VIOX VSP-60 / VSP-80 / VSP-100 / VSP-160 High-Capacity AC Type 2 SPD (60–160kA)

The VIOX VSP-60, VSP-80, VSP-100, and VSP-160 series deliver heavy-duty AC Type 2 surge protection from Imax 60 kA up to 160 kA (8/20 μs) for main industrial switchboards, exposed overhead-line feeders, and high-keraunic commercial installations. Built with high-energy MOV stacks, <25 ns response, and optional remote signaling across 385 V and 440 V AC networks.

سلسلة VIOX
VSP-60 / VSP-80 / VSP-100 / VSP-160
الجهد المقنن
AC 385V / 440V
Surge Rating
In 30–100 kA · Imax 60–160 kA
قياسي
IEC 61643-11 · TUV / CE / CB

نظرة عامة

The VIOX VSP-60, VSP-80, VSP-100, and VSP-160 series deliver heavy-duty AC Type 2 surge protection from Imax 60 kA up to 160 kA (8/20 μs) for main industrial switchboards, exposed overhead-line feeders, and high-keraunic commercial installations. Built with high-energy MOV stacks, <25 ns response, and optional remote signaling across 385 V and 440 V AC networks.

الميزات

  • Four heavy-duty Type 2 discharge tiers: VSP-60 (In 30 / Imax 60 kA), VSP-80 (40/80 kA), VSP-100 (60/100 kA), and VSP-160 (100/160 kA).
  • Rated for Uc 385 V and 440 V AC to handle harsh industrial mains and transformer secondary fluctuations.
  • Fast <25 ns clamping with Up ≤2.2–3.0 kV and built-in thermal disconnection mechanism.
  • Supports 1P, 1+NPE, 2P, 3P, 4P, and 3+NPE wiring across TN-S, TN-C, and TT power systems.
  • Coordinated with VIOX VSP-SSD80 and VSP-SSD160 dedicated SPD backup disconnectors.

المواصفات

VSP-60 / VSP-80 / VSP-100 / VSP-160 Electrical & Mechanical Specifications

المعلمةالمواصفات
SPD ClassificationType 2 (Class II) Heavy-Duty · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)385 V / 440 V AC
Nominal Discharge Current (In, 8/20 μs)VSP-60: 30 kA · VSP-80: 40 kA · VSP-100: 60 kA · VSP-160: 100 kA
Max Discharge Current (Imax, 8/20 μs)VSP-60: 60 kA · VSP-80: 80 kA · VSP-100: 100 kA · VSP-160: 160 kA
مستوى حماية الجهد (Up)VSP-60: ≤2.2/2.5 kV · VSP-80/100/160: ≤2.5/3.0 kV
Response Time (tA)<25 ns
Recommended Backup SCBVSP-SSD80 (for 60–80 kA) · VSP-SSD160 (for 100–160 kA)
Conductor Cross-SectionLine ≥10–16 mm² · Earth ≥16 mm² · Terminals 6–25 mm² (2.5 N·m)
Housing & EnvironmentPBT / PA UL94 V-0 · IP20 · -40°C to +70°C · 35 mm DIN rail
الشهاداتTUV, CE, CB, UKCA, RoHS

VSP-60 / VSP-80 / VSP-100 / VSP-160 Available Poles & Dimensions

Model Tier1P1+NPE / 2P3P4P / 3+NPE
VSP-60 / VSP-8018 × 90 × 67 mm36 × 90 × 67 mm54 × 90 × 67 mm72 × 90 × 67 mm
VSP-100 / VSP-16036 × 90 × 68 mm72 × 90 × 68 mm108 × 90 × 68 mm144 × 90 × 68 mm

الأبعاد والتركيب

VIOX VSP-60 / VSP-80 / VSP-100 / VSP-160 High-Capacity AC Type 2 SPD (60–160kA) Dimensional Drawing (mm)
VSP-60 / VSP-80 / VSP-100 / VSP-160 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Pair VSP-80 with VIOX VSP-SSD80 and VSP-100/160 with VIOX VSP-SSD160 so backup breakers never nuisance-trip during 80–160 kA surge events.
  • Use ≥16 mm² copper earth bonding cable directly to the main equipotential bonding bar.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

الأسئلة الشائعة

When should I specify 80–160kA Type 2 instead of standard 40kA?

Use VSP-60 through VSP-160 at main distribution boards fed by overhead lines or in tropical/high-lightning-density regions where repeated high-energy induced surges quickly exhaust 40 kA cartridges.