개요
The VIOX DC6 Series is a compact electromagnet-type electric operating mechanism engineered to motorize VIOX VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, and VM6ELY molded case circuit breakers from 125 A through 2000 A. Supporting AC/DC 220 V, AC/DC 380 V, and DC 24 V control supplies (50/60 Hz) with dedicated P1/P2 power terminals, S1/S2/S4 control inputs, ON/TRIPPED/OFF visual status, manual/auto selector, and RS485 communication, DC6 enables reliable remote switching and SCADA automation.
특징
- Complete 8-frame compatibility: DC6-125, 160, 250, 400, 630, 800, 1250, and 2000 A.
- Fast, compact electromagnet mechanism with integrated ON / TRIPPED / OFF indicator and Manual/Auto lock.
- Wide control voltage options: AC/DC 220 V, AC/DC 380 V, and DC 24 V (50/60 Hz).
- Built-in RS485 communication support for remote breaker control and status feedback.
- 2000 V AC 50 Hz dielectric withstand on P1/P2 power terminals (for 220 V / 380 V models).
- Direct bolt-on front mounting matches VIOX VM6 family mounting hole geometry.
모델
| 모델 | Target MCCB Frame | Body A × W (mm) | Total Height H (mm) | Control Voltages |
|---|---|---|---|---|
| DC6-125 | 125 A Frame | 130 × 75 | 140 | AC/DC 220V · 380V · DC 24V |
| DC6-160 | 160 A Frame | 155 × 90 | 151 | AC/DC 220V · 380V · DC 24V |
| DC6-250 | 250 A Frame | 165 × 105 | 153.5 | AC/DC 220V · 380V · DC 24V |
| DC6-400 | 400 A Frame | 257 × 140 | 170.5 | AC/DC 220V · 380V · DC 24V |
| DC6-630 | 630 A Frame | 257 × 140 | 170.5 | AC/DC 220V · 380V · DC 24V |
| DC6-800 | 800 A Frame | 275.5 × 210 | 190.5 | AC/DC 220V · 380V · DC 24V |
| DC6-1250 | 1250 A Frame | 275.5 × 210 | 190.5 | AC/DC 220V · 380V · DC 24V |
| DC6-2000 | 2000 A Frame | 340 × 210 | 225 | AC/DC 220V · 380V · DC 24V |
사양
Detailed Mounting Dimensions (mm)
| 모델 | A1 / A2 | W1 / W2 | H1 / H2 / H3 |
|---|---|---|---|
| DC6-125 | 122 / 109.5 | 90 / 25 | 78.5 / 62 / 34.2 |
| DC6-160 | 144 / 109.5 | 90 / 30 | 76 / 62 / 34.2 |
| DC6-250 | 149.6 / 114 | 105 / 35 | 72 / 59 / 29.5 |
| DC6-400 / 630 | 212 / 177 | 140 / 44 | 74 / 61 / 32.5 |
| DC6-800 / 1250 | 264 / 174 | 210 / 70 | 93 / 78 / 45 |
| DC6-2000 | — / 174 | 210 / 70 | — / 78 / 45 |
선택 가이드
| 코드 위치 | 의미 | Catalog Value or Options |
|---|---|---|
| DC6 | 시리즈 | Electromagnet electric operating mechanism for VIOX MCCBs |
| 125–2000 | Frame match | Matches VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, VM6ELY frames |
| P1/P2 & S1/S2/S4 | Terminal wiring | P1/P2: Power supply · S1: Common · S2: Close · S4: Open |
1. Match MCCB Frame
Select the exact DC6 size (125 to 2000) matching your VIOX MCCB frame.
2. Confirm Coil Supply
Specify AC/DC 220 V, AC/DC 380 V, or DC 24 V control voltage.
3. Follow Wiring Rules
Keep P1/P2 power terminals strictly isolated from S1/S2/S4 control inputs.
4. Order Factory-Mounted
Specify Operation Code P2 on any VM6/VM6E order for pre-mounted delivery.
설치
- When operating manually, rotate 180° clockwise only—counterclockwise manual operation is prohibited.
- Never connect P1/P2 power supply terminals to S1 (common), S2 (close), or S4 (open) control terminals.
- Do not apply 2000 V dielectric withstand test to DC 24 V rated mechanisms.
- Pair with VM6 나 VM6E MCCBs.
자주 묻는 질문
Which VIOX MCCB series are compatible with DC6?
DC6 fits all 8 frame sizes (125 A to 2000 A) across VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, and VM6ELY.
What control voltages does DC6 support?
AC/DC 220 V, AC/DC 380 V, and DC 24 V at 50/60 Hz.
How are the DC6 control terminals wired?
P1 and P2 connect to the operating power supply; S1 is the common control terminal, S2 triggers closing, and S4 triggers opening. Never bridge P1/P2 to S1/S2/S4.
Can DC6 be operated manually during maintenance?
Yes. Switch to Manual mode and rotate 180° clockwise only (counterclockwise rotation is prohibited).
Does DC6 support RS485 communication?
Yes. DC6 supports RS485 communication for automated panel integration.
How do I order DC6 pre-installed on a VIOX MCCB?
Specify operation code P2 in the MCCB ordering code along with your required control voltage.