Thiết bị phát hiện hồ quang điện từ VAF3-40M

The VIOX VAF3-40M magnetic arc fault detection device combines arc-fault detection with Type A residual-current, overload and short-circuit protection. Designed for 240 V AC, 50 Hz final circuits, it is available in 6-40 A ratings, B or C tripping characteristics and 10 or 30 mA sensitivities for residential and commercial installations.

Bình Hiện Tại
6-40 A
Dòng rò (Residual Current)
10, 30 mA
Tripping Characteristic
B, C
-Chập Hiện Tại
6 kA

Tổng quan

The VAF3-40M is a magnetic arc fault detection device combining arc-fault detection with Type A residual-current, overload and short-circuit protection. Designed for AC 50 Hz final circuits, it has a rated voltage of 240 V AC and is available in rated currents from 6 A to 40 A. The 1P+N device offers B or C overcurrent tripping characteristics and 10 mA or 30 mA residual-current sensitivities. It is intended for residential and commercial final circuits requiring combined protection against arc faults, electric shock, overload and short circuits.

Đặc trưng

  • Magnetic version with integrated arc-fault, Type A residual-current, overload and short-circuit protection.
  • Compliant with IEC/EN 61009-1 and IEC/EN 62606.
  • Rated-current options from 6 A to 40 A.
  • B and C overcurrent tripping characteristics.
  • 10 mA and 30 mA residual-current sensitivities.
  • Load-disconnect contact with 6 kA rated short-circuit current.

Thông số kỹ thuật

Electrical Data

Tham số Đặc điểm kỹ thuật
Dòng điện định mức (In) 6, 10, 13, 16, 20, 25, 32, 40 A
Điện áp định mức (Ue) 240 V AC
Tần suất hoạt động 50 Hz
Minimum test-circuit operating voltage 196 V
Maximum test-circuit operating voltage 253 V
Điện áp cách điện định mức (Ui) 250 V
Điện áp chịu xung định mức (Uimp) 4 kV
Dòng điện ngắn mạch định mức 6 kA
Maximum total rated switching capacity 6 kA
Surge-current withstand strength 0.25 kA
Power loss per current path 3 W
Short-circuit back-up fuse (SCPD) 100 A
Back-up fuse type gG
Loại quá áp III

Protection Data

Tham số Đặc điểm kỹ thuật
Cấu hình sản phẩm AFDD tích hợp bảo vệ dòng điện dư loại A, bảo vệ quá tải và ngắn mạch
Số cực 1P+N
Loại dòng dư Loại A
Rated residual operating current (IΔn) 10, 30 mA
Overcurrent tripping characteristic B, C
Load-circuit specification Load-disconnect contact

Installation Data

Tham số Đặc điểm kỹ thuật
Loại thiết bị đầu cuối Screw-type terminals; top or bottom connection on the load circuit
Neutral conductor position Left or right
Chiều dài cáp kết nối tối đa 70 m between the distribution board and the furthest socket outlet
Terminal clamping capacity 1-25 mm²
Terminal tightening torque 2-2.4 N·m

Standards Data

Tham số Đặc điểm kỹ thuật
Các tiêu chuẩn áp dụng IEC/EN 61009-1; IEC/EN 62606

Hướng dẫn lựa chọn

Code position Ý nghĩa Catalog reference
V VIOX identification V
AF Arc-fault protection product family AF
3 Design series 3
40 Maximum frame current 40
M Phiên bản từ tính M
C16 C tripping characteristic and rated current 16 giờ sáng
A30 Thiết bị bảo vệ dòng rò loại A 30 mA

Bình Hiện Tại

Select a listed rating from 6 A to 40 A to match the final-circuit rating.

Tripping Characteristic

Select a B or C overcurrent tripping characteristic according to the circuit requirements.

Residual Sensitivity

Select a Type A residual operating-current sensitivity of 10 mA or 30 mA.

Ứng dụng

  • Residential final circuits.
  • Commercial final circuits.
  • Circuits requiring combined arc-fault and electric-shock protection.
  • Circuits requiring combined overload and short-circuit protection.

Cài đặt

  • Use screw-type terminals with top or bottom connection on the load circuit.
  • Confirm whether the selected configuration places the neutral conductor on the left or right.
  • Use conductors within the listed terminal clamping capacity of 1-25 mm².
  • Apply the listed terminal tightening torque of 2-2.4 N·m.
  • Keep the connected cable length within 70 m between the distribution board and the furthest socket outlet.
  • Use the listed 100 A gG short-circuit back-up fuse.

Câu hỏi thường gặp

What distinguishes the VAF3-40M?

The catalog identifies the VAF3-40M as the magnetic version of the arc fault detection device.

Which protection functions are integrated?

It combines arc-fault detection with Type A residual-current, overload and short-circuit protection.

Which rated currents and tripping characteristics are available?

The catalog lists 6, 10, 13, 16, 20, 25, 32 and 40 A ratings with B or C overcurrent tripping characteristics.

Which residual-current sensitivities are offered?

The VAF3-40M provides Type A residual-current protection with 10 mA or 30 mA sensitivity.

What is the rated short-circuit current?

The rated short-circuit current is 6 kA.

Which standards are listed for the VAF3-40M?

The applicable standards are IEC/EN 61009-1 and IEC/EN 62606.