, 4P
Manual Rotary Handle (ZY1/ZF1/ZY2/ZF2/Z3)3P, 4P
Extension Copper Bar (P)3P, 4P
기계적 연동3P, 4P (up to 800 A)
Plug-in Front / Back Panel (Z2Q/Z2H/Z3Q/Z3H)3P, 4P (up to 800 A)
Draw-out Back-Panel (DR)400 / 630 / 800 A (3P only)

선택 가이드

코드 위치의미Catalog Value or Options
VM6E시리즈Electronic molded case circuit breaker (IEC/EN 60947-2)
160–2000프레임 전류160, 250, 400, 630, 800, 1250, 2000 A
3 / 6Knob configuration3 knobs (LSI basic) or 6 knobs (full LSIG + time delays)
G / III / R / VAdditional functionsG: Ground fault · III: Overload alarm w/o trip · R: Thermomagnetic backup · V/VI/VII: 40K/50K/60K low temp rise
3 / 4폴란드3P or 4P (Neutral Types A, B, C, D)
00–78Internal accessory code00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux · 50 Shunt+UVT · 60–69 Multi-Aux · 70–78 UVT+Aux (DC 24/110/220 V, AC 230/400 V)

1. Select Knob Depth

Choose 3-knob electronic trip for standard feeders or 6-knob LSIG for full time-graded selectivity.

2. Leverage Class B Icw

Use 10–20 kA/1s short-time delay on 400–2000 A main incoming MCCBs to coordinate with downstream breakers.

3. Specify Ground Fault

Add Code G for integrated ground-fault protection or Code R for dual electronic + thermomagnetic redundancy.

4. Consolidate Spares

0.4–1.0×In wide dial range lets one VM6E-400 or VM6E-630 cover an entire sub-panel spectrum.

설치

  • Verify short-time delay (tsd) settings against upstream ACB and downstream MCB/MCCB coordination curves.
  • Confirm 50/60 Hz AC 400 V or AC 690 V rated voltage and prospective fault level.
  • Select Code V (40 K) or VI (50 K) low-temperature-rise builds for IP54/IP65 sealed switchgear.
  • Compare with LCD metering VM6EY or thermomagnetic VM6 on our MCCB page.

자주 묻는 질문

Why is Class B selectivity (Icw 10–20 kA/1s) important on VM6E?

Class B MCCBs can withstand a short-circuit current for a programmable short-time delay (up to 1 second) without tripping instantaneously, allowing downstream branch breakers to clear the fault first and preventing upstream blackouts.

What is the difference between 3-knob and 6-knob VM6E trip units?

3-knob units provide compact Ir/Isd/Ii current settings, while 6-knob units add programmable long-delay/short-delay time settings and optional ground-fault protection for complex switchgear.

Does VM6E support both 400 V and 690 V AC?

Yes. All 7 VM6E frames (160 A to 2000 A) are rated for both AC 400 V and AC 690 V at 50/60 Hz with Ui = 1000 V and Uimp = 8 kV.

What does Additional Function Code R mean on VM6E?

Code R equips the VM6E with dual electronic + thermomagnetic protection for maximum reliability in critical industrial feeders.

What is the adjustable current range of VM6E?

Every VM6E frame is field-adjustable from 0.4 to 1.0×In—spanning 12 A on VM6E-160 up to 2000 A on VM6E-2000.

Are draw-out bases available for VM6E?

Yes. Draw-out back-panel bases are supported on VM6E-400, VM6E-630, and VM6E-800 (3P), and plug-in bases are supported from 160 A to 800 A (3P/4P).

2026 Technical Catalog · Online PDF
VIOX Full 18-Series MCCB & Intelligent Breaker Catalog
Open the complete 18-series catalog online for frame dimensions, time-current trip curves, wiring schematics, and factory order codes (PDF · 26.7 MB).
Open Full Catalog PDF ↗

제품 견적이 필요하신가요?
함께 만들어 갑시다.

제품 모델, 기술 정격, 수량 및 OEM 요구 사항을 보내주십시오. 당사 팀에서 귀하의 애플리케이션을 검토한 후 영업일 기준 1일 이내에 답변해 드리겠습니다.

견적 요청하기