Áttekintés
The VIOX VSP-60, VSP-80, VSP-100, and VSP-160 series deliver heavy-duty AC Type 2 surge protection from Imax 60 kA up to 160 kA (8/20 μs) for main industrial switchboards, exposed overhead-line feeders, and high-keraunic commercial installations. Built with high-energy MOV stacks, <25 ns response, and optional remote signaling across 385 V and 440 V AC networks.
Jellemzők
- Four heavy-duty Type 2 discharge tiers: VSP-60 (In 30 / Imax 60 kA), VSP-80 (40/80 kA), VSP-100 (60/100 kA), and VSP-160 (100/160 kA).
- Rated for Uc 385 V and 440 V AC to handle harsh industrial mains and transformer secondary fluctuations.
- Fast <25 ns clamping with Up ≤2.2–3.0 kV and built-in thermal disconnection mechanism.
- Supports 1P, 1+NPE, 2P, 3P, 4P, and 3+NPE wiring across TN-S, TN-C, and TT power systems.
- Coordinated with VIOX VSP-SSD80 and VSP-SSD160 dedicated SPD backup disconnectors.
Műszaki adatok
VSP-60 / VSP-80 / VSP-100 / VSP-160 Electrical & Mechanical Specifications
| Paraméter | Specifikáció |
|---|---|
| SPD Classification | Type 2 (Class II) Heavy-Duty · IEC 61643-11 / EN 61643-11 |
| Max Continuous Operating Voltage (Uc) | 385 V / 440 V AC |
| Nominal Discharge Current (In, 8/20 μs) | VSP-60: 30 kA · VSP-80: 40 kA · VSP-100: 60 kA · VSP-160: 100 kA |
| Max Discharge Current (Imax, 8/20 μs) | VSP-60: 60 kA · VSP-80: 80 kA · VSP-100: 100 kA · VSP-160: 160 kA |
| Feszültségvédelmi szint (Up) | VSP-60: ≤2.2/2.5 kV · VSP-80/100/160: ≤2.5/3.0 kV |
| Response Time (tA) | <25 ns |
| Recommended Backup SCB | VSP-SSD80 (for 60–80 kA) · VSP-SSD160 (for 100–160 kA) |
| Conductor Cross-Section | Line ≥10–16 mm² · Earth ≥16 mm² · Terminals 6–25 mm² (2.5 N·m) |
| Housing & Environment | PBT / PA UL94 V-0 · IP20 · -40°C to +70°C · 35 mm DIN rail |
| Tanúsítványok | TUV, CE, CB, UKCA, RoHS |
VSP-60 / VSP-80 / VSP-100 / VSP-160 Available Poles & Dimensions
| Model Tier | 1P | 1+NPE / 2P | 3P | 4P / 3+NPE |
|---|---|---|---|---|
| VSP-60 / VSP-80 | 18 × 90 × 67 mm | 36 × 90 × 67 mm | 54 × 90 × 67 mm | 72 × 90 × 67 mm |
| VSP-100 / VSP-160 | 36 × 90 × 68 mm | 72 × 90 × 68 mm | 108 × 90 × 68 mm | 144 × 90 × 68 mm |
Méretek és telepítés

- Pair VSP-80 with VIOX VSP-SSD80 and VSP-100/160 with VIOX VSP-SSD160 so backup breakers never nuisance-trip during 80–160 kA surge events.
- Use ≥16 mm² copper earth bonding cable directly to the main equipotential bonding bar.
- Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.
GYIK
When should I specify 80–160kA Type 2 instead of standard 40kA?
Use VSP-60 through VSP-160 at main distribution boards fed by overhead lines or in tropical/high-lightning-density regions where repeated high-energy induced surges quickly exhaust 40 kA cartridges.