VIOX ELECTRIC
Sprache

VIOX VSP-60 / VSP-80 / VSP-100 / VSP-160 High-Capacity AC Type 2 SPD (60–160kA)

The VIOX VSP-60, VSP-80, VSP-100, and VSP-160 series deliver heavy-duty AC Type 2 surge protection from Imax 60 kA up to 160 kA (8/20 μs) for main industrial switchboards, exposed overhead-line feeders, and high-keraunic commercial installations. Built with high-energy MOV stacks, <25 ns response, and optional remote signaling across 385 V and 440 V AC networks.

VIOX Serie
VSP-60 / VSP-80 / VSP-100 / VSP-160
Nennspannung
AC 385V / 440V
Surge Rating
In 30–100 kA · Imax 60–160 kA
Standard
IEC 61643-11 · TUV / CE / CB

Übersicht

The VIOX VSP-60, VSP-80, VSP-100, and VSP-160 series deliver heavy-duty AC Type 2 surge protection from Imax 60 kA up to 160 kA (8/20 μs) for main industrial switchboards, exposed overhead-line feeders, and high-keraunic commercial installations. Built with high-energy MOV stacks, <25 ns response, and optional remote signaling across 385 V and 440 V AC networks.

Eigenschaften

  • Four heavy-duty Type 2 discharge tiers: VSP-60 (In 30 / Imax 60 kA), VSP-80 (40/80 kA), VSP-100 (60/100 kA), and VSP-160 (100/160 kA).
  • Rated for Uc 385 V and 440 V AC to handle harsh industrial mains and transformer secondary fluctuations.
  • Fast <25 ns clamping with Up ≤2.2–3.0 kV and built-in thermal disconnection mechanism.
  • Supports 1P, 1+NPE, 2P, 3P, 4P, and 3+NPE wiring across TN-S, TN-C, and TT power systems.
  • Coordinated with VIOX VSP-SSD80 and VSP-SSD160 dedicated SPD backup disconnectors.

Spezifikationen

VSP-60 / VSP-80 / VSP-100 / VSP-160 Electrical & Mechanical Specifications

ParameterSpezifikation
SPD ClassificationType 2 (Class II) Heavy-Duty · IEC 61643-11 / EN 61643-11
Max Continuous Operating Voltage (Uc)385 V / 440 V AC
Nominal Discharge Current (In, 8/20 μs)VSP-60: 30 kA · VSP-80: 40 kA · VSP-100: 60 kA · VSP-160: 100 kA
Max Discharge Current (Imax, 8/20 μs)VSP-60: 60 kA · VSP-80: 80 kA · VSP-100: 100 kA · VSP-160: 160 kA
Spannungs-Schutzpegel (Up)VSP-60: ≤2.2/2.5 kV · VSP-80/100/160: ≤2.5/3.0 kV
Response Time (tA)<25 ns
Recommended Backup SCBVSP-SSD80 (for 60–80 kA) · VSP-SSD160 (for 100–160 kA)
Conductor Cross-SectionLine ≥10–16 mm² · Earth ≥16 mm² · Terminals 6–25 mm² (2.5 N·m)
Housing & EnvironmentPBT / PA UL94 V-0 · IP20 · -40°C to +70°C · 35 mm DIN rail
ZertifizierungenTUV, CE, CB, UKCA, RoHS

VSP-60 / VSP-80 / VSP-100 / VSP-160 Available Poles & Dimensions

Model Tier1P1+NPE / 2P3P4P / 3+NPE
VSP-60 / VSP-8018 × 90 × 67 mm36 × 90 × 67 mm54 × 90 × 67 mm72 × 90 × 67 mm
VSP-100 / VSP-16036 × 90 × 68 mm72 × 90 × 68 mm108 × 90 × 68 mm144 × 90 × 68 mm

Größe und aufbau

VIOX VSP-60 / VSP-80 / VSP-100 / VSP-160 High-Capacity AC Type 2 SPD (60–160kA) Dimensional Drawing (mm)
VSP-60 / VSP-80 / VSP-100 / VSP-160 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Pair VSP-80 with VIOX VSP-SSD80 and VSP-100/160 with VIOX VSP-SSD160 so backup breakers never nuisance-trip during 80–160 kA surge events.
  • Use ≥16 mm² copper earth bonding cable directly to the main equipotential bonding bar.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

FAQ

When should I specify 80–160kA Type 2 instead of standard 40kA?

Use VSP-60 through VSP-160 at main distribution boards fed by overhead lines or in tropical/high-lightning-density regions where repeated high-energy induced surges quickly exhaust 40 kA cartridges.

Benötigen Sie ein Produktangebot?
Lassen Sie es uns gemeinsam aufbauen.

Senden Sie uns das Produktmodell, die technischen Nennwerte, die Menge und die OEM-Anforderungen. Unser Team wird Ihre Anwendung prüfen und innerhalb eines Werktages antworten.

Angebot anfordern