VIOX ELECTRIC
Ngôn ngữ

VIOX VSP-15T/G1000 / G1500 Solar PV DC Type 1+2 Lightning Arrester (1000V / 1500V)

The VIOX VSP-15T/G1000 (1000 V DC) and VSP-15T/G1500 (1500 V DC) are heavy-duty IEC 61643-31 Type 1 + Type 2 solar photovoltaic lightning current arresters engineered for utility-scale solar farms and commercial rooftops equipped with external lightning protection systems (LPS). Rated for Iimp 6.25 kA (10/350 μs) and Imax 40 kA (8/20 μs) in a fault-tolerant Type Y (3P) 108 mm DIN-rail chassis.

Dòng VIOX
VSP-15T/G1000 / G1500
Điện áp định mức
1000V DC / 1500V DC
Surge Rating
Iimp 6.25 kA (10/350μs) · Imax 40 kA
Chuẩn
IEC 61643-31 · T1+T2 PV · CE / CB

Tổng quan

The VIOX VSP-15T/G1000 (1000 V DC) and VSP-15T/G1500 (1500 V DC) are heavy-duty IEC 61643-31 Type 1 + Type 2 solar photovoltaic lightning current arresters engineered for utility-scale solar farms and commercial rooftops equipped with external lightning protection systems (LPS). Rated for Iimp 6.25 kA (10/350 μs) and Imax 40 kA (8/20 μs) in a fault-tolerant Type Y (3P) 108 mm DIN-rail chassis.

Đặc trưng

  • IEC 61643-31 Type 1 + Type 2 DC lightning arrester rated Iimp 6.25 kA (10/350 μs), In 20 kA, and Imax 40 kA (8/20 μs).
  • Dedicated 1000 V DC (Up 3.5 kV) and 1500 V DC (Up 5.5 kV) ratings for ground-mount and commercial C&I solar plants with external LPS.
  • 3-pole Type Y (DC+ / PE / DC-) pluggable architecture with DC arc-quenching thermal disconnectors and remote signaling (11/12/14).
  • Heavy-duty 36 mm/pole (108 × 90 × 72 mm) housing with 6–35 mm² terminals.

Thông số kỹ thuật

VSP-15T/G1000 / G1500 Electrical & Mechanical Specifications

Tham sốĐặc điểm kỹ thuật
SPD ClassificationPV Type 1 + Type 2 (T1+T2) DC · IEC 61643-31 / EN 50539-11
Max Continuous Operating Voltage (Ucpv)1000 V DC (VSP-15T/G1000) · 1500 V DC (VSP-15T/G1500)
Lightning Impulse Current (Iimp, 10/350 μs)6.25 kA (per pole) / 12.5 kA (total)
Nominal / Max Discharge Current (8/20 μs)In 20 kA · Imax 40 kA
Mức bảo vệ điện áp (Up)1000V DC: 3.5 kV · 1500V DC: 5.5 kV
Topology & ResponseType Y (3P: DC+ / PE / DC-) · <25 ns · Icpv ≤0.2 mA
Dimensions & Terminals108 × 90 × 72 mm · 6–35 mm² (2.5 N·m) · 35 mm DIN rail · IP20
Chứng nhậnCE, CB, UKCA, RoHS

VSP-15T/G1000 / G1500 Available Poles & Dimensions

Người mẫuCấu trúc liên kếtDimensions (W × H × D)
VSP-15T/G1000Type Y (3P)108 × 90 × 72 mm
VSP-15T/G1500Type Y (3P)108 × 90 × 72 mm

Kích thước & Lắp đặt

VIOX VSP-15T/G1000 / G1500 Solar PV DC Type 1+2 Lightning Arrester (1000V / 1500V) Dimensional Drawing (mm)
VSP-15T/G1000 / G1500 Outline & DIN-Rail Mounting Dimensions (unit: mm)
  • Required wherever PV array frames are bonded to an external lightning protection system (LPS) or separation distance s cannot be maintained.
  • Connect PE terminal to the main equipotential bonding bar using ≥16 mm² copper conductor.
  • Explore the complete VIOX Surge Protection Devices (SPD) catalog for matched AC, Solar PV DC, and SCB backup protection.

Câu hỏi thường gặp

When do I need PV Type 1+2 (VSP-15T/G) instead of PV Type 2 (VSP-40/G)?

Specify VSP-15T/G whenever the building or solar plant has an external lightning protection system (lightning rods/mesh) or direct-strike exposure, as Type 2 SPDs are not tested for 10/350 μs partial lightning currents.

Cần báo giá sản phẩm?
Hãy cùng chúng tôi thực hiện dự án này.

Gửi cho chúng tôi mã sản phẩm, các định mức kỹ thuật, số lượng và yêu cầu OEM. Đội ngũ của chúng tôi sẽ xem xét ứng dụng của bạn và phản hồi trong vòng một ngày làm việc.

Yêu cầu báo giá