VIOX DC6 Series Electric Operating Mechanism for MCCB (125A–2000A Frames)

VIOX DC6 Series Electromagnet Electric Operating Mechanism fits all 8 VIOX MCCB frame sizes from 125 A to 2000 A (AC/DC 220 V, AC/DC 380 V, DC 24 V; 50/60 Hz) with compact front-mount integration, ON/TRIPPED/OFF status indication, manual override, and optional RS485 communication.

Compatible Frames
125–2000 A (All 8 VM6 Frames)
Control Voltages
AC/DC 220 V · 380 V · DC 24 V
Mechanizmus típusa
Compact Electromagnet Drive
Smart Feature
RS485 Comm · Manual/Auto Switch

Áttekintés

The VIOX DC6 Series is a compact electromagnet-type electric operating mechanism engineered to motorize VIOX VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, and VM6ELY molded case circuit breakers from 125 A through 2000 A. Supporting AC/DC 220 V, AC/DC 380 V, and DC 24 V control supplies (50/60 Hz) with dedicated P1/P2 power terminals, S1/S2/S4 control inputs, ON/TRIPPED/OFF visual status, manual/auto selector, and RS485 communication, DC6 enables reliable remote switching and SCADA automation.

Jellemzők

  • Complete 8-frame compatibility: DC6-125, 160, 250, 400, 630, 800, 1250, and 2000 A.
  • Fast, compact electromagnet mechanism with integrated ON / TRIPPED / OFF indicator and Manual/Auto lock.
  • Wide control voltage options: AC/DC 220 V, AC/DC 380 V, and DC 24 V (50/60 Hz).
  • Built-in RS485 communication support for remote breaker control and status feedback.
  • 2000 V AC 50 Hz dielectric withstand on P1/P2 power terminals (for 220 V / 380 V models).
  • Direct bolt-on front mounting matches VIOX VM6 family mounting hole geometry.

Modellek

ModellTarget MCCB FrameBody A × W (mm)Total Height H (mm)Control Voltages
DC6-125125 A Frame130 × 75140AC/DC 220V · 380V · DC 24V
DC6-160160 A Frame155 × 90151AC/DC 220V · 380V · DC 24V
DC6-250250 A Frame165 × 105153.5AC/DC 220V · 380V · DC 24V
DC6-400400 A Frame257 × 140170.5AC/DC 220V · 380V · DC 24V
DC6-630630 A Frame257 × 140170.5AC/DC 220V · 380V · DC 24V
DC6-800800 A Frame275.5 × 210190.5AC/DC 220V · 380V · DC 24V
DC6-12501250 A Frame275.5 × 210190.5AC/DC 220V · 380V · DC 24V
DC6-20002000 A Frame340 × 210225AC/DC 220V · 380V · DC 24V

Műszaki adatok

Detailed Mounting Dimensions (mm)

ModellA1 / A2W1 / W2H1 / H2 / H3
DC6-125122 / 109.590 / 2578.5 / 62 / 34.2
DC6-160144 / 109.590 / 3076 / 62 / 34.2
DC6-250149.6 / 114105 / 3572 / 59 / 29.5
DC6-400 / 630212 / 177140 / 4474 / 61 / 32.5
DC6-800 / 1250264 / 174210 / 7093 / 78 / 45
DC6-2000— / 174210 / 70— / 78 / 45

Kiválasztási útmutató

KódpozícióJelentéseCatalog Value or Options
DC6SorozatElectromagnet electric operating mechanism for VIOX MCCBs
125–2000Frame matchMatches VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, VM6ELY frames
P1/P2 & S1/S2/S4Terminal wiringP1/P2: Power supply · S1: Common · S2: Close · S4: Open

1. Match MCCB Frame

Select the exact DC6 size (125 to 2000) matching your VIOX MCCB frame.

2. Confirm Coil Supply

Specify AC/DC 220 V, AC/DC 380 V, or DC 24 V control voltage.

3. Follow Wiring Rules

Keep P1/P2 power terminals strictly isolated from S1/S2/S4 control inputs.

4. Order Factory-Mounted

Specify Operation Code P2 on any VM6/VM6E order for pre-mounted delivery.

Telepítés

  • When operating manually, rotate 180° clockwise only—counterclockwise manual operation is prohibited.
  • Never connect P1/P2 power supply terminals to S1 (common), S2 (close), or S4 (open) control terminals.
  • Do not apply 2000 V dielectric withstand test to DC 24 V rated mechanisms.
  • Pair with VM6 vagy VM6E MCCBs.

GYIK

Which VIOX MCCB series are compatible with DC6?

DC6 fits all 8 frame sizes (125 A to 2000 A) across VM6, VM6AL, VM6RT, VM6LY, VM6E, VM6EY, and VM6ELY.

What control voltages does DC6 support?

AC/DC 220 V, AC/DC 380 V, and DC 24 V at 50/60 Hz.

How are the DC6 control terminals wired?

P1 and P2 connect to the operating power supply; S1 is the common control terminal, S2 triggers closing, and S4 triggers opening. Never bridge P1/P2 to S1/S2/S4.

Can DC6 be operated manually during maintenance?

Yes. Switch to Manual mode and rotate 180° clockwise only (counterclockwise rotation is prohibited).

Does DC6 support RS485 communication?

Yes. DC6 supports RS485 communication for automated panel integration.

How do I order DC6 pre-installed on a VIOX MCCB?

Specify operation code P2 in the MCCB ordering code along with your required control voltage.

2026 Technical Catalog · Online PDF
VIOX Full 18-Series MCCB & Intelligent Breaker Catalog
Open the complete 18-series catalog online for frame dimensions, time-current trip curves, wiring schematics, and factory order codes (PDF · 26.7 MB).
Open Full Catalog PDF ↗

Termékajánlatot kérne?
Építsük fel együtt.

Küldje el nekünk a termékmodelljét, a műszaki jellemzőket, a mennyiséget és az OEM-követelményeket. Csapatunk áttekinti az alkalmazást, és egy munkanapon belül válaszol.

Kérjen Árajánlatot