The VIOX VM6RT Series (including VM6RT double-adjustable, VM6RT/A thermal-adjustable, and VM6RT/P magnetic-adjustable) bridges fixed thermomagnetic breakers and electronic trip units across 8 industrial frames from 125 A to 2000 A (16 A–1600 A rated current, 3P/4P, AC 400 V). Front-mounted rotary dials let panel builders fine-tune thermal overload protection from 0.8–1.0×In and instantaneous magnetic tripping from 5–10×In on site, simplifying spare-part inventory and feeder selectivity up to 100 kA Icu / 85 kA Ics.
الميزات
- Field-adjustable thermal overload setting (0.8–1.0×In) and adjustable magnetic instantaneous pickup (5–10×In).
- 8 industrial frames from VM6RT/A-125 through VM6RT-2000 (16 A–1600 A rated currents, 3P/4P).
- Breaking capacity up to 100 kA Icu / 85 kA Ics at AC 400 V (VM6RT-2000H) and 85 kA Icu / 65 kA Ics (800/1250 A H).
- Multi-contact blade design delivers low temperature rise and compact enclosure footprint.
- Ui 1000 V, Uimp 8 kV, Selectivity Category Class A per IEC/EN 60947-2.
- Full compatibility with DC3/DC6 motor operators, rotary handles, plug-in/draw-out bases, and internal codes 00–78.
النماذج
| Frame Series | Rated Current In (A) | Breaking Tiers | القطبين | Max Icu / Ics (400 V AC) |
|---|---|---|---|---|
| VM6RT/A-125 | 16, 20, 25, 32, 40, 50, 63, 80, 100, 125 A | C, S, M, H | 3P, 4P | 50 kA / 50 kA |
| VM6RT-160 | 25, 32, 40, 50, 63, 80, 100, 125, 140, 160 A | C, S, M, H | 3P, 4P | 50 kA / 50 kA |
| VM6RT-250 | 100, 125, 140, 160, 180, 200, 225, 250 A | C, S, M, H | 3P, 4P | 50 kA / 50 kA |
| VM6RT-400 | 315, 320, 350, 400 A | M, H | 3P, 4P | 50 kA / 50 kA |
| VM6RT-630 | 400, 500, 630 A | M, H | 3P, 4P | 50 kA / 50 kA |
| VM6RT-800 | 630, 700, 800 A | M, H | 3P, 4P | 85 kA / 65 kA |
| VM6RT-1250 | 1000, 1250 A | M, H | 3P, 4P | 85 kA / 65 kA |
| VM6RT-2000 | 1600 A | M, H | 3P, 4P | 100 kA / 85 kA |
المواصفات
Breaking Capacity (AC 400 V)
| Frame & Tiers | Ics (400 V) | Icu (400 V) | نطاق الضبط |
|---|---|---|---|
| VM6RT/A-125 C / S / M / H | 5 / 10 / 18 / 50 kA | 10 / 20 / 36 / 50 kA | Thermal 0.8–1.0×In |
| VM6RT-160 C / S / M / H | 5 / 10 / 10 / 50 kA | 8 / 20 / 20 / 50 kA | Thermal 0.8–1.0×In · Mag 5–10×In |
| VM6RT-250 C / S / M / H | 5 / 8 / 10 / 50 kA | 8 / 15 / 20 / 50 kA | Thermal 0.8–1.0×In · Mag 5–10×In |
| VM6RT-400 / 630 M / H | 50 / 50 kA | 50 / 50 kA | Thermal 0.8–1.0×In · Mag 5–10×In |
| VM6RT-800 / 1250 M / H | 50 / 65 kA | 65 / 85 kA | Thermal 0.8–1.0×In · Mag 5–10×In |
| VM6RT-2000 M / H | 50 / 85 kA | 50 / 100 kA | Thermal 0.8–1.0×In · Mag 5–10×In |
Outline Dimensions (mm)
| إطار | القطبين | Width W (mm) | Length L (mm) | Height Cover / Handle (mm) |
|---|---|---|---|---|
| VM6RT/A-125 | 3P / 4P | 75 / 100 | 130 | 68 / 94.5 |
| VM6RT-160 | 3P / 4P | 90 / 120 | 155 | 68–82 / 94–108 |
| VM6RT-250 | 3P / 4P | 105 / 140 | 165 | 68–88 / 96–116 |
| VM6RT-400 / 630 | 3P / 4P | 140 / 184 | 257 | 103 / 152 |
| VM6RT-800 / 1250 | 3P / 4P | 210 / 280 | 275.5 | 103 / 152 |
| VM6RT-2000 | 3P / 4P | 210 / 280 | 340 | 141 / 244 |
External Accessories Compatibility
| ملحق | Supported Frames & Poles |
|---|---|
| Electric Motor Operation | 3P, 4P |
| Manual Rotary Handle (ZY1/ZF1/ZY2/ZF2/Z3) | 3P, 4P |
| Extension Copper Bar (P) | 3P, 4P |
| التشابك الميكانيكي | 3P, 4P (up to 800 A) |
| Plug-in Front / Back Panel (Z2Q/Z2H/Z3Q/Z3H) | 3P, 4P (up to 800 A) |
| Draw-out Back-Panel (DR) | 400 / 630 / 800 A (3P only) |
دليل الاختيار
| موقع الكود | المعنى | Catalog Value or Options |
|---|---|---|
| VM6RT / RT-A / RT-P | السلسلة | Double-adjustable (RT), thermal-adjustable (RT-A), or magnetic-adjustable (RT-P) |
| 125–2000 | تيار الإطار | 125 (RT/A only), 160, 250, 400, 630, 800, 1250, 2000 A |
| C / S / M / H | Breaking tier | C/S/M/H on 125–250 A; M/H on 400–2000 A |
| 3 / 4 | القطبين | 3P or 4P (Neutral Types A, B, C, D) |
| 00–78 | Internal accessory code | 00 None · 08 Alarm · 10 Shunt · 18 Shunt+Alarm · 20/27 Aux · 28/29 Aux+Alarm · 30 UVT · 38 UVT+Alarm · 40/41/48 Shunt+Aux · 50 Shunt+UVT · 60–69 Multi-Aux · 70–78 UVT+Aux (DC 24/110/220 V, AC 230/400 V) |
1. Tune to Actual Load
Dial thermal Ir (0.8–1.0×In) to match cable ampacity or seasonal load growth without swapping breakers.
2. Coordinate Inrush
Set magnetic pickup (5–10×In) above motor or transformer starting inrush while keeping fast fault clearance.
3. Reduce SKU Stock
One adjustable VM6RT frame replaces multiple fixed-rating spares for distributors and panel shops.
4. Add Switchgear Kits
Pair with rotary handles, DC3/DC6 motor operators, or plug-in/draw-out bases.
التركيب
- Adjust the front thermal (0.8–1.0×In) and magnetic (5–10×In) dials with a flathead driver before energizing.
- Seal the transparent dial cover after commissioning to prevent unauthorized field tampering.
- Verify frame cutout dimensions (same footprint as VM6 standard series across all 8 frames).
- Compare with fixed VM6 or electronic VM6E on our MCCB hub.
الأسئلة الشائعة
What is the difference between VM6RT, VM6RT-A, and VM6RT-P?
VM6RT provides double adjustment (both thermal 0.8–1.0×In and magnetic 5–10×In); VM6RT-A provides thermal adjustment only (including the 125 A frame); VM6RT-P provides magnetic adjustment only.
Why choose an adjustable thermomagnetic MCCB over a fixed MCCB?
Adjustable dials let engineers tune overload pickup to exact cable ampacity and adjust magnetic pickup for motor inrush, while allowing distributors to stock fewer SKUs.
Does VM6RT share the same mounting footprint as VM6?
Yes. Every VM6RT frame from 125 A to 2000 A shares the exact same W × L × H outline dimensions and external accessory ecosystem as VM6.
What is the maximum breaking capacity of VM6RT?
At AC 400 V, VM6RT reaches 50 kA Icu/Ics up to 630 A, 85 kA Icu / 65 kA Ics on 800–1250 A, and 100 kA Icu / 85 kA Ics on VM6RT-2000H.
Are plug-in and draw-out bases supported on VM6RT?
Yes. Plug-in front/back bases are available from 125 A to 800 A (3P/4P), and draw-out back-panel bases are supported on 400, 630, and 800 A (3P).
Can VM6RT be equipped with shunt and undervoltage releases?
Yes. All internal accessory combinations (codes 08–78) are factory-installable in DC 24/110/220 V and AC 230/400 V.